Summary of SkyStar

  • Page 1

    New con trol boar d with modb us comm uni cati on pr otocol air conditioning skystar skystar ecm cassette fan coil units quality management systems iso 9001 – cert. N° 0545/5 www.Eurovent-certification.Com www.Certiflash.Com.

  • Page 2

    Sabiana take part to the eurovent program of fan coil performance certification. The official figures are published in the web site www.Eurovent-certification.Com and in the web site www.Certiflash.Com . The tested performances are: • fan absorption • water pressure drop • sound power • heating emis...

  • Page 3: Skystar

    Innovating and beautiful design, seven different sizes, high control flexibility, easy maintenance: the new skystar chilled water cassette is the result of an extended technical and design development aimed at achieving the highest level in terms of performance, silent operation and control possibil...

  • Page 4: Skystar

    4 intake grid and distribution of the air intake grids, frame and adjustable air distribution louvers on each side, made from abs. Hta version : white abs, ral 9003 htb version : with intake grid, frame and louvers, choice of one colour only htc version : with intake grid and louvers, choice of one ...

  • Page 5

    310 1,84 1,35 2,22 316 4,9 4,1 33 24 25 0,11 420 2,34 1,75 2,90 402 7,6 6,3 40 31 32 0,15 520 2,68 2,04 3,35 461 9,7 8,2 45 36 44 0,20 320 2,25 1,57 2,56 387 4,6 3,5 33 24 25 0,11 500 3,34 2,39 3,93 574 9,4 7,3 45 36 44 0,20 710 4,33 3,18 5,23 745 15,1 11,4 53 44 68 0,32 430 2,94 2,08 3,43 506 7,5 6...

  • Page 6: Skystar

    386 310 237 482 417 356 787 593 412 903 702 520 1118 865 734 1683 1146 876 2015 1471 876 2,24 1,80 1,38 2,80 2,42 2,07 4,57 3,45 2,39 5,25 4,08 3,02 6,50 5,03 4,27 9,78 6,67 5,09 11,72 8,55 5,09 203 164 126 266 232 198 440 334 235 504 394 294 624 486 415 951 655 505 1132 834 505 2,37 1,91 1,46 3,10 ...

  • Page 7: Skystar

    Model speed air flow ewt 45 - lwt 40°c ewt 50 - lwt 40°c ewt 60 - lwt 50°c ewt 70 - lwt 60°c ewt 80 - lwt 70°c l/h m 3 /h kw l/h kw l/h kw l/h kw l/h kw water flow emission water flow emission water flow emission water flow emission water flow emission 256 215 166 283 247 196 351 277 196 402 317 247...

  • Page 8: Skystar

    710 500 320 880 610 430 1500 970 710 1820 1280 710 279 226 165 315 255 205 720 541 441 824 651 441 1,62 1,32 0,96 1,83 1,48 1,19 4,18 3,14 2,56 4,79 3,79 2,56 139 113 83 156 127 103 493 365 291 569 449 291 1,61 1,32 0,97 1,82 1,48 1,20 4,33 3,27 2,67 6,61 5,22 3,39 213 173 127 241 195 157 554 416 34...

  • Page 9: Skystar

    °c k 20 0,94 30 0,90 40 0,86 50 0,82 60 0,78 70 0,74 80 0,70 °c k 40 1,14 50 1,08 60 1,02 70 0,96 80 0,90 °c k 20 0,94 30 0,90 40 0,86 50 0,82 60 0,78 70 0,74 80 0,70 water flow air flow supply max. Working pressure 8 bars suitable relative humidity 15 - 75% single phase 230v 50hz min. Entering wate...

  • Page 10: Skystar

    790 350 750 150 a b c d mm 30 24 6 3 kg kg weights packed unit weights unpacked unit sk 02 - 12 sk 04 - 14 sk 22 - 24 - 26 sk 32 - 34 - 36 28 22 unit diffuser kg kg model weights packed unit weights unpacked unit packed unit dimensions md-600 metal diffuser (rs receiver, code 9066338, for md-600 met...

  • Page 11: Skystar

    Packed unit dimensions 1050 400 1000 200 a b c d mm 47 39 10 6 kg kg weights packed unit weights unpacked unit sk 42 sk 44 sk 52 - 54 - 56 sk 62 - 64 - 66 44 36 unit diffuser kg kg model weights packed unit weights unpacked unit packed unit sk 42-44 / sk 52-54-56 / sk 62-64-66(version 800 x 800) 11 ...

  • Page 12: Skystar

    Speed air throw l m 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 3,0 3,5 3,8 3,0 3,8 4,5 3,5 4,2 5,0 3,2 3,7 4,3 3,4 4,0 5,0 3,4 4,6 5,5 model sk 02-04-12-14 sk 22-24-26 sk 32-34-36 sk 42-44 sk 52-54-56 sk 62-64-66 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 3,3 2,2 2,5 3,9 2,6 2,9 4,2 2,8 3,1 3,3 2,2 2,5 4,2 2,8 3,...

  • Page 13: Skystar

    13 skystar spigot for air distribution air outlet air intake two air outlets are provided on the side of the unit for connection to separate supply air outlets. They can be used to supply air from the fan coil unit to distant areas of a room or even to a different room. The total air flow does not c...

  • Page 14: Skystar

    Fresh air kit this is used to introduce primary air into the environment directly through the diffuser. The kit includes a flow separator to be fitted inside the cassette, and a circular fitting for connection to the flexible system ducting. The flow of air is sent directly to just one of the outlet...

  • Page 15: Skystar

    Rated pressure: max. Ambient temperature: max. Water flow temperature: power: rating: protection: travel time: max. Glycol content of water: 16 bar 50 °c 110 °c 230 v - 50/60 hz 3 va ip 43 approx. 3 min. 50% 3 ways 2 ways 3 ways 2 ways 15 skystar accessories valve set, 2 or 3 ways, on-off, with ther...

  • Page 16: Skystar

    Cassette skystar can be equipped with the innovative plate type electrostatic filter, crystall, combining air treatment and purifying in a single product. The electronic filter is patented and certified according to standard uni 11254. Introduction 16 skystar dimensions sk 0 / 1 / 2 / 3 (model 600 x...

  • Page 17: Skystar

    When the polluted air goes through the mechanical pre-filter the particles * 50 μ are eliminated (powder, insects, etc). Then the smallest particles (50 ÷ 0.01 μm) are exposed to an intensive ionizing field and are polarized (phase 1). The charged particles passing through the second filter section,...

  • Page 18: Skystar

    High medium low not classified (l.S. Per person) + (l.S. Per m 2 ) (l.S. Per person) + (l.S. Per m 2 ) (l.S. Per person) + (l.S. Per m 2 ) not classified total fresh air volume varies based on the intended use of the confined area uni en 13779:2008 ida 1 ida 2 ida 3 ida 4 > 15 10 − 15 6 − 10 20 12,5...

  • Page 19: Skystar

    The crystall electrostatic filtering system consists of two parts: the first is a plate type electronic active filter and is fitted in the return air section of the cassette, while the second is an electronic control and regulation board, fixed on the structure. All electrical connections are made d...

  • Page 20

    Dimensions: 133x93x37 mm dimensions: 133x93x37 mm dimensions: 133x93x37 mm 20 wall electronic controls if using the skystar cassette fan coils with electronic controllers, the voltage values at the autotransformer terminals must be kept in consideration (transformer return voltages). These values ma...

  • Page 21: Skystar

    Dimensions: 128x75x25 mm dimensions on the wall: 133x93x27 mm dimensions in the din 503 box: 133x93x18 mm dimensions: 118x87x8 mm dimensions: 133x93x37 mm 21 skystar wall electronic controls 2 pipes units only. • on-off switch. • 3 speed switch. • manual summer/winter switch. • thermostatic control ...

  • Page 22: Skystar

    22 skystar speed switches • speed switch (slave). • it allows to control up to 8 units with only one centralized wall control (1 speed switch for each unit). • for controls cr-t, tmo-t, tmo-t-au and tmo-503-sv2. • speed switch (slave) for tmo-di • it allows to control up to 10 units with only one tm...

  • Page 23: Skystar

    Control codes control operations control identification 9060174 t2t tmo-di tmo-503-sv2 tmo-t-au tmo-t cr-t 9060165 9060173 9060164 9060161 9066330 mo-3v 9060160 installation of electronic low temperature cut-out thermostat (tme) room thermostat for fan and electric heater control room thermostat for...

  • Page 24: Skystar

    24 skystar freesabiana wireless control system freesabiana free sabiana is an innovative, fully wireless, electronic system for use with fan coil units, based on radio communication. This technology provides installation flexibility and a more accurate measurement of the room temperature. The probe ...

  • Page 25: Skystar

    25 skystar freesabiana wireless control system the power unit controls the fan and the valves of the fan coil. The power unit receives the information required to control such units both from the remote control and locally. This device is able to measure the temperature of the air in the spot where ...

  • Page 26: Skystar

    Rt03 infra-red remote control psm-di multifunction control sabianet software sabianet screenshot pc t-mb wall control all the controls for the ecm version and their functions are described in detail from page 43. All the skystar units can be supplied in mb version. This version includes a wide range...

  • Page 27: Skystar

    27 skystar the skystar 2 pipe models are available with electric heater that is controlled in place of the heating battery valve. The electric heater is controlled in place of the hot water valve and not as integration to it. The heater is hermetically sealed and supplied inside the battery pipes an...

  • Page 28: Skystar Ecm

    The skystar ecm series uses an innovative brushless synchronous permanent magnet electric motor controlled by an inverter card that is directly installed on the unit. The air flow can be varied continuously with a 1-10 v signal from sabiana controls or by independent contollers (programmable control...

  • Page 29: Skystar

    Intake grid and distribution of the air intake grids, frame and adjustable air distribution louvers on each side, made from abs. Hta version : white abs, ral 9003 htb version : with intake grid, frame and louvers, choice of one colour only htc version : with intake grid and louvers, choice of one co...

  • Page 30: Skystar

    3,0 4,0 1,4 2,1 2,1 820 x 820 x 303 575 x 575 x 275 710 5,29 3,69 5,89 909 9,4 7,2 34 25 10 1130 7,72 5,53 8,83 1328 18,5 14,9 47 38 32 1770 10,75 7,94 12,73 1848 33,6 28,8 57 48 108 630 4,21 3,03 5,11 723 10,9 8,7 33 24 10 870 5,15 3,77 6,35 885 15,6 12,8 39 30 17 1165 6,33 4,72 8,01 1089 22,7 19,5...

  • Page 31: Skystar

    7/12 °c 10/15 °c 14/18 °c k k k 0,9 0,72 0,5 0,94 0,78 0,58 1,06 0,9 0,72 7/12 °c 10/15 °c 14/18 °c k k k 0,82 0,56 0,35 0,89 0,63 0,41 1,11 0,82 0,52 water (°c) air (°c) 25-18 26-18.5 28-20 water (°c) air (°c) 25-18 26-18.5 28-20 total emission sensible emission note: the correction factors are ind...

  • Page 32: Skystar Ecm

    7/12 °c 10/15 °c 14/18 °c k k k 0,9 0,72 0,5 0,94 0,78 0,58 1,06 0,9 0,72 7/12 °c 10/15 °c 14/18 °c k k k 0,82 0,56 0,35 0,89 0,63 0,41 1,11 0,82 0,52 water (°c) air (°c) 25-18 26-18.5 28-20 water (°c) air (°c) 25-18 26-18.5 28-20 total emission sensible emission note: the correction factors are ind...

  • Page 33: Skystar

    Water flow air flow supply max. Working pressure 8 bars suitable relative humidity 15 - 75% single phase 230v 50hz min. Entering water temperature: + 5°c max. Entering water temperature: + 80°c min. Entering air temperature: 6°c max. Entering air temperature: 40°c installation max. Height: see table...

  • Page 34: Skystar Ecm

    790 350 750 150 a b c d mm 30 24 6 3 kg kg weights packed unit weights unpacked unit sk 12 sk 14 sk 22 - 26 sk 32 - 36 28 22 unit diffuser kg kg ecm model weights packed unit weights unpacked unit packed unit dimensions sk 12-14 / sk 22-26 / sk 32-36(version 600 x 600) skystar ecm 34 skystar skystar...

  • Page 35: Skystar Ecm

    Unit diffuser 1050 400 1000 200 10 6 packed unit dimensions a b c d mm 47 39 kg kg weights packed unit weights unpacked unit sk 42 sk 44 sk 52 - 56 44 36 unit diffuser kg kg ecm model weights packed unit weights unpacked unit packed unit sk 42-44 / sk 52-56(version 800 x 800) 35 skystar ecm skystar ...

  • Page 36: Skystar Ecm

    1 2 3 3,3 2,2 2,5 3,9 2,6 2,9 4,2 2,8 3,1 1 2 3 3,3 2,2 2,5 4,2 2,8 3,1 4,8 3,2 3,6 1 2 3 3,9 2,6 2,9 4,5 3,0 3,4 5,2 3,4 3,9 1 2 3 3,5 2,2 2,7 4,1 2,6 3,2 4,8 3,0 3,8 1 2 3 3,8 2,4 3,0 4,6 2,8 3,6 5,4 3,4 4,2 sk 12-14 sk 22-26 sk 32-36 sk 42-44 sk 52-56 speed air throw l m height h m distance b m e...

  • Page 37: Skystar

    Fresh air kit this is used to introduce primary air into the environment directly through the diffuser. The kit includes a flow separator to be fitted inside the cassette, and a circular fitting for connection to the flexible system ducting. The flow of air is sent directly to just one of the outlet...

  • Page 38: Skystar Ecm

    Rated pressure: max. Ambient temperature: max. Water flow temperature: power: rating: protection: travel time: max. Glycol content of water: 16 bar 50 °c 110 °c 230 v - 50/60 hz 3 va ip 43 approx. 3 min. 50% battery type main ecm model auxiliary 12 - 22 - 32 14 - 26 - 36 42 - 52 44 - 56 14 - 26 - 36...

  • Page 39: Skystar

    Legend sep = pump control board blac = inverter board m = electronic motor controller = controller for this cassette configuration, the 1-10 vdc signal, which controls the inverter, must be supplied by a controller with the following signal specifications: • impedance 1; • maximum speed 10vdc; • fan...

  • Page 40: Skystar Ecm

    Skystar ecm 40 skystar skystar ecm power unit to be installed on the fan coil (fan coil interface). It controls the fan and the valves of the fan coil. The power unit is connected to the electric supply. The power unit receives the information required from the control. Power unit for cr-t-ecm and c...

  • Page 41: Skystar

    Red black 41 skystar skystar ecm skystar ecm to be fitted between the coil fins. When connecting the control, the ntc probe cable must be separated from the power supply wires. To be used with cr-t-ecm and cr-di-ecm controls. It stops the fan when the water temperature is lower than 28°c and it star...

  • Page 42: Skystar

    42 skystar all the skystar ecm units can be supplied in mb version. This version includes a wide range of controls, including the infra-red remote control, which allows managing one single unit or several units by using the modbus rtu - rs 485 communication protocol. Units can be managed according t...

  • Page 43: Skystar

    43 skystar the mb electronic board, mounted as per standard on the sk–mb and sk–ecm–mb versions, is set to carry out different functions and adjustment modes, in order to meet the installation requirements. These modes are selected by setting the configuration dip switches on the board. • 2/4 pipe s...

  • Page 44: Skystar

    44 skystar skystar ecm skystar / skystar ecm wall control with display that allows controlling one or more units in master/slave mode. The control is equipped with internal sensor to detect the room temperature, which can be defined as a priority compared to the return air sensor on the fan coil. Th...

  • Page 45: Skystar

    45 skystar skystar ecm skystar / skystar ecm the infra-red remote control allows setting by a remote position the fan coil operation parameters. The rt03 infra-red remote control features the following functions: • switch the appliance on and off. • temperature set. • set the fan speed (low, medium,...

  • Page 46: Skystar

    46 skystar the t2 sensor can be combined with mb boards to be placed on the water supply pipe upstream 3 way valves (not to be used with 2 way valve). The t2 sensor must be used as described below: - change-over for 2-pipe system for the automatic switch of the operating mode. If water temperature i...

  • Page 47: Skystar

    47 skystar another option available for the serial communication between the units is the possibility to connect up to 60 cassette units in series and manage them with just one wall mounted psm-di controller. The wall mounted controller can be used to set the operating mode for each individual unit ...

  • Page 48: Skystar

    “monitoring” s creen 48 skystar skystar ecm skystar / skystar ecm sabianet is a centralised control system for networks of sabiana mb fan coils, based on software that runs on linux™. The sabianet software offers a practical and economical solution for managing the units, with the simple click of th...

  • Page 49: Skystar

    “event management” s creen 49 skystar skystar ecm skystar / skystar ecm time bands are available for each day of the week. The time and the type of operation to be performed by the unit can be set for each band. The time and the operating parameters can then be displayed before being sent to the uni...

  • Page 50: Skystar

    Usb-rs 485 outputs for system power input converter rs 485 outputs for system power input outputs for system power input mc2 jumper to be closed. End of network. Cassette unit cassette unit cassette unit sabianet 60 units max. ( * ) 50 skystar skystar ecm skystar / skystar ecm sios is a board equipp...

  • Page 51: Skystar McT

    51 introduction the mct version has been designed for all environments where false ceilings are not featured or cannot be constructed. The cover cabinet fits perfectly to the air intake and outlet diffuser, maintaining the appealing design that defines the skystar series. The water fittings can be t...

  • Page 52: Skystar McT

    Skystar mct dimensions and weights sk 02-mct / sk 12-mct / sk 22-mct / sk 32-mct casing code: 9079240 casing weight: 5 kg (7,5 kg with the packaging) sk 42-mct / sk 52-mct / sk 62-mct casing code: 9079250 casing weight: 10,5 kg (13,5 kg with the packaging) warning: the electrical and water connectio...

  • Page 53: Skystar

    53 skystar skystar mct skystar mct assembly diagram.

  • Page 54: Skystar McT

    The descriptions and illustrations provided in this publication are not binding: sabiana reserves the right, whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time, without the requirement to promptly update this piece of literature, any changes...

  • Page 55

    Md-600 diffuser.

  • Page 56

    Air conditioning skystar - skystar ecm cassette fan coil units skyst ar - ex - 11/13 c od. A4790100 h/11/13 sabiana s.P.A. • via piave, 53 • 20011 corbetta • milano • italy • phone +39.02.97203.1 r.A. / +39.02.97270429 / +39.02.97270576 fax +39.02.9777282 / +39.02.9772820 • www.Sabiana.It • info@sab...