Raychem H908 Installation instructions manual

Manual is about: WinterGard Plug-in Power Connection Kit with End Seal

Summary of H908

  • Page 1

    Installation instructions h908 wintergard plug-in power connection kit with end seal description the h908 is a plug-in, ground-fault-protected power connection kit for use with wintergard h311, h611, and h612 120-v heating cables. This kit ensures compliance with raychem and nec requirements for gro...

  • Page 2

    2 h908 design and installation information for heating cable on pipes only (wintergard h311, h611, and h612 heating cables) table 1. For metal pipes with fiberglass insulation or equivalent (based on 40°f maintain temperature, 10% safety factor) articles 422 and 427 of the national electrical code g...

  • Page 3

    3 2. Calculate the total heating cable length. Pipe length × spiraling ratio + 4 ft × # gate/globe valves × valve length (ft) × spiraling ratio + 2 ft × # ball/butterfly valves × valve length (ft) × spiraling ratio + 2 ft × # flanges × pipe diameter (ft) × spiraling ratio + 2 ft × # pipe supports × ...

  • Page 4

    4 table 4. Product data—wintergard products on pipe only heating cable type wintergard wintergard plus wintergard wet h311 h611 h612 service voltage (v) 120 120 120 thermal output at 40°f (w/ft) 3 6 6 weight per 100 ft (lb) 6 6 9 minimum installation temp. (°f) 0 0 0 maximum exposure temp. (°f) 150 ...

  • Page 5

    Article 426 of the national electrical code governs the installation of wintergard heating cable systems for roof and gutter de-icing. Important: for the raychem hts warranty to be valid, you must comply with all the requirements outlined in these guidelines. All design information provided here is ...

  • Page 6

    H908 design and installation information for roof and gutter de-icing only (continued) (wintergard wet h612 heating cable) product data–wintergard wet h612 heating cable for roof and gutter de-icing only service voltage (v) 120 thermal output at 32°f (w/ft) (in ice and snow) 8 weight per 100 ft (lb)...

  • Page 7

    7 h913/h914 roof clip h915 downspout hanger cable ties h910 tee end seal (included in h900 and h910 kits) clamp ties (two places) h915 downspout hanger power connection splice h908: ground-fault equipment protection device end seal (included in h908 and h910 kits) weatherproofed outlet approved for ...

  • Page 8

    8 h908 installation instructions – power connection kit outer jacket braid bus wires conductive core inner jacket braid bus wires conductive core inner jacket identify heating cable wintergard h311, h611 heating cables with braid and no outer jacket wintergard h612 heating cables with braid and oute...

  • Page 9

    9 2-3/4" 2b for h612 heating cable only 2c for h612 heating cable only 1/4" 5 expose bus wires (continued) 6 prepare bus wires 1-3/4" 1/4" 1/4" 3 remove inner jacket (h612 cable shown) 4 expose bus wires 1 2 3 4 5 6 7 8 9 • score between bus wires at inner jacket. • slide 1/8˝ x 1˝ shrink tubes over...

  • Page 10

    10 heat-shrink tube plug-in cord green wire black and white wires mastic 7 connect bus wires 8 apply mastic to bus wires black cloth tape green ground wire braid 10 connect ground wire note: ring of adhesive will appear at both ends 9 apply 5-inch shrink tube • use insulated bus wire crimps and ct-1...

  • Page 11

    11 1 2 3 4 5 6 7 8 9 note: ring of adhesive will appear at both ends 11 apply 8-inch shrink tube • center the 8-inch heat-shrinkable tube over the splice. Make sure that the tube extends over the end of the heating cable and cord. • shrink the tube completely. Start at the middle and work toward eac...

  • Page 12

    12 h908 installation instructions – end seal 1 2 3 4 5 6 7 8 9 note: the end seal is designed to be installed only once; it cannot be removed from the heating cable once installed. Do not use until ready for final installation. 1" r r 2" r • remove the outer jacket. • do not cut or damage inner jack...

  • Page 13

    13 h908 installation instructions – securing the ground-fault device 1 2 3 4 5 6 7 8 9 clamp ties warning fire and shock hazard self-regulating electrical heating cable attached to this pipe: disconnect before servicing cord label warning fire and shock hazard self-regulating electrical heating cabl...

  • Page 14

    14 raychem hts warrants all heatsystems self-regulating heating cable against faulty workmanship and use of defective materials for two (2) years from the date of purchase. This warranty can be amended only by a written instrument signed by a duly authorized officer of raychem hts. Buyer’s, exclusiv...

  • Page 15

    15 h908 design and installation information notes.

  • Page 16

    16 h908 design and installation information worldwide headquarters raychem hts 300 constitution drive menlo park, california 94025-1164 tel (800) 545-6258 fax (650) 474-7517 fax-on-demand (800) 901-8107 info@raychemhts.Com www.Raychemhts.Com north america raychem hts 1960 blue heron drive london, on...