    Printed in u.S.A. 9-08 © copyright 2009 tac all rights reserved. F-25906-2 application the tp-16xx series are electronic modulating room thermostats designed to be wall-mounted and used in fan coil applications. These thermostats incorporate an attractive case and are available in either celsuis or ...

  • Page 2

    2 © copyright 2008 tac all rights reserved. F-25906-2 specifications setpoint dial range: 55 to 85 °f or 5 to 30 °c.Refer to table-1 for scale. Operating voltage: 24 vac, 50/60 hz. Power consumption: 0.35 watts at 24v. Fan power supply: 24 to 240 vac, 50/60 hz. Sensing element: electronic sensor. De...

  • Page 3

    F-25906-2 © copyright 2008 tac all rights reserved. 3 typical applications (wiring and function diagrams) refer to figure-2 through figure-2 for wiring diagrams and function diagrams of the tp-16xx series thermostats. Figure-1 wiring diagram for tp-1601. Figure-2 function diagram for tp-1601. Tp-160...

  • Page 4

    4 © copyright 2008 tac all rights reserved. F-25906-2 figure-3 wiring diagram for tp-1611 and tp-1616. Figure-4 function diagram for tp-1611 and tp-1616. Tp-1611, tp-1616 remote sensor 11 remote sensor 12 heating 2 24 vac supply 4 fan medium 21 fan supply 19 fan high 22 n l 1 2 fan low 20 cooling 6 ...

  • Page 5

    F-25906-2 © copyright 2008 tac all rights reserved. 5 installation inspection inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Requirements • job wiring diagrams ...

  • Page 6

    6 © copyright 2008 tac all rights reserved. F-25906-2 6. Extend, from the wall, the wires that will be connected to the thermostat. 7. Connect the wires to the screw terminals on the thermostat. Refer to the applicable wir- ing diagram in figure-2 or figure-2 . C a u t i o n • always connect the neu...

  • Page 7

    F-25906-2 © copyright 2008 tac all rights reserved. 7 checkout following installation, allow a thermostat to acclimatize to the environment for at least 2 hours before attempting to test its accuracy. After the newly-installed thermostat has acclimatized, perform an initial check of the switching ac...

  • Page 8