RKC INSTRUMENT SA100L Instruction Manual

Manual is about: Limit Controller

Summary of SA100L

  • Page 1

    ® rkc instrument inc. All rights reserved, copyright  2004, rkc instrument inc. Limit controller sa100l instruction manual imr01j07-e2 thank you for purchasing this rkc product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instru...

  • Page 2: 3. Wiring

    Imr01j07-e2 2 (4) mount this instrument in the panel considering the following conditions:  provide adequate ventilation space so that heat does not build up.  do not mount this instrument directly above equipment that generates large amount of heat (heaters, transformers, semi-conductor functiona...

  • Page 3: 4. Parts Description

    Imr01j07-e2 3  this instrument with 24 v power supply is not provided with an overcurrent protection device. For safety install an overcorrect protection device (such as fuse) with adequate breaking capacity close to the instrument.  fuse type: time-lag fuse (approved fuse according iec60127-2 and...

  • Page 4: 5. Setting

    Imr01j07-e2 4 5. Setting input type/input range display (display for approx. 4 seconds) set key (2 seconds) display changes automatically set  set  (2 seconds) set key (2 seconds) communication setting mode for details, refer to the communication instruction manual (imr01j08-e ). Engineering mode...

  • Page 5: 6. Operation

    Imr01j07-e2 5  changing parameter settings procedures to change parameter settings are shown below. When the set data is locked, the digits on the sv display are brightly lit and the set value cannot be changed.  change the limit set value (sv) change the limit set value (sv) from 0 °c to 200 °c 1...

  • Page 6: 8. Initial Setting

    Imr01j07-e2 6 8. Initial setting 8.1 go to engineering mode 1. Turn on the power to this controller. The instrument goes to the pv/sv monitor after confirming input type symbol and input range. 2. Press and hold the set key for 2 seconds with the sv setting & monitor mode change the instrument to pa...

  • Page 7

    Imr01j07-e2 7  if the setting range is not between 1999 and 9999 regardless of the position of the decimal point, it is limited by the range from 1999 to 9999. Example: suppose set slh is 1372 c, if change decimal point position from 0 to 1.  if the number of digits below the decimal point is...

  • Page 8

    Imr01j07-e2 8  change settings example: change the decimal point position from “one decimal place (0001)” to “no decimal place (0000)” 1. Press the set key several times at “f21” until “pgdp” is displayed. 2. Press the down key to change the number to 0. 3. Press the set key to store the new set va...

  • Page 9

    Imr01j07-e2 9 (4) alarm 1 process abnormality action selection (aeo1) alarm 2 process abnormality action selection (aeo2) it is judged that the input is abnormal when over-scale or underscale occurs. For a voltage input of 0 to 5 v dc or 0 to 10 v dc, as over-scale or underscale does not occur when ...

  • Page 10

    Imr01j07-e2 may 2013 website: http://www.Rkcinst.Com/ the first edition: jul. 2004 [imq00] the second edition: may 2013 [imq00] ® rkc instrument inc. Headquarters: 16-6, kugahara 5-chome, ohta-ku tokyo 146-8515 japan phone: 03-3751-9799 (+81 3 3751 9799) e-mail: info@rkcinst.Co.Jp fax: 03-3751-8585 ...