    Printed in u.S.A. 8/08 © copyright 2008 tac all rights reserved. F-24576-4 application the 2212-318 and 2212-319 dual setpoint/deadband pneumatic room thermostats are designed for the proportional control of pneumatic valves, damper actuators, or other final control devices in environmental control ...

  • Page 2

    2 © copyright 2008 tac all rights reserved. F-24576-4 ordering data table-1 model chart — thermostats. Wholesale number replaces model action description 2212-318 t35-301 direct includes (2) 1/4" x 3/16" barbed couplings, 6" piece of polyethylene tubing, 20-714 wall plate, 20-711 mounting plate, and...

  • Page 3

    F-24576-4 © copyright 2008 tac all rights reserved. 3 requirements • tools (not provided): – appropriate screwdriver for mounting the thermostat – 20-881 thermostat calibration and cover screw wrench (or 1/16” and 1/4” hex wrenches) • training: installer must be a qualified, experienced technician •...

  • Page 4

    4 © copyright 2008 tac all rights reserved. F-24576-4 optional mounting eliminate the pipehead fitting by using the 22-022 thermostat conversion kit and the included instructions, plus the following: 1/4" plastic air lines: install the 1/4" barbed couplings into the air lines. Connect the tube assem...

  • Page 5

    F-24576-4 © copyright 2008 tac all rights reserved. 5 operation the deadband output (branch) pressure is factory set at 8 psig (55.2 kpa), placing both heating and cooling actuators in the “off” (or closed) position. The output remains at that pressure while the ambient (room) temperature varies wit...

  • Page 6

    6 © copyright 2008 tac all rights reserved. F-24576-4 2. To calibrate the cooling dial, the heating dial must first be turned to the 57°f setting. This moves the heating bimetal away from the deadband lever. Turn screw “b” to obtain 10.5 psig. If there is a difference between the ambient temperature...

  • Page 7

    F-24576-4 © copyright 2008 tac all rights reserved. 7 maintenance the thermostat requires no maintenance. Regular maintenance of the total system is recommended to assure sustained, optimum performance. Field repair none. Replace an inoperative thermostat with a functional unit. Dimensional data 1-1...

  • Page 8