Samlexpower Soleil 2000-120 Owner's Manual

Manual is about: Grid Tie DC-AC Inverter Pure Sine Wave

Summary of Soleil 2000-120

  • Page 1

    Owner's manual please read this manual before operating your inverter grid tie dc-ac inverter pure sine wave model: soleil 2000-120 soleil 2000-240 110-17 fawcett rd coquitlam, b.C. Canada v3k 6v2 t: 604 525 3836 f: 604 525 5221 e-mail: samlex@samlexamerica.Com website: www.Samlexamerica.Com 093-200...

  • Page 2

    Www.Samlexamerica.Com toll free 1-800-561-5885 2 important safety instructions save these instructions to reduce the risk of electrical shock and to ensure safe installation and operation of soleil 2000, please carefully read and strictly follow all safety instructions and cautionary markings. Warni...

  • Page 3

    Www.Samlexamerica.Com toll free 1-800-561-5885 3 caution : this unit is provided with fixed trip limits and shall not be aggregated above 30kw on a single point of common connector. Caution : the ac output of this unit is not bonded to ground. Caution : the input and output circuits are isolated fro...

  • Page 4

    Www.Samlexamerica.Com toll free 1-800-561-5885 4 table of contents 1. Introduction ……………………………………………………. 5 2. Installation …………………………………………………...... 6 3. Wiring process …………………………………………………10 4. Operating procedure…………………………………………..15 5. System structure……………………………………………… 21 6. Electrical specificati...

  • Page 5

    Www.Samlexamerica.Com toll free 1-800-561-5885 5 1. Introduction product features full dsp digital control pv module wp=2.5kw power output capacity: 2kw/120vac 60hz maximum power conversion efficiency >94% (without isolation transformer) high efficiency maximum power point tracking function lcd disp...

  • Page 6

    Www.Samlexamerica.Com toll free 1-800-561-5885 6 2. Installation warning : all electrical installation shall be done in accordance with local and national codes ansi/nfpa 70. Warning : connecting the soleil 2000 to the electrical grid shall only be performed by qualified personnel and only after for...

  • Page 7

    Www.Samlexamerica.Com toll free 1-800-561-5885 7 eventually damage the electronics that are sensitive to humidity. Ambient temperature should be between –20°c and +50°c. Heat sink may reach over 70 o c, so pay special attention to air circulation for sufficient heat dissipation. For indoor unit, ple...

  • Page 8

    Www.Samlexamerica.Com toll free 1-800-561-5885 8 fig. 2-3: side view of the unit mounting to the wall metal fixing plate secure screw.

  • Page 9

    Www.Samlexamerica.Com toll free 1-800-561-5885 9 mounting of soleil 2000 place the metal fixing plate on the designated surface of the wall and mark the holes of the screw. Drill the holes and hammer in the wall anchors. Place the metal fixing plate again and fasten the four screws into their respec...

  • Page 10

    Www.Samlexamerica.Com toll free 1-800-561-5885 10 3. Wiring process the photovoltaic inverter wiring is as shown above. Warning : national electrical code (nec) requires that the inverter be connected to a dedicated circuit and no other outlets or device may be connected to this circuit. See nec sec...

  • Page 11

    Www.Samlexamerica.Com toll free 1-800-561-5885 11 caution : longer wire or voltage drop would require that larger wire sizes be used. For a 70 feet (16.4 m) cable, use size of awg 12 for a 100 feet (33 m) cable, use size of awg 10 notes for wiring make sure the unit is fixed securely and all power s...

  • Page 12

    Www.Samlexamerica.Com toll free 1-800-561-5885 12 connecting ac wiring make sure ac main breaker is at off position. Install a 1/2 inch conduit fitting to the ac knockout at the left side of the soleil 2000. Install two 1/2 inch conduit fittings respectively to the two knockouts at the bottom of iso...

  • Page 13

    Www.Samlexamerica.Com toll free 1-800-561-5885 13 connecting dc wiring make sure that ac main breaker and dc disconnect breaker are at off position. Install a 3/4 inch conduit fitting to the dc knockout at the right side of the soleil 2000. Install a 3/4 inch conduit between the dc knockout and the ...

  • Page 14

    Www.Samlexamerica.Com toll free 1-800-561-5885 14 connect the cable to the appropriate port of the communication pwb in the unit. Connect the other end of the cable to the appropriate port of the pc. Make sure the conduit fitting or cable grand on the knockout is sealed and safe from rain replacing ...

  • Page 15

    Www.Samlexamerica.Com toll free 1-800-561-5885 15 4. Operation warning : connection between the soleil 2000, the pv string and the utility grid must be done in the order described bellow. Operation ignoring the order will cause hazardous accident. Start operation verify all breakers are at off posit...

  • Page 16

    Www.Samlexamerica.Com toll free 1-800-561-5885 16 monitoring and setup rs-232 use standard db9 cable to connect serial port on the computer to that on the machine. After complete setting of com port following monitoring software, it is ready to start monitoring and setting up the photovoltaic invert...

  • Page 17

    Control panel switch on photovoltaic inverter switches the photovoltaic inverter on. Switch on photovoltaic inverter when solar panel input voltage reaches the required range for starting, press this button for a few seconds until a buzzing sound is audible. Release the button. Lcd panel will show t...

  • Page 18

    Pic -1 pic – 2 boot up screen 1. Switch on the power grid circuit breaker, the screen shows “ver. 10”(pic-1) 2. Dsp initial boot up sequence completed as shown on (pic-2), notified by half a second “beep” sound. The system is ready and enters idle mode. Pic - 3 pic - 4 pic - 5 pic - 6 system initial...

  • Page 19

    Www.Samlexamerica.Com toll free 1-800-561-5885 19 pic-7 pic - 8 pic - 9 mppt mode 1. Under the initial mode, after pressing “power” button for more than 3 seconds, or, after dsp takes 5 minutes to detect and confirm that the voltages of power grid and solar module are in operating range, the unit wi...

  • Page 20

    20 pic - 11 pic - 12 pic - 13 pic – 14 protection mode fault display 1. Under conditions as voltage too high, current overflow or inappropriate frequency, the unit will switch off pwm immediately and relay jump off to enter fault mode as shown on (pic-11) to (pic-16). A. When input/ output current o...

  • Page 21

    Www.Samlexamerica.Com toll free 1-800-561-5885 21 5 system structure system structure block diagram system structure can be divided into the following sections: 1. Inverter: by using spwm control and parallel circuit control technology, the inverter can invert electricity from dc into ac and feeds c...

  • Page 22

    Www.Samlexamerica.Com toll free 1-800-561-5885 22 6. Electrical specifications item description data comment architecture converter topology full-bridge dc-ac converter control processor dsp (ti tms320lf2407a, 40mhz) pv input maximum input voltage 450vdc voltage range 200~360vdc (120v mode) groundin...

  • Page 23

    Item description data comment protection anti-islanding yes dc input over voltage and under voltage yes input over current yes ac output over voltage and under voltage yes output over current yes dc ground fault detect and interruption yes current limiting yes power limiting yes frequency decrease a...

  • Page 24

    Www.Samlexamerica.Com toll free 1-800-561-5885 24 7.Trouble shooting problem possible causes how to correct over current output/input current over supply check the output stage of pv inverter for short circuit or inappropriate wiring check if pv inverter is placed in a well-ventilated area line freq...

  • Page 25

    Owner's manual please read this manual before operating your inverter grid tie dc-ac inverter pure sine wave model: soleil 2000-120 soleil 2000-240 110-17 fawcett rd coquitlam, b.C. Canada v3k 6v2 t: 604 525 3836 f: 604 525 5221 e-mail: samlex@samlexamerica.Com website: www.Samlexamerica.Com 093-200...