RAB Lighting Mini Sensor Installation Manual - page 5
Assembly and Wiring
1. Screw the threaded arm of the sen-
sor into the center hole of the mounting
plate. Sensors can be wall or ceiling
mounted.
2. If mounting on the same cover
plate as floodlight(s), screw the
threaded arm(s) of each floodlight
into the mounting plate. Leave the
locknuts and arm screws loose until
ready to aim. Always mount the
sensor below lights.
3. Bring power leads and sensor
leads into box.
4. Attach ground wire(s) to outlet
box grounding screw.
5. Strip 1/2” of insulation from all
leads. Connect as shown in Wiring
Diagram.
6. Twist on wire nuts. Secure with
electrical tape.
7. Align gasket to insure proper seal.
Fasten mounting plate with sensor
with two screws provided. Use sili-
cone sealant around all openings, if
necessary.
8. Screw in light bulbs. Turn on power.
9. Conduct Walk Test to adjust
sensor response.
5
Sensor
Red
Black
White
Power In
Basic Wiring Diagram
6
Wiring more than one sensor
together is recommended only for
the experienced installer because it
becomes difficult to troubleshoot.
Single sensors that control their
own lights pinpoint movement more
accurately and operate better.
Sensors should not be installed on
a circuit that also feeds motor
loads such as HVAC equipment,
kitchen appliances, or garage door
openers. If voltage varies signifi-
cantly from 120 volts, sensors
may malfunction.
Wiring Diagrams
To override
sensor with a
manual switch
To switch more than
rated load
(Relay model only)
Hi/Lo sensors can not
accept an auxiliary relay
to increase their switch-
ing capacity.
Multiple Sensors:
Power Quality:
Black
Red
Black
Black
White
White
Power In
Black
Red
White
White
White
Power In
Power In
.1µF
400V DC
Capacitor
Black
Relay rated to
handle load
required