Raypak ELS 1102-2 Installation & Operating Instructions Manual

Other manuals for ELS 1102-2: Illustrated Parts List

Summary of ELS 1102-2

  • Page 1

    Installation & operating instructions catalog no. 6100.53u effective: 09-28-09 replaces: 11-11-08 p/n 240362 rev. 22 for your safety: do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result ...

  • Page 2

    2 water chemistry for your health and the protection of your pool equip- ment, it is essential that your water be chemically balanced. The following levels must be used as a guide for balanced water. Caution: corrosive water voids all warranties. Recommended level(s) fiberglass pools fiberglass spas...

  • Page 3

    Introduction the spa-pak spa heaters have been designed to pro- vide efficient, pollution-free, electric pool heating while requiring minimal installation. The spa-pak consists of a sheathed resistance element installed in a copper tank. This tank has a 1-1/2” inlet and outlet on the side for plumbi...

  • Page 4

    4 thermostat the heater thermostat located on the front of the unit, may be set for any desired spa temperature. Maximum temperature setpoint (knobstop adjustment) adjustment to a different maximum setting is a simple task. Loosen the small set screw on the knobstop and rotate the knobstop ring unti...

  • Page 5

    5 model amp draw conduit size wire size (including ground) size of fused disconnect (amps) els 1102-2 46 1” 6 60 els 552-2 23 *1/2” 10 30 *use a reducer bushing. Table a: wire sizes for field connection l1 l2 model els 552-2 only schematic diagram ladder diagram.

  • Page 6

    Controls spa-pak spa heaters have integral thermostats and contactors. They are also equipped with a high tem- perature limit thermostat which will open the circuit cutting off power to the heating element in the event of excessive water temperature. This high limit thermo- stat is factory set at 14...

  • Page 7

    7 3. A green terminal (or wire connector marked "g", "gr", "ground" or "grounding") is provided within the control box. To reduce the risk of electric shock, connect this terminal or connector to the grounding terminal of the electric service or supply panel with a continuous copper wire in accordan...

  • Page 8

    8 4. Remove retainer clip at bulb and remove capillary bulb. 5. Remove aquastat, using extreme care to see that the capillary tube is not kinked or broken. (never use anything but fingers to bend capillary tubing). Removing the high limit 1. Turn off electrical power to heater at main discon- nect. ...

  • Page 9

    9 troubleshooting problem cause solution nothing happens when the ther- mostat is turned on low flow.......................................... High limit......................................... Thermostat not calling for heat....... 1. Check filter, skimmer basket, pump. 2. If a 2-speed pump is use...

  • Page 10

    10 8 12 9 part description els 552-2 els 1102-2 f 2 0 8 1 0 0 f 1 0 8 1 0 0 t n e m e l e 1 2 element gasket (not shown) 800164 800164 3 element tube assy. 001805f 001808f f 7 8 0 4 0 0 f 7 8 0 4 0 0 ll e w r o s n e s 4 5 well retaining clip 300203 300203 6 pressure switch 062237b 062237b f 1 1 8 1...

  • Page 11

    11.

  • Page 12: Www.Raypak.Com

    Www.Raypak.Com raypak, inc., 2151 eastman avenue, oxnard, ca 93030 (805) 278-5300 fax (805) 278-5468 litho in u.S.A..