SafeFlame SF200A Installation Manual

Summary of SF200A

  • Page 1

    Safeflame flame detector installation manual october, 2012 safe fire detection inc. 5915 stockbridge dr. Monroe, nc 28110 phone: (704) 821-7920 fax: (704) 821-4327 website: www.Safefiredetection.Com e-mail: staff@safefiredetection.Com notice: installers of any safeflame products or systems must be t...

  • Page 2

    2 safe fire detection – home office safe fire detection, inc. 5915 stockbridge drive. Monroe, north carolina 28110 usa phone: 704-821-7920 fax: 704-821-4327 e-mail: staff@safefiredetection.Com web page: http://www.Safefiredetection.Com notice: these instructions do not purport to cover all details o...

  • Page 3: Warranty Information

    3 warranty information all accessories pertaining to the detector for installation and mounting must be purchased from safe fire detection or the warranty may be void. If a system is desired, the fire alarm control/releasing panel can be purchased from safe fire detection to create a system, and if ...

  • Page 4

    4 table of contents 1. Safe fire detection company introduction 5 2. Safeflame ir3 introduction 6 2.1 overview 6 2.2 principles of operation 7 2.3 detector performance options 7 3.3 mounting bracket 12 2.3.1 cone of vision 7 3.3.1 specifications 12 3.5 setting up the detector 17 3.5.1 sensitivity 17...

  • Page 5: 1. Safe Introduction

    5 1. Safe introduction safe fire detection, inc. Is committed to providing the be st customer support in the industry. This provides our clients with the satisfaction of knowing that their valuable assets and business operation are our greatest concerns. This trust has been earned through 40 years o...

  • Page 6

    6 2. Safeflame ir3 introduction 2.1 overview safeflame is the sensors monitors the spectral band for co the spectrum for the radiation emitted by a flame measured by the detector is altered by the distance between the detector and the fire. It can also be influenced by the concentration of co a ir3 ...

  • Page 7

    7 2.2 principles of operation safeflame’s triple ir (ir3) flame detector compares three specific wavelength bands within the ir spectral range of a fire and their ratio to each other. This offers fast response without the fear of typical false alarms. One sensor monitors the 4.4 micrometer range and...

  • Page 8

    8 2.3.2 detector sensitivity the detector has two alarm levels: warning (pre-alarm) and alarm. The detection range for the detector is 200 feet (60 meters) for a standard fire. A standard fire is defined as a 1ft² (0.1m²) n-heptane pan fire. The warning level is an alarm verification system. Having ...

  • Page 9

    9 2.3.4 false alarm protection and immunity the detector is immune to a variety of potential false alarm sources. Below is a table showing either the immunity to a radiation source or the distance beyond which the detector is immune to the radiation source. Electric heater 1500w indirect or reflecte...

  • Page 10

    10 [figure 4] front [figure 5] side 2.4.3 mechanical specifications enclosure (material): aluminum weight: detector- 1.3kg(3.3lbs.), detector w/ bracket- 2.5kg (5.5lbs.) dimensions(detector): 150 x 103 x 125mm (5.9” x 4.1” x 4.9”) dimensions (with bracket): 150 x 171 x 347mm (5.9” x 6.7” x 13.7”) co...

  • Page 11: 3. Installation

    11 3. Installation 3.1 guidelines for installation for optimal detector performance and protection of the hazard, please consider the guidelines for installation: spacing: the number of flame detectors in the protected area is determined by the size of the area, the cone of vision, obstructions, and...

  • Page 12

    12 3.3 mounting bracket 3.3.1 specifications angle adjustment: horizontal 180 °, vertical 180° weight: 1kg color: metal enclosure material: 316 stainless steel wall mounted size: 6 x 4 (5mm bolt) Φ dimensions(bracket): 276 x 100 x 88mm (10.9” x 3.9” x 3.4”) 3.3.2 installation necessary tool: hexagon...

  • Page 13

    13 alarm relay output: wiring diagram alm_com terminal alm_n.C. Alm_n.O. Common normal (de-energized) normally closed (n.C.) normally open (n.O.) relay status alarm (energized) common rating: 2a@28vdc, 4a@125vac, 2a@250vac [figure 8] terminal wiring diagram at fire alarm relay warning relay output: ...

  • Page 14

    14 fault relay output: wiring diagram tb1 flt_com terminal flt_n.C. Common normal (de-energized) relay status fault (energized) common rating: 2a@28vdc, 4a@125vac, 2a@250vac -flt_n.C. Is default. To disable fault relay switch sw1-8 to on 0-20ma current source: wiring diagram normally open (n.O.) nor...

  • Page 15

    15 rs-485: wiring diagram terminal 485+ 485- rs-485 terminals and their connection description connection remote reset: wiring diagram tb2 rs-485 a rs-485 b non-isolation communication full-duplex, half-duplex 4800, 9600, 19200, 38400bps are available (dip-switch selectable) 1:n support (client) sup...

  • Page 16

    16 external self-diagnosis test: wiring diagram terminal 485- external self-diagnosis connection connection tb2 external self diagnosis signal line operating signal: same level of signal with 24v-_in operating delayed time: 5 seconds operating continuous time: operating delayed time + 10 sec. Normal...

  • Page 17

    17 3.5 setting up the detector 3.5.1 sensitivity sensitivity setting can be adjusted by the user according to adhere to local codes, environments, or the desires of the client. Please make sure all laws, codes, and regulations are met when installing the safeflame detector note: the detector must be...

  • Page 18

    18 3.5.4 built-in-test (bit) the detector has the self diagnosis function to check whether sensors are detectable (detection of internal circuitry or sensor itself) for radiant energy as well as cleanliness of transmission windows. If there are some fault on the internal circuit or decrease of trans...

  • Page 19

    19 3.5.6 rs-485 this is a feature to enable the rs-485 communication between maser(server) and slave(detector) with modbus command. This feature can be disabled to save power. Sw1 switch setting sw3-2 off on function rs-485 communication disabled (default) rs-485 communication enabled setting detect...

  • Page 20

    20 4. Operating and testing the detector 4.1 initial power-up before powering-up a safeflame detector inspect all aspects of the installed equipment. This initial inspection can help to prevent future down time and improve the longevity and performance of the detectors. Initial operation operational...

  • Page 21

    21 Ÿ testing procedures with the tl305 1. Please wait for 10 seconds after power is connected. Check if yellow led is blinking 2. Turn on the tl305 and point it at the front of the safeflame. The recommended distance between the test lamp and the detector is within 16ft(5m) 3. If the red led is on, ...

  • Page 22

    22 5.1 maintenance the detector must be kept as clean as possible. Clean the viewing window and the reflector of the safeflame periodically. The frequency of cleaning depends on the local environmental conditions and specific applications. Cleaning and operation testing must be completed at least ev...

  • Page 23

    23 5915 stockbridge dr. • monroe, nc 28110 tel.: 704-821-7920 • fax: 704-821-4327 safeflame installation and operation manual (publication#: ma-sf200om).