  • Page 2: Safety Precautions

    2 safety precautions contents general information carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be able to use it as reference after installation. For maximum safety, installers should always carefully read the follow...

  • Page 3

    3 english installed in areas used for laundry. Do not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply. In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact samsung’s technical ...

  • Page 4

    Aa 4 preparation for outdoor unit installation the air conditioner uses r-410a refrigerant. A type: ac035hcadkh/ ac026hcadkh heat pump b type: ac052hcadkh heat pump (unit : mm) c type: ac060hcadkh / ac071hcadkh / ac052hcapkh heat pump 548 265 720 60 318 510 12 25 364 310 638 880 54 660 12 23 310 798...

  • Page 5

    5 english plate protection cloth wire rope moving the outdoor unit by wire rope fasten the outdoor unit by two 8m or longer wire ropes as shown at the figure. To prevent from damage or scratches, insert a piece of cloth between the outdoor unit and rope, then move the unit. The appearance of the uni...

  • Page 6

    Aa 6 deciding on where to install the outdoor unit fuse outdoor unit stereo outdoor unit the outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling circuit and seriously damage the unit. Choose a location that is dry and sunny, but not...

  • Page 7

    7 english when installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not find a adequate place without direct see breeze, protection wall should be constructed. • you have just purchased a system air conditioner and it has been installed by your in...

  • Page 8

    Aa 8 space requirements for outdoor unit when installing 1 outdoor unit 300 or mor e when the air outlet is opposite the wall 1500 or mor e when the air outlet is towards the wall 300 or mor e 300 or more 600 or more when 3 sides of the outdoor unit are blocked by the wall 1500 or mor e 2000 or more...

  • Page 9

    9 english 1500 or mor e when the air outlet is towards the wall 300 or mor e 300 or more 1500 or more 600 or more 3000 or more 300 or more 3000 or more 600 or more 600 or more 300 or mor e 1500 or mor e 600 or more 600 or more 600 or more when 3 sides of the outdoor unit are blocked by the wall when...

  • Page 10: Outdoor Unit Installation

    10 outdoor unit installation (unit : mm) 510 720 265 300 318 660 880 310 340 364 660 880 310 340 364 anchor bolt hole anchor bolt hole anchor bolt hole the outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor un...

  • Page 11: Connecting The Cable

    11 aa english connecting the cable two electronic cables must be connected to the outdoor unit.  the connection cord between indoor unit and outdoor unit.  the power cable between outdoor unit and auxiliary circuit breaker.  specially for russian and european market, before installation, the supp...

  • Page 12: Connecting The Cable

    Aa 12 1. Voltage range - units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits 2. Maximum allowable voltage variation between phases is 2%. 3. Wire size & type must comply with the applicable local and national code. - wire...

  • Page 13

    13 english • you should connect the power cable into the power cable terminal and fasten it with a clamp. • the unbalanced power must be maintained within 2% of supply rating. - if the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over 4% ...

  • Page 14: Connecting The Cable

    14 aa tightening torque (kgf • cm) m4 12.0~15.0 ac power : l,n,1(l),2(n), communication : f1, f2 • when connecting cables, you can connect the cables to the electrical part or connect them through the holes below depending on the spot. • run transmission wiring between the indoor and outdoor units t...

  • Page 15

    15 aa english refrigerant piping system items maximum allowable lengh single installation dpm installation applicable outdoor unit models ac026hcadkh ac035hcadkh ac052hcadkh ac052hcapkh ac060hcadkh ac071hcadkh ac071hcadkh total pipe length (l1+…+ln+1 +a+b) - - - 50 m main pipe (l1) 20 m 30 m 50 m 30...

  • Page 16: Adding Refrigerant

    Aa 16 the outdoor unit is loaded with sufficient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is lengthened. This operation can only be performed by a qualified refrigeration specialist. For quantity of adding refrigerant, refer to page 17. 1. Check that the sto...

  • Page 17

    17 english how to calculate the quantity of adding refrigerant the quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialis...

  • Page 18: Installing Dpm

    Aa 18 installing dpm dpm allowable outdoor and indoor unit models dpm allowable outdoor and indoor unit models outdoor unit models 2 indoor units connection indoor unit ac071hcadkh ac035hbmdkh installation of multiple indoor units should consist of units that have the same capacity. Space requiremen...

  • Page 19

    19 english connecting communication line and wired remote controller in case of 2 indoor units connection operation and specification - the two, the three, or the four sets of the indoor units with dpm installation which are controlled by wired and wireless remote controller work equally. (all contr...

  • Page 20

    20 aa connecting up and removing air in the circuit the air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the compressor either reduce cooling/heating capacity or lead to a malfuction. Refrigerant for air purging is not charged in the ou...

  • Page 21: Cutting/flaring The Pipes

    21 aa english 5. Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring. • if the pipes require brazing ensure that ofn(oxygen free nitrogen) is flowing through the system. • nitrogen blowing pressure range is 0.02 ~ 0.05mpa. Uneven thickness cracke...

  • Page 22: Performing Leak Tests

    22 aa connecting the drain hose to the outdoor unit a(gas) performing leak tests the designs and shape are subject to change according to the model. Leak test with nitrogen (before opening valves) in order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the r-410a, ...

  • Page 23: Insulation

    23 aa english insulation once you have checked that there are no leaks in the system, you can insulate the piping and hose. 1. To avoid condensation problems, place an insulator around each refrigerant pipe. 2. Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe...

  • Page 24: Using Stop Valve

    24 aa using stop valve 1. Open the cap and turn the stop valve counterclockwise by using a hexagonal wrench. 2. Turn it until the axis is stopped. 3. Tighten the cap securely. 1. Remove the cap. 2. Turn the stop valve clockwise by using a hexagonal wrench. 3. Tighten the axis until the valve reached...

  • Page 25

    25 english interface module installation (optional) interface module interface module power cable interface module communication cable installation manual case cable-tie fix the case with hinges (control box in the outdoor unit) ✴ 026/035/052✴ ✴ 052/060/071✴ fix the case with hinges (control box in ...

  • Page 26: Pump Down Procedure

    26 pump down procedure relocation of the air conditioner • refer to this procedure when the unit is relocated. • carry out the pump down procedure (refer to the details of ‘pump down’). • remove the power cord. • disconnect the assembly cable from the indoor and outdoor units. • remove the flare nut...

  • Page 27: Checking Correct Grounding

    27 aa english if the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed. The corresponding accessories are not supplied with the air conditioner. 1. Select an grounding electrode that complies with the s...

  • Page 28: Testing Operations

    Aa 28 1. Check the power supply between the outdoor unit and the auxiliary circuit breaker.  1 phase power supply : l, n 2. Check the indoor unit. 1) check that you have connected the power and communication cables correctly. (if the power cable and communication cables one mixed up or connected in...

  • Page 29

    29 english short push display contents seg1 seg2 seg3 seg4 unit 1 order frequency 1 hundreds' digit tens' digit unit digit hz 2 current frequency 2 hundreds' digit tens' digit unit digit hz 3 the number of current indoor units 3 hundreds' digit tens' digit unit digit ea 4 the sensor for outdoor air ...

  • Page 30

    Aa 30 commission delegated regulation (eu) no 626/2011 ⁱ) product fiche (energy labelling of air conditioners) ⁱⁱ) a supplier's name - samsung electronics co., ltd. Samsung electronics co., ltd. Samsung electronics co., ltd. B model name (indoor/outdoor) - ac052hbldkh ac052hcadkh ac071hbldkh ac071hc...

  • Page 31

    31 english a supplier's name - samsung electronics co., ltd. Samsung electronics co., ltd. Samsung electronics co., ltd. B model name (indoor/outdoor) - ac052hbmdkh ac052hcadkh ac060hbmdkh ac060hcadkh ac071hbmdkh ac071hcadkh c sound power level (inside/outside) db(a) 53/63 57/64 57/65 d refrigerant ...

  • Page 32

    Aa 32 a supplier's name - samsung electronics co., ltd. Samsung electronics co., ltd. Samsung electronics co., ltd. B model name (indoor/outdoor) - ac052hbmpkh ac052hcapkh ac026hbldkh ac026hcadkh ac035hbldkh ac035hcadkh c sound power level (inside/outside) db(a) 53/63 53/63 53/63 d refrigerant name ...

  • Page 33

    33 english [nederlands-nl] [polski-pl] a naam van de leverancier nazwa dostawcy b modelnaam (binnen/buiten) nazwa modelu (wewnętrzny/zewnętrzny) c geluidsniveau (binnen/buiten) poziom mocy akustycznej (wewnętrzna/ zewnętrzna) d koelmiddel 1) nazwa środka chłodzącego 1) e gwp gwp f seer seer g enegie...

  • Page 34

    Aa 34 [magyar-hu] [ ČeŠtina-cs ] a forgalmazó neve název dodavatele b modellnév (beltéri/kültéri) název modelu (vnitřní/venkovní) c zajszint (beltéri/kültéri) hladina akustického výkonu (vnitřní/venkovní) d hűtőközeg neve 1) název chladiva 1) e gwp gwp f seer seer g energiahatékonysági osztály (seer...

  • Page 35

    35 english [slovenČina-sk] [romnĂ-ro] a názov dodávateľa numele furnizorului b názov modelu(vnútorné/ vonkajšie) numele modelului (interior/exterior) c hladina akustického výkonu (vnútorná/vonkajšia) nivel de putere acustică (interior/exterior) d chladivo 1) numele agentului frigorific 1) e gwp gwp ...

  • Page 36

    Aa 36 commission delegated regulation (eu) no 626/2011 ⁱ) product fiche (energy labelling of air conditioners) ⁱⁱ) [БЪЛГАРСКИ-bg] [srpski-sr] a Име на доставчик naziv dobavljača b Име на модел (вътрешно/външно тяло) naziv modela (unutršnja jedinica/ spoljašnja jedinica) c Ниво на акустична мощност (...

  • Page 37

    37 english [hrvatski-hr] [shqip-sq] a naziv dobavljača emri i ofruesit b naziv modela (unutarnji/spoljni) emri i modelit (i brendshëm/jashtëm) c razina zvučne snage (u zatvorenom/ otvorenom) niveli i fuqisë së zhurmës (brenda/jashtë) d naziv rashladnog sredstva 1) emri i ftohësit 1) e gwp gwp f seer...

  • Page 38

    Aa 38 commission delegated regulation (eu) no 626/2011 ⁱ) product fiche (energy labelling of air conditioners) ⁱⁱ) [МАКЕДОНСКИ-mk] [slovenČina-sl] a Име на испорачувач názov dodávateľa b Име на модел (внатрешен/надворешен) názov modelu(vnútorné/ vonkajšie) c Ниво на јачина на звук (внатре/надвор) hl...

  • Page 39

    39 english [dansk-da] [svenska-sv] a leverandørens navn leverantörens namn b modelnavn (indendørs/udendørs) modellnamn (inomhus/utomhus) c lydeffektniveau (indenfor/udenfor) ljudnivå (inomhus/utomhus) d navnet på køleelementet 1) köldmedium 1) e gwp gwp f seer seer g energieffektivitetsklasse (seer)...

  • Page 40

    Aa 40 commission delegated regulation (eu) no 626/2011 ⁱ) product fiche (energy labelling of air conditioners) ⁱⁱ) [suomi-fi] [eesti-et] a tavarantoimittajan nimi tarnija nimi b mallin nimi (sisä/ulko) mudeli nimi (sisetingimused/välistingimused) c Äänitehotaso (sisä/ulko) helivõimsuse tase (sisetin...

  • Page 41

    41 english [latvieŠu-lv] [lietuviŲ kalba-lt] a piegādātāja nosaukums tiekėjo pavadinimas b modeļa nosaukums (iekštelpu/ārtelpu) modelio pavadinimas (naudojamo patalpose / lauke) c skaņas intensitātes līmenis (iekštelpu/ārtelpu) garso galios lygis (patalpose / lauke) d aukstumaģenta nosaukums 1) Šald...

  • Page 42

    Aa 42 commission delegated regulation (eu) no 626/2011 ⁱ) product fiche (energy labelling of air conditioners) ⁱⁱ) [nederlands-nl] 1) lekken van koelmiddel dragen bij tot de klimaatveranderingen. Koelmiddelen met een lager global warming potential (gwp) dragen minder bij tot de klimaatveranderingen ...

  • Page 43

    43 english [ČeŠtina-cs] 1) dopady úniků chladiva na klimatické změny. Chladivo s nižším potenciálem globálního oteplování (gwp) má v případě úniku do ovzduší menší vliv na globální oteplování než chladivo s vyšším gwp. Zařízení obsahuje chladicí kapalinu s gwp, který odpovídá hodnotě [2088]. To znam...

  • Page 44

    Aa 44 [Български-bg] 1) Течовете на хладилен агент допринасят за изменението на климата. Хладилен агент с по-нисък потенциал за глобално затопляне (gwp) би допринесъл по-малко за глобалното затопляне, отколкото хладилен агент с по-висок gwp, в случай на изтичане в атмосферата. Този уред съдържа тече...

  • Page 45

    45 english [ shqip-sq ] 1) rrjedhja e ftohësit ndikon në ndryshimin e klimës. Ftohësi me potencial më të ulët për ngrohje globale (gwp) do të ndikonte më pak në ngrohjen globale se ftohësit me gwp më të lartë, nëse rrjedh në atmosferë. Kjo pajisje përmban lëng ftohës me gwp të barabartë me [2088]. K...

  • Page 46

    Aa 46 [dansk-da] 1) udsivning fra køleelementet er medvirkende til klimaforandringerne. Køleelementer med et lavere globalt opvarmningspotentiale (gwp) bidrager mindre til den globale opvarmning end køleelementer med et højere gwp, hvis der er udsivning i atmosfæren. Denne enhed indeholder et kølemi...

  • Page 47

    47 english [eesti-et] 1) jahutusaine lekkimine soodustab kliimamuutust. Väiksema globaalse soojenemise potentsiaaliga jahutusaine soodustab atmosfääri lekkimise korral globaalset soojenemist vähem kui suurema globaalse soojenemise potentsiaaliga jahutusaine. See seade sisaldab jahutusainet, mille gl...

  • Page 48: Troubleshooting

    48 aa troubleshooting the table below give indication about self diagnostic routine. Some of error code requires activities exclusively for authorized service center. If an error occurs during the operation, it is displayed on the outdoor unit pcb led, both main pcb and inverter pcb. Outdoor unit no...

  • Page 49: Appendix

    49 english dimension and weight type model net dimension (wxdxh) (mm) net weight(kg) outdoor unit ac026hcadkh 720*265*548 29.5 ac035hcadkh 720*265*548 29.5 ac052hcadkh 880*310*638 45.0 ac060hcadkh 880*310*793 55.0 ac071hcadkh 880*310*793 55.0 ac052hcapkh 880*310*793 54.0 model specification (dimensi...

  • Page 50

    Aa 50 how to connect your extended power cables 1. Prepare a compressor and the following tools. Tools crimping pliers connection sleeve (mm) insulation tape contraction tube (mm) spec mh-14 20xØ6.5(hxod) width 19mm 70xØ8.0(lxod) shape 2. As shown in the figure, peel off the shields from the rubber ...

  • Page 51

    51 english 5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. A total of three or more layers of insulation is required. F method 1 40 mm insulation tape f method 2 insulation tape 35 mm 6. Apply heat to the contraction tube to ...

  • Page 52

    Samsung electronics co.,ltd. No.501,suhong east road,suzhou industrial park,jiangsu province,p.R.China samsung electronics (uk) ltd, euro qa lab. Blackbushe business park. Saxony way, yateley, hampshire. Gu46 6gg united kingdom.

  • Page 53

    Ac✴✴✴hcadkh ac✴✴✴hcapkh air conditioner installation manual imagine the possibilities thank you for purchasing this samsung product. Db68-04465a-10 en es fr it pt de el.