Jumper Selection
(CP-8552 Only)
Note:
The CP-8552 is factory calibrated for the 4 to 20 mA and 0 to 10 V ranges. Switching
to the 6 to 9 V range requires recalibration of the start point and span potentiometers.
The CP-8552 has three jumper selectable input ranges. Refer to Figure-4 for jumper block
detail. Make proper jumper selection as follows:
1. Choose input range.
2. Consult Table-1 for jumper position.
3. Place jumper over square posts on appropriate lettered block (Figure-4 ).
4. Calibrate by performing appropriate CHECKOUT procedure.
Table-1 CP-8552 Jumper Selection.
Figure-4 CP-8552 Internal View.
Range
x = Insert jumper at position shown in chart.
A
B
C
4 to 20 mA
X
6 to 9 V
X
0 to 10 V
a
X
a
CP-8552 factory supplied at 0 to 10 V input.
Wiring
terminations
Zero adjust
potentiometer
Jumper
Square
post
Jumper
block
Span adjust
potentiometer
Transducer
A B C
1
2
3
Start point
potentiometer