Smart Temp SMT?770 Installer Manual - Setting
Other manuals for SMT?770:
Owner & User Manual, Installer Manual
Manual is about: Chameleon Multifunction
of
46
6
|
P a g e
Setting
the
hardware
switches
Switch
Off
On
Sw1
–
Fan
Speeds
1
Speed
Fan
3
Speed
Fan
Sw2
–
Equipment
Type
Heat
Cool
Heat
Pump
(O/B
terminals)
Sw3
–
Stages
1
Stage
2
Stages
Sw4
–
Reversing
Valve
If
Sw
2=
ON
–
Heat
Pump
Energise
in
cool
(O)
Energise
in
heat
(B)
Sw4
–
Fan
Mode
If
Sw
2=
OFF
–
Heat/cool
Fan
Control
by
Heater
(HG)
Fan
Control
by
T’stat
(HE)
Sw5
–
Anti
cycle
timer
Off
4
Minutes
Sw6
–
Operation
Manual
Thermostat
Programmable
Thermostat
Sw7
–
Minimum
Run
2
minutes
6
Minutes
Sw8
–
Program
Type
If
Sw
6=
ON
–
Programmable
Commercial
Program
Residential
Program
Sw8
–
Set
points
If
Sw
6=
OFF
–
Manual
Single
Set
point
Two
Set
points
Typical
drawings
have
been
provided
on
page
12
of
this
manual
that
will
assist
with
the
selection
of
the
correct
positions
for
these
function
switches.