Samsung AM007FN1DCH Series Installation Manual

Manual is about: Cassette Type Series Slim 1 Way cassette

Summary of AM007FN1DCH Series

  • Page 1

    미주향_dvms_1way cassette_im_en_03806a(1).Indd 34 2013-03-06 오후 5:58:38.

  • Page 2

    Air conditioner installation manual imagine the possibilities thank you for purchasing this samsung product. To receive more complete service, please register your product at www.Samsung.Com/register cassette type series slim 1 way cassette db68-03806a(1) this manual is made with 100% recycled paper...

  • Page 3: Contents

    E- 2 contents safety precautions ......................................................................................... 3 accessories ........................................................................................................ 5 selecting the installation location .......................

  • Page 4

    E- 3 english (carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.) warning • always disconnect the air conditioner from the power supply before servicing it or accessing its internal components. • verify that installation and testing ope...

  • Page 5

    E- 4 make sure that you earth the cables. - do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, electric shock or fire may occur. Install the circuit breaker. - if the circuit breaker is not installed, electric shock or fire may occ...

  • Page 6

    E- 5 english accessories selecting the installation location the following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. Pattern sheet insulation drain flexible hose rubber insulation cover band installation manual bushing bracket in...

  • Page 7

    E- 6 selecting the installation location (continued) space requirements for indoor unit 150 0(5 9) o r m ore 150 0(5 9) o r m ore 1500 (59) o r mo re 1500 (59) o r mo re unit : mm(inch) 미주향_dvms_1way cassette_im_en_03806a(1).Indd 6 2013-03-06 오후 5:58:15.

  • Page 8

    E- 7 english selecting the installation location (continued) no. Name description liquid pipe connection ø6.35(1/4") gas pipe connection ø12.70(1/2") drain pipe connection od ø29(1 1/8") power supply connection - air discharge grille - air suction grille - dimension of the indoor unit unit : mm(inch...

  • Page 9

    E- 8 concrete suspension bolt(ø9.52(3/8") or m10) hole in anchor hole in plug insert ceiling support it is recommended to install the y-joint before installing the indoor unit. 1 place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Since the diagram is made o...

  • Page 10

    E- 9 english indoor unit installation 4 screw eight nuts to the suspension bolts making space for hanging the indoor unit. You must install the suspension bolts more than four when installing the indoor unit. 5 check the level of the indoor unit by using a leveler. A tilt of the indoor unit may caus...

  • Page 11

    E- 10 purging the unit gas refrigerant port liquid refrigerant port g the designs and shape are subject to change according to the model. From factory the unit is supplied and set with a pre-charge of nitrogen gas (insert gas). Therefore, all insert gas must be purged before connecting the assembly ...

  • Page 12

    E- 11 english connecting the refrigerant pipe there are two refrigerant pipes of differing diameters: a smaller one for the liquid refrigerant a larger one for the gas refrigerant the inside of copper pipe must be clean & has no dust. 1 before connecting the reprigerant pipe, open the cover side. 2 ...

  • Page 13

    E- 12 cutting/flaring the pipes 1 make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder) 2 if you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctl...

  • Page 14

    E- 13 english performing leak test & insulation g the designs and shape are subject to change according to the model. Leak check leak test with nitrogen (before opening valves) in order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the r-410a, it’s responsible of ...

  • Page 15

    E- 14 performing leak test & insulation (continued) 5 select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size. Indoor temperature of 30°c(86°f) and humidity of 85% is the standard condition. If installing in a hi...

  • Page 16

    E- 15 english drain pipe and drain hose installation insulation drainpipe band band flexible hose drain hose port drainpipe adhesives insulation cover band insulation cover drain band(not supplied) indoor unit drain hose port care must be taken when installing the drainpipe and drain hose for the in...

  • Page 17

    E- 16 drain pipe connection 1 the drain pipe should be installed within 100mm(3.94") from the flexible hose, lift up from 100mm(3.94") to 550mm(21.65") and lift down 20mm(0.79") or more. 2 install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1~1.5m (3.28~4.92 ft)....

  • Page 18

    E- 17 english testing the drainage you should test drainage after completing the installation. Prepare a little water about 1.0 liter. 1 open the cover water supply intake. 2 pour water into the water supply intake. 3 operate the unit in the cool mode and check a drain pump pumping. 4 check drain wa...

  • Page 19

    E- 18 wiring work silver solder n l n l n l n l indoor unit 1 outdoor unit indoor unit 2 indoor unit 3 wired remote control 208-230v~ h elb : essential installation eev kit indoor unit 4 indoor unit 5 indoor unit 6 h ceiling, wall-mounted indoor unit. Selecting compressed ring terminal 1 before wiri...

  • Page 20

    E- 19 english wiring work h rating current unit model rating current amfn1dch 007 009 012 0.23 a 0.25 a 0.28 a specification of electronic wire power supply mccb elb power cable earth cable communication cable max : 242v min : 198v x a x a, 30mma 0.1 s 2.5mm 2 (0.004 inch 2 ) 2.5mm 2 (0.00...

  • Page 21

    E- 20 wiring work (continued) select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. For the power cable, use the grade of h07rn-f or h05rn-f materials. You should connect the power cable into the power cable terminal an...

  • Page 22

    E- 21 english setting an indoor unit address and installation option set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the address setting and indoor unit installation setting option at the same time. You need to se...

  • Page 23

    E- 22 setting an indoor unit address and installation option (continued) option setting status 1. Setting seg2, seg3 option press low fan button( ∨) to enter seg2 value. Press high fan button( ∧) to enter seg3 value. Each time you press the button,   …  will be selected in rotation. 2. Setting co...

  • Page 24

    E- 23 english setting an indoor unit address and installation option (continued) option setting status 12. Setting cool mode press mode button to be change to cool mode in the off status. 13. Setting seg16, seg17 option press low fan button( ∨) to enter seg16 value. Press high fan button( ∧) to ente...

  • Page 25

    E- 24 setting an indoor unit address and installation option (continued) 1. Check whether power is supplied or not. - when the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display) should be connected to an indoor unit to receive option. 3. ...

  • Page 26

    E- 25 english setting an indoor unit address and installation option (continued) 1. Check whether power is supplied or not. - when the indoor unit is not plugged in, there should be additional power supply in the indoor unit. 2. The panel(display) should be connected to an indoor unit to receive opt...

  • Page 27

    E- 26 setting an indoor unit address and installation option (continued) option no. : 02xxxx-1xxxxx-2xxxxx-3xxxxx 02 series installation option(detailed) option seg1 seg2 seg3 seg4 seg5 seg6 explanation page mode use of robot cleaning use of external room temperature sensor use of central control fa...

  • Page 28

    E- 27 english setting an indoor unit address and installation option (continued) option seg19 seg20 seg21 seg22 seg23 seg24 explanation page individual control of a remote controller heating setting compensation eev step of stopped unit during oil return/defrost mode motion detect sensor - remote co...

  • Page 29

    E- 28 setting an indoor unit address and installation option (continued) option no. : 05xxxx-1xxxxx-2xxxxx-3xxxxx 05 series installation option(detailed) 1) height difference : the difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place. For e...

  • Page 30

    E- 29 english changing a particular option option seg1 seg2 seg3 seg4 seg5 seg6 explanation page mode the option mode you want to change the tens’ digit of an option seg you will change the unit digit of an option seg you will change the changed value remote controller display indication and details...

  • Page 31

    E- 30 wireless remote control-buttons and display final checks and user tips to complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. 1 check the followings. Strength of the installation site tightness of pipe connection to detect a ...

  • Page 32

    E- 31 english troubleshooting if an error occurs during the operation, an led flickers and the operation is stopped except the led. If you re-operate the air conditioner, it operates normally at first, then detect an error again. Detection of errors led display on the receiver & display unit led dis...

  • Page 33

    E- 32 if you turn off the air conditioner when the led is flickering, the led is also turned off. If you re-operate the air conditioner, it operates normally at first, then detect an error again. When e108 error occurs, change the address and reset the system. Ex.) when address of the indoor unit #1...

  • Page 34: Memo

    E- 33 english memo 미주향_dvms_1way cassette_im_en_03806a(1).Indd 33 2013-03-06 오후 5:58:38.