    Owner's manual please read this manual before operating your inverter dc-ac inverters pse-12125a pse-12175a pse-12275a.

  • Page 2: Index

    Index safety instructions ............................................................................................. 2,3 inverters - general information ...................................................................... 4,5,6 characteristics of sinusoidal ac power ...............................

  • Page 3

    Page 2 please read these instructions before installing or operating the inverter to prevent personal injury or damage to the inverter. General installation and wiring compliance - installation and wiring must comply with the local and national electrical codes and must be done by a certified electr...

  • Page 4

    Page 3 inverter related preventing paralleling of the ac output the ac output of this inverter cannot be synchronised with another ac source and hence, it is not suitable for paralleling. The ac output of the inverter should never be connected directly to an electrical breaker panel / load center wh...

  • Page 5

    Inverters - general information why an inverter is needed the utility grid supplies you with alternating current (ac) electricity. Ac is the standard form of electricity for anything that “plugs in” to the utility power. Direct current (dc) electricity flows in a single direction. Batteries provide ...

  • Page 6

    Page 5 loads that require “surge power” to start resistive types of loads (like incandescent lamps, toaster, coffee maker, electric range, iron etc) do not require extra power to start. Their starting power is the same as their running power. Some loads like induction motors and high inertia motor d...

  • Page 7

    Page 6 power rating of microwaves the power rating of the microwave generally refers to the cooking power. The electrical power consumed by the microwave will be approximately 2 times the cooking power. The “surge power” of the inverter should be 2 times the electrical power (i.E., 4 times the cooki...

  • Page 8: Note :

    Page 7 characteristics of sinusoidal ac power voltage, current, power factor, types of loads the voltage waveform of 120 vac, 60 hz mains / utility power is like a sine wave. In a voltage with a sine wave-form, the instantaneous value and polarity of the voltage varies with respect to time and the w...

  • Page 9: Caution!

    Page 8 ac power distribution and grounding caution! Please note that the ac output connections and the dc input connections on these inverters are not connected (bonded) to the metal chassis of the inverter. Both the input and output connections are isolated from the metal chassis and from each othe...

  • Page 10

    Page 9 grounded electrical power distribution system the national electrical code (nec) requires the use of a “grounded electrical distribution system”. As per this system, one of the two current-carrying conductors is required to be grounded. This grounded conductor is called the “neutral / cold / ...

  • Page 11

    Page 10 pse-12275a is also provided with a separate plate which has a nema 5-15r receptacle wired through a 15 a beaker. This plate with the receptacle and breaker fits in the pocket through which the output conductors exit the inverter. The nema 5-15r receptacle can be connected to the three output...

  • Page 12

    Page 11 0v -155 to -170v, peak sinewave: smoothly increases to its peak and smoothly decreases. It crosses 0 v immediately. Has rms value of 120v modified sinewave: shoots straight up, levels off at peak & drops straight down. Also, it sits at 0 v for some time. Has rms value of 120v 1 /60 sec +155 ...

  • Page 13

    Page 12 devices that may not operate on modified sine wave the output wave form of these inverters is a modified sine wave. See the diagram under “principle of operation” on page 11. In a sine wave, the voltage rises and falls smoothly with a smoothly changing phase angle and also changes its polari...

  • Page 14

    Page 13 limiting electro-magnetic interference (emi) the inverter contains internal switching devices which generate conducted and radiated electromagnetic interference (emi). The emi is more pronounced in inverters whose output voltage has modified sine wave form as modified sine wave form is compo...

  • Page 15: Pse-12125A,  Pse-12175A

    Page 14 layout g. F. Pse-12125a, pse-12175a rear view bottom view a. C. D. E. B . H. I. Pse-12275a front view b. A. C. D. E. K. J. F. G. H. I. Rear view.

  • Page 16

    Page 15 features, controls & indications important : each of the following operating procedures and safety features must be carefully reviewed and thoroughly understood prior to using the inverter. Failure to do so may result in damage to the inverter or equipment or serious personal injury a on/off...

  • Page 17

    Page 16 battery current & voltage bar graph meters (green, yellow, red). D current indicator. This illuminated bar graph monitors the current being drawn from the battery by the inverter. Depending on the amount of current being drawn, the bar graph reading generally will be in the green or yellow z...

  • Page 18

    Specifying batteries, chargers & alternators the inverter will require deep cycle lead acid batteries of appropriate capacity. Lead-acid batteries can be categorized by the type of application: automotive service - starting/lighting/ignition (sli, a.K.A. Cranking) and deep cycle service sli batterie...

  • Page 19

    Typical battery sizes below is a chart of some battery sizes applicable for powering inverters: bci * group battery voltage, v battery ah 27 / 31 12 105 4 d 12 160 8d 12 225 gc2** 6 220 * battery council international ** golf cart reduction in usable capacity at higher discharge rates. As stated abo...

  • Page 20

    Depth of discharge and battery life the more deeply a battery is discharged on each cycle, the shorter the battery life. Using more batteries than the minimum required will result in longer life for the battery bank. A typical cycle life chart is given at table 2 below: table 2. – typical cycle life...

  • Page 21

    Sizing the inverter battery bank one of the most frequently asked question is, “how long will the batteries last?’. This question cannot be answered without knowing the size of the battery system and the load on the inverter. Usually this question is turned around to ask “how long do you want your l...

  • Page 22

    Charging batteries the batteries can be charged by using good quality ac powered battery charger or from alternative energy sources like solar panels, wind or hydro systems. Make sure an appropriate battery charge controller is used. It is recommended that the batteries may be charged at 10% to 13 %...

  • Page 23

    Installation the success of a dc to ac power inverter installation depends mainly on the methods and materials used for installation. Please read and comply with instructions given below general installation and wiring compliance - installation and wiring must comply with the local and the national ...

  • Page 24

    Cooling by forced air fan ventilation the inverters produce heat when operating. The amount of heat produced is proportional to the amount of power supplied by the inverter. Dc fan is used to provide forced air cooling of this inverter. The fan is thermostatically controlled and will be switched on ...

  • Page 25

    Preventing reverse polarity on the input side when making battery connection on the input side, make sure that the polarity of battery connection is correct (connect the positive of the battery to the positive terminal of the inverter and the negative of the battery to the negative terminal of the i...

  • Page 26

    Using proper dc cable termination the battery end and the inverter end of the cables should have proper terminals that will ensure a firm and tight connection. Dc input terminals on pse-12125a and pse-12175a the dc input terminals on pse-12125a and pse-12175a have a tubular hole with a set screw. A ...

  • Page 27

    Connecting to multi-wire branch circuits do not directly connect the hot side of the 120 vac of the inverter to the two hot legs of the 120 / 240 vac electrical breaker panel / load centre where multi-wire ( common neutral ) branch circuit wiring method is used for distribution of ac power. This may...

  • Page 28

    Grounding of pse-12125a / pse-12175a to earth or to other designated ground please see details regarding grounding under “ac power distribution and grounding” on page 8 for safety, the metal chassis of the inverter is required to be grounded to the earth ground or to the other designated ground (for...

  • Page 29

    Operation powering on the loads after the inverter is switched on, it takes a finite time for it to become ready to deliver full power. Hence, always switch on the load(s) after a few seconds of switching on the inverter. Avoid switching on the inverter with the load already switched on. This may pr...

  • Page 30

    Switching on / off using the optional remote on / off remote control an optional corded remote control, model no. Rc-15, is available to enable switching on and off from a distance of 18 ft. The remote on / off control comes with 18 ft. Of wire. One end of the remote control is plugged into the 6 po...

  • Page 31

    Shut-down due to reversal of polarity at the dc input terminals. The positive of the battery should be connected to the positive dc input terminal of the inverter and the negative of the battery should be connected to the negative dc input terminal of the inverter. A reversal of polarity (the positi...

  • Page 32

    Troubleshooting guide symptom on switching on, the input voltage bar graph indicator does not light. There is no ac voltage ac output voltage reads low ( 96 to 104 vac) when measured with an ordinary voltmeter low ac output voltage and the battery current bar graph indicator shows very high current ...

  • Page 33

    Symptom the ac output shuts down sometimes and resumes automatically. Overload led is not lighted ( might happen during starting of certain loads) the ac output shuts down completely. The red overload led is lighted. Buzzer alarm is sounded. Red over temp led is on. There is no ac output possible ca...

  • Page 34

    Input voltage, volts dc output voltage, volts rms output frequency, hz continuous output power, watts instantaneous overload (surge no load current draw output waveform peak efficiency protections: high input voltage shut down & latch, volts dc low input voltage warning alarm, volts dc low input vol...

  • Page 35: 2 Year Limited Warranty

    2 year limited warranty pse-12125a, pse-12175a & pse-12275a's manufactured by samlex america, inc. ( the “ warran- tor “ ) are warranted to be free from defects in workmanship and materials under normal use and service. This warranty is in effect for 2 years from the date of purchase by the user ( t...