Ranger PM3000 Configuration Manual - 3Ø 4W Y Unbal 7Day
PM3000 Power Quality Analyzer Factory Configurations
3ø 4w Y Unbal 7day
24
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Van 480 Volts = 480.0
2 Ia 1000 Amps = 1000.0
3 Vbn 480 Volts = 480.0
4 Ib 1000 Amps = 1000.0
5 Vcn 480 Volts = 480.0
6 Ic 1000 Amps = 1000.0
Alarms
: On
Alarm Values High Low
1
Vac 253.0 216.2
2
Vac 253.0 216.2
3
Vac 253.0 216.2
15
%
2.0
Off
Hook Up
: 3-Phase 4-Wire Wye
Channel Functions
Input Channels
1 Van 0 to 480 Vac
2 Ia 0 to 3000 Aac (Rogowski)
3 Vbn 0 to 480 Vac
4 Ib 0 to 3000 Aac (Rogowski)
5 Vcn 0 to 480 Vac
6 Ic 0 to 3000 Aac (Rogowski)
Detailed (Math) Channels
1 RMS of Signal Van (Vac)
2 RMS of Signal Vbn (Vac)
3 RMS of Signal Vcn (Vac)
4 RMS of Signal Ia (Aac)
5 RMS of Signal Ib (Aac)
6 RMS of Signal Ic (Aac)
7 Real Power Factor (V,A)= Van, Ia (PF)
8 Real Power Factor (V,A)= Vbn, Ib (PF)
9 Real Power Factor (V,A)= Vcn, Ic (PF)
10 3 Phase 4 wire Real Power (Inputs 1,2,3,4,5,6) (kW)
11 3 Phase 4 wire Reactive Power (Inputs 1,2,3,4,5,6) (kVr)
12 3 Phase 4 wire Apparent Power (Inputs 1,2,3,4,5,6) (kVA)
13 3 Phase 4 wire Power Factor (Inputs 1,2,3,4,5,6) (PF)
14 3 Phase %UnBalance on 3 Currents (Inputs 4,5,6) (%)
15 3 Phase Volts NPS-PPS ratio (Inputs 1,2,3) (%)
16 3 Phase Volts NPS-Volts Phase Angle [Inputs 1,2,3] (°)