Range:
5° to 35° c.
Deadband:
1~5 deg C
(Adjustable)
Alarms:
2~45 deg C
(Adjustable)
After Hours:
0~4 Hours
(Adjustable)
Cal Offset:
+/- 6 C
(Adjustable)
Resolution:
1°c
Accuracy:
+/- 0.3°c
Load rating:
2 Amps @ 24 VAC max.
Lithium Bat:
10 Years
(Or 8 weeks accumulated power outage)
Voltage:
24VAC.
Connectors:
Screw type.
Material:
PC/ABS
Weight:
210g
Size:
82 x 140 x 27
Warranty:
1 year R.T.B
Rev G June 2007
Electrical Diagram
Optional 240V Interface available
Smart Temp
Optional Adjustable Remote Sensor
(Non Adjustable and Duct Mount Sensors available)
Specifications
Jumper
Position
JP6
Jp5
Jp4
JP7
JP3
Fan ON
immediate
with Heat call
(Elec. Heat)
Fan controlled
by plenum switch
(Gas. Heat)
4 min
Time
Delay
Time
Delay
Off
Clock
AM/PM
Clock
24 Hour
On
On
Off
Off
Must be
in this
position
JP-1
Position A = Internal Sensor
Position B = Remote Sensor
ISIS Heat Cool Configuration
Rev Valve
Energize “O”
(cooling)
Rev Valve
Energize “B”
(heating)
Jumper
Position
JP6
Jp5
Jp4
JP7
JP3
4 min
Time
Delay
Time
Delay
Off
Clock
AM/PM
Clock
24 Hour
Must be
in this
position
JP-1
Position A = Internal Sensor
Position B = Remote Sensor
ISIS Heat Pump Configuration
Optional Smart Pak Cover Shown
Smart Pak
Jp1
Internal or
Remote Sensor
Jp3 Compressor Protection
Jp4 12/24 hour clock
JP 5 Factory USE ONLY - N/A
Jp6 Heat Pump / Heat Cool select
JP7 Fan / RV Select
Battery
Holder
A
B
Flat cable connector
24 Volt Control
ISIS
Y1 Y2
O/B
W2 W3
AL AL Rc
Rh
C
Aux
G1 N/A
T1
T1
T0
T0
Heat Pump Connections
Remote
Override
Rerversing Valve
Auxilary Heat
Compressor 1
Compressor 2
Fan
24V Active
24V Common
Remote
Sensor
Fault Input
Alarm Output
Dry Contact (Max 24V)
Link must be installed
between RH &RC
Flat cable connector
24 Volt Control
ISIS
Y1 Y2 W1 W2 W3
AL AL Rc
Rh
C
Aux
G1 N/A
T1
T1
T0
T0
Heat / Cool Connections
Remote
Override
Heat 1
Heat 2
Heat 3
Cool 1
Cool 2
Fan
24V Active
24V Common
Remote
Sensor
Fault Input
Alarm Output
Dry Contact (Max 24V)
Link must be installed
between RH &RC
Smart Temp
Australia
Making Life Comfortable
N/A
N/A
N/A
N/A