Setra Systems SSC-2S Operation And Installation Instructions

Summary of SSC-2S

  • Page 1

    Introduction the sure-set current switch (ssc) series of digital output switches are noninva- sive devices designed to detect current flowing through a cable or wire. A cost effective solution for monitoring on and off status or proof of operation, these devices are ideal for monitoring the cur- ren...

  • Page 2: Installation

    Installation mounting 1. Shut off all power to the enclosure prior to installing. 2. Remove the sure-set mounting bracket from the main housing. 3. Using the two screws (included), at- tach the mounting bracket to the back of the electrical enclosure. (a piece of double side tape is included in the ...

  • Page 3

    Returning products for repair please contact a setra application engi- neer (800-257-3872, 978-263-1400) be- fore returning unit for repair to review information relative to your application. Many times only minor field adjustments may be necessary. When returning a prod- uct to setra, the material ...

  • Page 4: Symptom

    Symptom action ssc solid state output does not change state when motor current is changed. Insufficient current to the load to reach the selected setpoint threshold. Incorrect motor hp range selected verify that the sure-set range selector switch is set to the proper motor fla. Incorrect sure-set mo...