    1. General information .................................................................................................... 4 2. Dimensions ............................................................................................................................ 4 3. Installation ....................

  • Page 3

    19. Heat exchanger settings .................................................................................... 25 20. Heater settings ........................................................................................................... 26 20.1. Supplied air heater settings .....................

  • Page 4: 1. General Information

    4 1 en 1. General information ptouch remote control panel is designed for: • salda ventilation units and other devices based on prv, mcb or eco controllers; • modbus-controlled devices. Remote control panels guarantee optimal comfort of operation, monitoring, maintenance and service. All operations ...

  • Page 5

    5 3. Ptouch installation on a plaster-board wall: ptouch installation on a plaster-board wall: 1-2 turn over the panel. Use a screwdriver to lift the cover as shown in fig. 2 . 3 take the cover apart. 4 put it at desired location on the wall. The arrow must point upwards. Mark the positions of mount...

  • Page 6: 4.1. Service Login

    6 b2 b1 i1 4.1. Service login 4. Service number function entered code (masked) 2200 number function clear last entered digit confirm entered code i1 b1 b2 4 en 4.2. Service menu b2 b6 b1 b5 b3 b4 b7 b8.

  • Page 7

    7 4 en b10 b9 b13 b11 b12 number function main settings. Fan settings. Damper settings. Heat exchanger settings. Heater settings. Cooler settings. Digital input settings. Sensor settings. Communication settings. B1 b4 b2 b3 b5 b6 b7 b8 b9 b10 b14 b15 b11 b12 b13 b14 b15.

  • Page 8: 4.3. Main Settings Menu

    8 4 en 4.3. Main settings menu b2 b10 b6 b1 b9 b5 b13 b3 b11 b12 b4 b7 b8 number function system blocking settings. Air temperature control settings. Air temperature protection settings. System mode switch settings. Fan speed settings. Air filter protection settings. Fire protection settings. Contro...

  • Page 9

    9 4 en 4.3.1. System blocking settings fire protection settings. Controller box heating settings. Co2 reduction settings. B11 b12 f1 f2 number function block automatic control: auto: automatic control is enabled; block: automatic control is disabled. Standby blocking mode: never: standby is allowed;...

  • Page 10

    10 5. Air temperature control settings 5 en number function temperature control type: by supply air: supplied air temperature is equal to set desired temperature; extract (room) air: supplied air temperature is variable and includes supply temperature compensation. Supply temperature compensation. O...

  • Page 11

    11 6 en number function supply temperature low limit (in °c * 10). Protects from supplying too cold air. Range: [0-200 °c] (0-20.0 °c) supply temperature high limit (in °c * 10). Protects from supplying too hot air. Range: [200-600 °c] (20.0-60.0 °c) supply temperature limit timeout. If supplied air...

  • Page 12

    12 7. System mode switch settings number function remote switch type: none: no remote switch; push: push-button type switch; on/off: normal switch; pir: passive infrared sensor. Mode selected using the remote switch: standby; building protection; economy; comfort. F1 f2 f1 f2 i1 number function curr...

  • Page 13

    13 8. Fan speed switch settings number function remote switch type: none: no remote switch; custom push: push-button type switch for enabling custom fan speeds; custom on/off: normal switch for enabling custom fan speeds; boost push: push-button type switch for operating fans at their maximum speeds...

  • Page 14

    14 9 en 9. Air filter protection settings number function filters press relay type: none: no pressure relays for filter-contamination detection; supply: one pressure relay in supplied air duct; extract: one pressure relay in extracted air duct; both: two pressure relays. Number of days between filte...

  • Page 15

    15 10 en 10. Fire protection settings number function fire protection action: stop system: fans are stopped, alert is risen; boost supply air: supply fan is operated at full speed, extract fan is stopped; boost extract air: supply fan is stopped, extract fan is operated at full speed; boost supply a...

  • Page 16

    16 11 en 11. Controler box heating settings number function ahu control box heating: enabled; disabled. Control box heating temperature set point. Range: [0-20 °c] f1 f2 f1 f2 i1 number function current setting indication. I1.

  • Page 17

    17 12 en 12. Co2 reduction settings number function co2 level protection: enabled; disabled. Optimal co2 level. Range: [0-1000 ppm] allowed co2 level range around the desired co2 level. Range: [0-1000 ppm] f1 f2 f3 f1 f2 f3 i1 number function current setting indication. I1.

  • Page 18: 13. Fan Settings

    18 13 en 13. Fan settings b2 b1 b3 number function fan speed settings. Fan voltage settings. Fan protection settings. B1 b2 b3 13.1. Fan speed control settings f1 f5 f2 f4 f3 i1.

  • Page 19

    19 number function current setting indication i1 number function control using fixed fan speeds: yes: use operating modes; no: use control by speed. Fans control type: percent’s: control linearly by voltage (within specified minimum and maximum voltages); pressure: control using pressure sensor sign...

  • Page 20: 14. Fan Voltage Settings

    20 number function maximum air flow pressure (when fan control type is pressure). Range: [0-1000 pa] f1 f2 f3 14. Fan voltage settings number function minimal fan voltage (in v/100). Used as a limiting value. Range: [0-1000] (0-10.00 v) maximal supply fan voltage (in v/100). Used as a limiting value...

  • Page 21

    21 15. Fan protection settings f1 f5 f2 f4 f3 i1 number function current setting indication i1 number function halted fan protection by monitoring its speed: enabled: alert is risen and system is stopped if after fan start signal its speed remains 0 rpm for at least 10 s; disabled: fan speed monitor...

  • Page 22: 16. Damper Settings

    22 16. Damper settings b2 b1 b3 number function supply/extract damper settings. Recirculation damper settings. Fire damper settings. B1 b2 b3 16.1. Supply/extract damper settings f1 f2 i1 16 en.

  • Page 23

    23 number function supply/extract damper type: none; on/off: one-terminal controlled damper. Closes mechanically if no signal is provided; openclose: two-terminal controlled damper. Stays still if no signal is provided. Can be opened or closed partially. Time required for supply/extract damper to fu...

  • Page 24: 18. Fire Damper Settings

    24 18. Fire damper settings f1 f5 f2 f4 f3 i1 number function current setting indication i1 number function fire damper type: none; one switch; two switches. Time required for fire damper to fully open (in seconds). Range: [0-255 s] fire damper testing: enabled; disabled. Fire damper testing interva...

  • Page 25

    25 19. Heat exchanger settings number function heat exchanger type: none; plate; rotor. Plate heat exchanger frost protection strategy: none; pre-heating by set point; pre-heating by frost point; recirculating by set point; recirculating by frost point. Set point (as a difference from frost point). ...

  • Page 26: 20. Heater Settings

    26 b2 b1 b3 b4 20. Heater settings number function supplied air heater settings. Fresh air pre-heater settings. Electrical heaters cooling settings. Hydraulic heater protection. B1 b2 b3 b4 19.1. Supplied air heater settings f1 f2 f3 i1 20 en.

  • Page 27

    27 number function supplied air heater type: none; electrical 0-10vdc; electrical on/off; hydraulic. Electrical pre-heater pwm time interval (if pre-heater type is electri- cal on/off). Range: [0-300 s] alarm overheat action: none; stop system; intensive ventilation. F1 f2 f3 number function current...

  • Page 28

    28 number function electrical heating components cooling time. During this time, ventilation is enabled to dissipate remaining heat. Range: [0-100 s] f1 number function current setting indication. I1 number function fresh air pre-heater type: none; electrical 0-10vdc; electrical on/off; hydraulic. E...

  • Page 29

    29 23. Hydraulic heater protection number function hydraulic heating components preparation time. Fluid heating time before initial fan start (during heating season). Range: [0-100 s] hydraulic heater frost temperature. In a case of lower supplied air temperature, system is stopped. Range: [-30-10 °...

  • Page 30: 24. Cooler Settings

    30 f1 f2 f4 f3 i1 24. Cooler settings number function current setting indication i1 number function hydraulic cooler: enabled; disabled. Hydraulic cooler frost temperature. In a case of lower supplied air temperature, system is stopped. Range: [-30-10 °c] dx cooler: enabled; disabled. Dx cooler mini...

  • Page 31

    31 25. Digital input settings b2 b6 b1 b5 b3 b4 b7 number function external control input settings. Fan protection input settings. Heater protection input settings. Cooler protection input settings. Filter pressure relay settings. Fire damper switch input settings. Bypass switch input settings. B1 b...

  • Page 32

    32 f1 f2 f3 i1 25.1. External control input settings number function current setting indication i1 number function fire protection input: no: normally open; nc: normally closed. System mode switch input: no: normally open; nc: normally closed. Fan speed switch input: no: normally open; nc: normally ...

  • Page 33

    33 26. Fan protection input settings number function supply fan protection input: no: normally open; nc: normally closed. Extract fan protection input: no: normally open; nc: normally closed. F1 f2 number function current setting indication. I1 f1 f2 i1 26 en.

  • Page 34

    34 f1 f2 f4 f3 i1 27. Heater protection input settings number function current setting indication i1 number function heater manual protection input: no: normally open; nc: normally closed. Heater automatic protection input: no: normally open; nc: normally closed. Pre-heater manual protection input: ...

  • Page 35

    35 number function dx cooler protection input: no: normally open; nc: normally closed. F1 number function current setting indication. I1 28. Cooler protection input settings f1 i1 29. Filter pressure relay input settings f1 f2 i1 28 en 29.

  • Page 36

    36 30. Fire damper switch input settings f1 f2 i1 number function supply filter pressure relay input: no: normally open; nc: normally closed. Extract filter pressure relay input: no: normally open; nc: normally closed. Number function fire damper opened input: no: normally open; nc: normally closed....

  • Page 37: 32. Sensor Settings

    37 31. Bypass switch input settings number function bypass opened input: no: normally open; nc: normally closed. Bypass closed input: no: normally open; nc: normally closed. F1 f2 number function current setting indication. I1 f1 f2 i1 32. Sensor settings b2 b1 31 en 32.

  • Page 38

    38 32.1. 0-10vdc sensor settings b2 b1 number function 0-10vdc sensor settings. Temperature sensor settings. Number function supplied air quality sensor settings. Extracted air quality sensor settings. B1 b1 b2 b2 f1 f2 f3 i1 33. Supplied air quality sensor settings 32 en 33.

  • Page 39

    39 number function current setting indication number function current setting indication i1 i1 number function supplied air quality sensor type: none; rh: relative humidity sensor; co2: carbon dioxide sensor. Co2 level (in ppm) at minimum voltage (0 vdc). Range: [0-2000 ppm] co2 level (in ppm) at ma...

  • Page 40

    40 b2 b6 b1 b5 b3 b4 b7 b8 number function supplied air temperature sensor settings. Extracted air temperature sensor settings. Exhausted air temperature sensor settings. Outdoor air temperature sensor settings. Hydraulic heater water temperature sensor settings. Hydraulic pre-heater water temperatu...

  • Page 41

    41 number function temperature sensor type: none; remote: temperature values are received over communication interface (using modbus); ntc 3997: thermo-resistive sensor. Temperature sensor alarm (activated if temperature sensor value is less than -50 °c or more than +50 °c): none; stop system; emerg...

  • Page 42: 36. Communication Settings

    42 b2 b1 number function internal modbus port settings. Bms modbus port settings. B1 b2 36. Communication settings number function current setting indication i1 f1 f2 f3 i1 36.1. Internal modbus port settings 36 en.

  • Page 43

    43 number function ahu control unit modbus address. Range: [1-247] baud rate: 1200; 2400; 4800; 9600; 19200; 38400; 57600; 115200. Frame settings: n-8-1: no parity – 8 data bits – 1 stop bit; e-8-1: even parity – 8 data bits – 1 stop bit; o-8-1: odd parity – 8 data bits – 1 stop bit; n-8-2: no parit...

  • Page 44

    44 frame settings: n-8-1: no parity – 8 data bits – 1 stop bit; e-8-1: even parity – 8 data bits – 1 stop bit; o-8-1: odd parity – 8 data bits – 1 stop bit; n-8-2: no parity – 8 data bits – 2 stop bits; e-8-2: even parity – 8 data bits – 2 stop bits; o-8-2: odd parity – 8 data bits – 2 stop bits. F3.