Smart Temp SMT - 131 Manual - page 13
Page 13
4000
9
Read / Write
User Set Point
Deg C = 0.5°C Steps
Deg F = 1°F Steps
Value / 10 ( e.g. 23.5°C = 235)
400
10
Read / Write
Contact Reception
Notification
0 = Off
1 = Show Contact Reception on LCD
SMT-131 LCD will flash “Contact Reception”
on LCD and sound chime. User may accept
alert by touching any button on SMT-131
400
11
Read Only
Room
Temperature
Value / 10 (e.g. 21.7c = 217)
400
12
Read / Write
Temperature
Display
0 = Show Room and Set Temperature
1 = Show Set Temperature Only
400
13
Read / Write
C/F Display
0 = Deg C format
1 = Deg F format
400
14
Read / Write
User Set Point
High Limit
5°C to 30°C Range (41°F-86°F) in 1°C/F Steps
1:1
400
15
Read / Write
User Set Point
Low Limit
5°C to 30°C Range (41°f-86°F) in 1°C/F Steps
1:1
400
16
Read / Write
Dead Band
0.5°C to 5.0°C in 0.5°C Steps
1.0°F to 10.0°F in 1°F Steps
Value / 10 (e.g. 1.5°C Dead Band = 15)
400
17
Read / Write
Relay Span
0.5°C to 3.0°C in 0.5°C Steps
1°F to 10°F in 1°F Steps
Value / 10 (e.g. 1.0°C Span = 10)
400
18
Read / Write
Fan Purge Period
0 = Off
1 = Fan Purge - 1 Min
2 = Fan Purge - 3 Min
3 = Fan Purge - 5 Min
4 = Fan Purge - 10 Min
5 = Heat Only Fan Purge - 1 Min
6 = Heat Only Fan Purge - 3 Min
7 = Heat Only Fan Purge - 5 Min
8 = Heat Only Fan Purge - 10 Min
9 = Cool Only Fan Purge - 1 Min
10 = Cool Only Fan Purge - 3 Min
11 = Cool Only Fan Purge - 5 Min
12 = Cool Only Fan Purge - 10 Min
400
19
Read / Write
0-10V Heat Span
0.5°C to 3°C in 0.5°C Steps
1°F to 6°F in 1°F Steps
Value / 10 (e.g. Heat Span of 1°C= 10)
400
20
Read / Write
0-10V Cool Span
0.5°C to 3°C in 0.5°C Steps
1°F to 6°F in 1°F Steps
Value / 10 (e.g. Cool Span of 1°C = 10)
400
21
Read / Write
Auto Off Timer
0 = 0ff
1 to 10 Hours.
Value / 10 (e.g. 3 Hour Auto Off Timer = 30)
400
22
Read /Write
Unoccupied Heat
Set Point
0 = Off
5°C to 30°C in 0.5°C Steps
41°F to 86°F in 1°F Steps
Value / 10 ( e.g. 17°C Unoccupied Heat = 170)