Samsung AC***FBCDEH Series Installation Manual

Manual is about: Convertible Type Series

Summary of AC***FBCDEH Series

  • Page 2: Warning

    2 contents accessories ............................................................................................................................................................................................................................... 4 selecting the installation location ..................

  • Page 3

    3 english installing the unit important: when installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always disassemble the electric lines before the refrigerant tubes. Upon receipt, inspect the product to verify that it has not been damaged during tr...

  • Page 4

    4 accessories thefollowingaccessoriesaresuppliedwiththeindoorunit. Thetypeandquantitymaydifferdependingonthespecifications. Pattern sheet user manual installation manual plate hanger cable-tie wireless remote controller remote controller holder battery m4 x 16 tapped screw installation manual wirele...

  • Page 5: Floor Installation

    5 english selecting the installation location select a convenient location that permits the air to reach every corner of the area to be cooled. Pre-plan for easy and short routing of the refrigerant tubing and wiring to the outdoor unit. There should be no flammable gas, alkaline, substances present...

  • Page 6

    6 selecting the installation location unit : mm back side p ip e o u tle t (b o tto m sid e ) a ir in ta k e h o le ( 5 0 ) w irin g h o le d ra in h o se o u tle t 2 1 3 pipe outlet-(bottom side) drain hose outlet wiring hole air intake hole (Ø50) no. Name description 1 liquid pipe connection ø6.35...

  • Page 7

    7 english ceiling installation 2 connection pipe drain hose connection pipe drain hose 300mm or more 300mm or more itisrecommendedtoinstallthey-jointbeforeinstallingthe indoorunit. 1 select pipe directions. When the directions are selected, drill 3-1/8''-(100mm, for pipe and cables) and 1-3/4''-(40m...

  • Page 8

    8 floor installation 1 select pipe directions. When the directions are selected, drill 3-1/8'' (100mm, for pipe and cables) and 1-3/4'' (40mm, for drain hose) diameter holes on the wall so that it slants slightly downwards toward the outdoor for smooth water flow. Note use the pattern sheet to selec...

  • Page 9

    9 english purging the unit ondelivery,theindoorunitisloadedwithaninertnitrogen gas.Allthisgasmustthereforebepurgedbeforeconnecting theassemblypiping.Topurgetheinertgas,proceedasfollows. 1 unscrew the caps at the end of each pipe. Result: all inert gas escapes from the indoor unit. Note to prevent di...

  • Page 10

    10 cutting/flaring the pipes 1 make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder) 2 if you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctly a...

  • Page 11

    11 english performing leak test & insulation leak check the designs and shape are subject to change according to the model. Leaktestwithnitrogen(beforeopeningvalves) in order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the r410a, it’s responsible of installer to...

  • Page 12

    12 performing leak test & insulation 5 select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size. Indoor temperature of 30°c and humidity of 85% is the stan dard condition. If installing in a high humidity conditio...

  • Page 13

    13 english drain hose installation caremustbetakenwheninstallingthedrainhosefortheindoorunittoensurethatanycondensation wateriscorrectlydrainedoutside.Whenpassingthedrainhosethroughtheholedrilledinthewall,check thatnoneofthefollowingsituationsoccur. The hose must not slope upwards. The end of the dr...

  • Page 14

    14 a wiring work between indoor and outdoor connection cord specifications indoor unit main power cable cable clamp indoor power 1(l) 2(n) f1 f2 communication cable cable tie indoor power supply communication cable power supply max/min(v) earth cable indoor power cable 220-240v~/50hz ±10% Ø 1.6mm,1 ...

  • Page 15

    15 english silver solder norminal dimensions for cable (mm 2 ) norminal dimensions for screw (mm) b d d1 e f l d2 t standard dimension (mm) allowance (mm) standard dimension (mm) allowance (mm) standard dimension (mm) allowance (mm) min. Min. Max. Standard dimension (mm) allowance (mm) min. 1.5 4 6....

  • Page 16

    16 a step 1. Entering mode to set option 1. Remove batteries from the remote controller. 2. Insert batteries and enter the option setting mode while pressing high temp button and low temp button. 3. Check if you have entered the option setting status. Step 2. The procedure of option setting after en...

  • Page 17

    17 english option setting status 1. Setting seg2, seg3 option press low fan button( ∨ ) to enter seg2 value. Press high fan button( ∧ ) to enter seg3 value. Each time you press the button, … will be selected in rotation. 2. Setting cool mode press mode button to be changed to cool mode in the on sta...

  • Page 18

    18 a setting an indoor unit address and installation option step 4. Input option press operation button with the direction of remote control for set. For the correct option setting, you must input the option twice. Step 5. Check operation 1. Reset the indoor unit by pressing the reset button of indo...

  • Page 19

    19 english 1. Check whether power is supplied or not. - when the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display ) should be connected to an indoor unit to receive option. 3. Before installing the indoor unit, assign an address to the i...

  • Page 20

    20 a setting an indoor unit address and installation option 1. Check whether power is supplied or not. - when the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display ) should be connected to an indoor unit to receive option. 3. Set the inst...

  • Page 21

    21 english option seg19 seg20 seg21 seg22 seg23 seg24 explanation page individual control of a remote controller reserved reserved motion detect sensor reserved indication and details indication details indication details indication details 3 0 or 1 indoor 1 0.No use (factory setting) 1.Standard mod...

  • Page 22

    22 asetting an indoor unit address and installation option you can change each digit of set option. Changing a particular option option seg1 seg2 seg3 seg4 seg5 seg6 explanation page mode the option mode you want to change the tens’ digit of an option seg you will change the unit digit of an option ...

  • Page 23

    23 a english troubleshooting if an error occurs during the operation, one or more led flickers and the operation is stopped except the led. If you re-operate the air conditioner, it operates normally at first, then detect an error again. Led display on the indoor unit on flickering x off if you turn...

  • Page 24: E101

    24 a troubleshooting if an error occurs, is displayed on the wired remote control. If you would like to see an error code, press the test button. Display explanation remark e101 indoor unit communication reception error e102 communication error between the outdoor and indoor unit e121 indoor unit te...

  • Page 25

    25 a english memo.

  • Page 27

    Convertible type series ceiling/floor : ns cdxea air conditioner installation manual imagine the possibilities thank you for purchasing this samsung product. To receive more complete service, please register your product at www.Samsung.Com/register e s f g i p d this manual is made with 100% recycle...