Salda Smarty 2X P Mounting And Installation Instructions Manual

Manual is about: AHU WITH HEAT RECOVERY

Summary of Smarty 2X P

  • Page 1

    Subject to technical modification smarty 2x-3x p_mi_p0112_az_0002 ahu with heat recovery smarty 2x p smarty 3x p mounting and installation instructions.

  • Page 2

    2 smarty 2x/3x p www.Salda.Lt safety instructions and precautions 3 information about the product 4 description 4 dimensionsandweight 5 technicaldata 6 airflowdiagrams 7 operatingconditions 8 standardpackageofcomponents 8 components 9 accessoriessmarty2xp 10 accessoriessmarty3xp 11 instalation 12 re...

  • Page 3: Pio

    3 smarty 2x/3x p www.Salda.Lt device is manufactured in compliance with the following directives: • machinery directive, 2006/42/ec; • low voltage directive, eec 2006/95; • electromagnetic compatibility directive, 2004/108/ec. Read this instruction very carefully before installing and using this equ...

  • Page 4

    4 smarty 2x/3x p www.Salda.Lt smarty 2x/3x p are residential air handling unit with a high efficiency (up to 90 %) counter flow heat exchanger. The unit provides ventilation in the home and takes the heat from the exhausted air. Ahu complies with erp 2018 ** and passivhaus requirements. The unit is ...

  • Page 5

    5 smarty 2x/3x p www.Salda.Lt smarty 2x p 360 mm 1 15 mm 1 15 mm 1043 mm 590 mm 250 mm 1009 mm 326 mm 113 mm g3/8" ø 21,3 mm ø 125 mm/160 mm* 223 mm smarty 3x p 1225 mm 408,5 mm g3/8" 150 mm 324 mm ø 21,3 mm ø 150/160 mm* 1381,5 mm 685,5 mm 128 mm 128 mm 429,5 mm smarty 2x p smarty 3x p weight (with...

  • Page 6

    6 smarty 2x/3x p www.Salda.Lt note. Subject to technical modification smarty 2x p lwa total, db(a) lwa, db(a) 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz supply 59,0 44,0 52,0 51,0 53,0 53,0 51,0 36,0 exhaust 55,0 42,0 47,0 47,0 50,0 48,0 44,0 29,0 surrounding 47,1 34,7 42,7 42,8 37,0 33,3 33,0 31,...

  • Page 7

    7 smarty 2x/3x p www.Salda.Lt operational limits power consumption smarty 2x p smarty 3x p supply air supply air 60 50 40 30 20 10 0 600 500 400 300 200 100 50 14 150 42 200 250 56 69 300 83 60 50 40 30 20 10 0 600 500 400 300 200 100 50 14 150 42 200 250 56 69 300 83 600 500 400 300 200 100 50 14 1...

  • Page 8

    8 smarty 2x/3x p www.Salda.Lt standard package (without optional accessories) includes: anti-vibration rubbers 4 pcs. Caps of a cover screws 8 pcs. (only smarty 2xp) supply air sensor tj 1 pc. Key 1 pc. Condensate outlet pipe g3/8 1 pc. * ‒ when relative humidity of extracted air is lower than 35 %....

  • Page 9

    9 smarty 2x/3x p www.Salda.Lt smarty 2x p 6 1 smarty 3x p 1. Mounting bracket with anti-vibration mounts - 4 pcs. 2. Outdoor air filter and the cover (if) 3. Outdoor air temperature sensor (tl) 4. Bypass damper (m1) ‒ only 1.1 and 1.2 versions 5. Control board 6. Ce7/7 power supply cable - 3m, suppl...

  • Page 10

    10 smarty 2x/3x p www.Salda.Lt ap aks skg ptouch stouch mb gateway alu eka eka nis maxi blue set s-kff-u s-rff-u-d-f2 s-kco2 s-rco2-f2 cm230-f-l smarty 2x p legs npu wsg te mpl (g4) mpl (f7) coupling npu 125 gfdnpuc002 supply and extract air gratings wsg 160 ggrwsg0126_509 dampers skg 125 gskskg002 ...

  • Page 11

    11 smarty 2x/3x p www.Salda.Lt wsg aks skg ptouch stouch mb gateway te eka eka nis maxi blue set s-kff-u s-rff-u-d-f2 s-kco2 s-rco2-f2 cm230-f-l smarty 3x p legs mpl (g4) mpl (f7) ap alu supply and extract air gratings wsg 160 ggrwsg0126_509 wsg 150 ggrwsg0126_508 dampers skg 160 gskskg003 skg 150 g...

  • Page 12

    12 smarty 2x/3x p www.Salda.Lt each device is thoroughly checked before transportation. While receiving goods it is recommended to check whether devices were not damaged dur- ing transportation. If a damage to the device is noticed, immediately address the representatives of a transport company. Ple...

  • Page 13

    13 smarty 2x/3x p www.Salda.Lt outdoor air supply air exhaust air extract air iv extract air fan tj supply air temperature sensor pv supply air fan cee7/7 power cable with plug pr plate heat exchanger x18 control panel connection place pf filter for supply air (g4/(f7 - optional)) m1 bypass motor if...

  • Page 14

    14 smarty 2x/3x p www.Salda.Lt outdoor air supply air exhaust air extract air iv extract air fan tj supply air temperature sensor pv supply air fan cee7/7 power cable with plug pr plate heat exchanger x18 bms or control panel connection place pf filter for supply air (g4/(f7 - optional)) pe* (eka ni...

  • Page 15

    15 smarty 2x/3x p www.Salda.Lt outdoor air supply air exhaust air extract air iv extract air fan tj supply air temperature sensor pv supply air fan cee7/7 power cable with plug pr plate heat exchanger x18 bms or control panel connection place pf filter for supply air (g4/(f7 - optional)) pe* (eka ni...

  • Page 16

    16 smarty 2x/3x p www.Salda.Lt • installation should only be performed by qualified and trained staff. • when connecting air ducts, consider the notices indicated on the casing of the unit. • before connecting to the air duct system, the connection openings of ventilation unit should be closed. • wh...

  • Page 17

    17 smarty 2x/3x p www.Salda.Lt levelling supports are provided as the accessories, the screws are included. 3 4 after hanging or setting a heat recovery unit (1), it is necessary to connect condensate discharge system (2-3). A pipe (3) (metal or plastic pipes are connected using an elbow g3/8, if th...

  • Page 18

    18 smarty 2x/3x p www.Salda.Lt smarty 2x p: i ii iii iv v vi vii viii ix x xi * drain (i-xi) of the condensate is installed when the device is set in position b* or c* (shown in the illustrations above). Before installing lateral condensate drainage, it is necessary to remove a plate (vi) in a metal...

  • Page 19

    19 smarty 2x/3x p www.Salda.Lt before every heating season the condensate tube shall be filled with water as indicated during the first start-up! Before every heating season the condensate tube shall be filled with water as indicated during the first start-up! * drain (i - xi) of the condensate is i...

  • Page 20

    20 smarty 2x/3x p www.Salda.Lt • connected air ducts must be straight and have their own fixing. • make sure that the fans can not be entered through air duct heads. If it is possible to enter the fan, protective grid should be installed. You can choose it in our website. • do not reduce the diamete...

  • Page 21

    21 smarty 2x/3x p www.Salda.Lt fig. 1. Unit automation 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 3 2 1 3 2 1 3 2 1 3 2 1 4 3 2 1 3 2 1 3 2 1 3 2 1 pe gnd +2 4 v d c di 1 gnd a o 1 (0-10 v ) gnd a o 2 (0-10 v ) gnd a o 3 (0-10 v ) +2 4 v d c _ p...

  • Page 22

    22 smarty 2x/3x p www.Salda.Lt a connector contactor no. Contactor name functional block name minimcb x1 1 pe not used 2 gnd 3 24vdc 4 di1 (holo) x2 1 gnd supply air fan control (output 0-10vdc) 2 ao1 (0-10v) 3 gnd extract air fan control (output 0-10vdc) 4 ao2 (0-10v) 5 gnd electric/water preheater...

  • Page 23

    23 smarty 2x/3x p www.Salda.Lt x7 1 di9 system mode switch 2 3.3v_1w 3 di10 fan speed switch 4 3.3v_1w 5 ai4 (0-10v) a2-extract air co 2 or rh (input 0-10vdc) 6 gnd 7 24vdc 24vdc power supply for air quality transmitter i 8 gnd d connector contactor no. Contactor name functional block name minimcb x...

  • Page 24

    24 smarty 2x/3x p www.Salda.Lt f connector contactor no. Contactor name functional block name minimcb x18 1 rs422_z rs422/485 communication port 2 rs422_y 3 - 4 rs422/485_a 5 rs422/485_b 6 rs_gnd 7 24vdc 8 gnd b c fig. 3. Ex1 controller zones b connector contactor no. Contactor name functional block...

  • Page 25

    25 smarty 2x/3x p www.Salda.Lt c connector contactor no. Contactor name functional block name miniex1 x23 1 di1 electric heater manual protection (nc) 2 12vdc 3 di2 electric heater automatic protection (nc) 4 12vdc 5 di3 filter relay/fire place i, di (nc) 6 12vdc 7 di4 filter relay/fire place ii, di...

  • Page 26

    26 smarty 2x/3x p www.Salda.Lt wiring diagram automation controller a (x2) and d (x12) zones. Sp58 ke (eka) + ta pe ptouch stouch * te** tinklas ke* (eka) ta * te** pe* (eka nis/ eka) ke* (eka) ta * te** pe* (eka nis/ eka) aks*** aks*** aks*** aks*** aks*** aks*** * * * mb- gateway ptouch stouch tin...

  • Page 27

    27 smarty 2x/3x p www.Salda.Lt drawn by checked by signature duties / name date uab"salda" drawing # book # checked by 1 1 2 3 4 4 5 6 7 7 external heater sp59 - pe - on/off principle connection scheme 12 05 2016-06-23 2016-06-23 2016-06-23 pe l n pe -k1 1 2 3 4 5 6 -k1 a1 a2 x5 :1 - di 5 x5 :2 - +1...

  • Page 28

    28 smarty 2x/3x p www.Salda.Lt installation diagram electric heater shall be installed inside air duct. Arrangement based on air direction electric heater -> supply air sensor (tj). Wiring diagram connection of on/off or 0-10 v heater’s power circuit. This control method suits only to electric heate...

  • Page 29

    29 smarty 2x/3x p www.Salda.Lt drawn by checked by signature duties / name date uab"salda" drawing # book # checked by 1 1 2 3 4 4 5 6 7 7 external heater sp56 principle connection scheme 12 03 2016-06-16 2016-06-16 2016-06-16 pe l n ke1 x1 0: 1 - p e x1 0: 2 - d o1 (l (l 2) ) x1 0: 3 - n( l1 ) mini...

  • Page 30

    30 smarty 2x/3x p www.Salda.Lt eka tj when using the supply air heater, the supply air sensor (ss) shall be installed downstream the heater (or cool- er) as the sensor cable allows or until the first branch- ing, bend of the air transportation system. Drawn by checked by signature duties / name date...

  • Page 31

    31 smarty 2x/3x p www.Salda.Lt n (l 1 ) p e 4 3 2 1 230vac on/off n l 1 l 1 m3 pe pe d o 4 (l (l 2 )) d o 3 (l (l 2 )) 230vac on/off n l 1 l 1 m2 product smarty 2xp and smarty 3xp all versions can be equipped with fresh air damper and extract air drives. They are coled open/close. Installation diagr...

  • Page 32

    32 smarty 2x/3x p www.Salda.Lt supply air co 2 or rh (input 0-10vdc) connection. This connection is possible for unit version 1.1 minimcb basic with ex1 controller. Installation diagram. Transmitter shall be installed inside supply air duct. Wiring diagram. Automation controller b zone x19. Supply a...

  • Page 33

    33 smarty 2x/3x p www.Salda.Lt min. 50 cm min. 60 cm 150 cm max. 400m 2 where the channel co 2 transmitter is used: it must be installed in the extract air duct. Tool for drilling holes are required for its installation. Co 2 concentration [ppm] 3000 effect on an individual 2500 2000 reduced concent...

  • Page 34

    34 smarty 2x/3x p www.Salda.Lt fire protection signal input must be normally closed, until the fire protection system is not connected a jumper is installed in the factory. Automation controller a zone x4. 1 2 3 4 5 6 • supply voltage to the unit must be connected by a qualified specialist following...

  • Page 35

    35 smarty 2x/3x p www.Salda.Lt unit controller minimcb has integrated protection against short-circuit. F1 - 1a (5x20) controller power supply 230vac/24vdc protection. To ensure safe maintenance of the unit, it is necessary to remove the plug from the power network. Prior to start-up the system must...

  • Page 36

    36 smarty 2x/3x p www.Salda.Lt.