Quest Engineering 506 Installation, Operation And Maintenance Manual - page 4
1-877-420-1330
Quest 506
Installation, Operation and Maintenance Instructions
4
www.QuestHydro.com
info@QuestHydro.com
1. Intended Application for Quest 506 Dehumidifier
The Quest 506 Dehumidifier is designed to operate in temperatures between 56° and 95°F.
In order to efficiently control humidity levels, the area in which the dehumidifier is to be operated must be free of water
intrusion or excessive fresh (outside) air infiltration. Before installing the Quest 506 Dehumidifier, water intrusion and
air infiltration problems should be addressed or noted in calculations.
2. Registrations
The Quest 506 Dehumidifier units conform to unified standard UL 60335-2-40.
3. Specifications @ 80°F/60% RH
Unit:
Quest 506
4036600
Power (Watts):
2700
Supply voltage:
220-240 VAC -
1 Phase - 60 Hz.
Current Draw (Amps):
11.0
Rated Current Draw (Amps):
(104°F 36%)
13.6
Energy Factor (L/kWh):
3.8
Operating Temp:
56°F Min - 95°F Max
Water Removal (Pints/Day):
Efficiency (Pints/kWh):
506
8.1
Air Filter (MERV-13): (2)
Size: 18" x 20" x 2"
Power Cord:
Drain Connection:
3/4 Threaded NPT
Refrigerant Type:
Refrigerant Amount:
R410A
4lb. 8oz.
Dimensions:
Width:
Height:
Length:
Weight:
Unit
Shipping
28.9”
36”
33.8”
40”
44.7”
48”
280 lbs
340 lbs
14ga 10’, NEMA 6-20P