Setra Systems 256 Installation Manual - Setra Model 256

Summary of 256

  • Page 1

    Installation guide 1-800-257-3872 toll free 1-978-264-0292 fax www.Setra.Com web site ✓ certified iso 9001 model 256 gage pressure transducer.

  • Page 2

    Industrial hvac test & measurement barometric ultra high purity/sanitary setra offers a complete line of products for these industries:.

  • Page 3: Table of Contents

    Table of contents 1.0 general information ............................................................................................... 4 2.0 mechanical installation ...................................................................................... 4 2.1 media compatibility ......................

  • Page 4: Setra Model 256

    4 setra model 256 pressure transducer 1.0 general information every model 256 has been tested and calibrated before shipment. Specific performance specifications are listed on page 7 of this guide. Setra systems 256 pressure transducers sense gage pressure and convert this pressure to a proportional...

  • Page 5: 3.0 Electrical Installation

    + ex c ex c gnd out + out voltage connections current connections screw terminal designations diagram 1 + ex c ex c gnd diagram 2 removable zero/span access plugs removable terminal block connector 5 3.1 voltage output units the model 256 is a 3-wire circuit. The -exc and -out are commoned on the ci...

  • Page 6: 4.0   Calibration

    3.2 current output units the 4-20 ma current output units are designed to have current flow in one direction only - please observe polarity. We suggest that the electrical conduit shield be connected to the system’s loop circuit ground to improve electrical noise rejection. The model 256 is a two-wi...

  • Page 7

    4.3 current output zero adjustment while monitoring the current output, and with the pressure port open to atmosphere or with zero pressure applied, the zero may be adjusted by turning the zero potentiometer screw. The factory setting is 4ma ( ± .08ma). 4.4 current output span adjustment span or ful...

  • Page 8

    8 6.0 returning products for repair please contact a setra systems application engineer (1-800-257-3872, 1-978-263-1400) before returning unit for repair to review information relative to your application. Many times only minor field adjustments may be necessary. When returning a product to setra sy...