Radionics D2112 Diagnostic Manual

Other manuals for D2112: User Manual, Installation Manual
Manual is about: control/communicator

Summary of D2112

  • Page 1

    1 radionics, inc. 74-07113-000-b 4/94 d2112 keypad diagnostics putting the keypad into the diagnostics mode 1. Lock the d2112's standby switch down. 2. Press the 1 key on the keypad. 3. Enter your “installer” passcode. The default installer passcode is 654321. The default passcode length is 3, so if...

  • Page 2: Bell Test

    2 radionics, inc. 74-07113-000-b 4/94 bell test the bell test powers the external bell with the burglar pattern for 2 seconds. • press ( 1 ) the bell test times out after 2 seconds. Battery test the battery test causes the panel to run on battery only for 4 minutes. During this time if the voltage d...

  • Page 3: Point Status

    3 radionics, inc. 74-07113-000-b 4/94 point status the point status function displays the electrical state of all points. The state of each point is shown with its corresponding light. 1. Press ( 5 ). The lights update every second. Light point state off normal wink open on short 2. Press ( clear ) ...

  • Page 4: Power Supply Status

    4 radionics, inc. 74-07113-000-b 4/94 power supply status (cont'd) to enter the power supply status mode, 1. Press ( 7 ). Light 7 winks to let you know that you’re in the power supply status function. …to display fire alarm load 2. Disconnect the battery. 3. Press ( 1 ). The bell and external relays...

  • Page 5: Current Consumption

    5 radionics, inc. 74-07113-000-b 4/94 current consumption scale ma light maximum fire 860 1 732 2 605 3 477 4 maximum normal 350 5 222 6 95 7 8 alarm load ☛ supervisory load when a test indicates an overload condition, the bar graph flashes. ☛.

  • Page 6: Power Supply Status

    6 radionics, inc. 74-07113-000-b 4/94 power supply status (cont'd from page 4) …to display the minimum battery voltage after 1 minute 2. Make sure the battery is connected. 3. Press ( 2 ). The d2112 automatically disconnects ac. The keypad displays the lowest battery voltage during the test, and giv...

  • Page 7: Battery Voltage

    7 radionics, inc. 74-07113-000-b 4/94 battery voltage scale volts light 13.75 1 minimum battery 13.25 2 12.75 3 read battery 12.25 4 11.75 5 11.25 6 10.75 7 10.25 8 voltage low battery flashes lights 5, 6, 7, 8. ☛ voltage after 1 minute ☛.

  • Page 8: Programming

    8 radionics, inc. 74-07113-000-b 4/94 programming function 8 is the keypad programming mode. For complete instructions on programming from the keypad, see the d2112 control/ communicator program entry guide (74-07112- 000). System troubles this diagnostic check is available in the user's check syste...