    Doc. No.Vp4 * 50 * -omc0001-b product name 5 port solenoid valve model / series / product number vp4 * 50/vp4 * 70/vvp4 * 0 series.

  • Page 2: Contents

    Vp4 * 50 * -omc0001-b contents safety instructions --------------------------------------------------------------------------- 2,3 design / selection ---------------------------------------------------------------------------- 4,5 mounting ------------------------------------------------------------...

  • Page 3: Safety Instructions

    Vp4 * 50 * -omc0001-b safety instructions these safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of “caution,” “warning” or “danger.” they are all important notes for safety and must be...

  • Page 4: Safety Instructions

    Vp4 * 50 * -omc0001-b safety instructions caution 1.The product is provided for use in manufacturing industries. The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult smc beforehand and exchange ...

  • Page 5: Vp4

    - 4 - vp4 * 50 * -omc0001-b warning design / selection 1. Confirm the specification products represented in this manual are designed only for use in compressed air systems (including vacuum). Do not operate at pressures or temperatures, etc., beyond the range of specifications, as this can cause dam...

  • Page 6: Vp4

    - 5 - vp4 * 50 * -omc0001-b warning design / selection 5. Surge voltage intrusion with non-polar type solenoid valves, at times of sudden interruption of the loading power supply, such as emergency shutdown, surge voltage intrusion may be generated from loading equipment with a large capacity (power...

  • Page 7: Vp4

    - 6 - vp4 * 50 * -omc0001-b warning piping 1. Preparation before piping before piping is connected, it should be thoroughly blow out with air (flushing) or washed to remove chips, cutting oil and other debris from inside the pipe. 2. Wrapping of pipe tape when screwing piping or fittings into ports,...

  • Page 8: Vp4

    - 7 - vp4 * 50 * -omc0001-b warning warning operating environment 1. Do not use in an atmosphere having corrosive gases, chemicals, sea water, water, water steam, or where there is direct contact with any of these . 2. Do not use in an environment where flammable gas or explosive gas exists. Usage m...

  • Page 9: Vp4

    - 8 - vp4 * 50 * -omc0001-b manifold specification 1. When using 4 or more stations on the manifold, supply pressure from both sides of p port. 2. If several manifold valves are used at the same time, pressure drop may occur. Vp4350 (closed center) type precautions precautions at intermediate stop s...

  • Page 10: Trouble Shooting

    - 9 - vp4 ∗ 50 ∗ -omc0001-b trouble shooting remedy ( next page ) sound is emitted when the power is turned on foreign matter caught in core of solenoid valve (such as cylinder) side air leaks through exh. Port (pe port) of pilot valve a continuous loud buzzing foreign matter caught in the valve sli...

  • Page 11: Remedy

    - 10 - vp4 ∗ 50 ∗ -omc0001-b remedy no. Remedy ① connect the wires again correctly. ② replace the part. ③ replace the part or connect wires securely. ④ replace pilot valve assembly. ⑤ adjust pressure so that pilot pressure is within operating pressure range during opretation. - if the lubrication oi...

  • Page 12

    Vp4 * 50 * -omc0001-b revision history □ a renewal px □ b renewal uy 1st printing: cv 4-14-1, sotokanda, chiyoda-ku, tokyo 101-0021 japan tel: + 81 3 5207 8249 fax: +81 3 5298 5362 url http://www.Smcworld.Com note: specifications are subject to change without prior notice and any obligation on the p...