TAC 2413 Handbook - Technical Data

Summary of 2413

  • Page 1

    Controller tac 2413 handbook 0-004-7614-0 (gb), 1998-10-23 100 % 0 % + + tac improves indoor climate and reduces operating costs through open solutions for demanding users..

  • Page 3: Tac 2413 Handbook

    Tac ab, 1998-10-23 contents 0-004-7614-0 (gb), i (ii) tac 2413 handbook tac 2413 handbook this document contains information which is the property of tac and is therefore made available only to those who use and maintain tac equipment. Disclosure of, copying or using this document or the information...

  • Page 4

    Tac ab, 1998-10-23 contents tac 2413 handbook ii (ii), 0-004-7614-0 (gb) 5.1 mounting ............................................................................................................................................ 5:1 5.2 connection .........................................................

  • Page 5: This Handbook

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 1:1 (4) tac 2413 handbook this handbook 1 this handbook 1.1 overview chapter 2, the air handling controller tac 2413 this chapter provides a short introduction to the controller. Chapter 3, using the operator’s panel this chapter will provide you with a more det...

  • Page 6: 1.2

    1:2 (4), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook this handbook index at the end of the handbook, you will find an index containing page references. 1.2 how you may use this handbook the tac 2413 handbook describes all the functions and procedu- res that are needed to install, commissi...

  • Page 7

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 1:3 (4) tac 2413 handbook this handbook supplementary documentation there is more information to be found in the document below. It may be ordered from your nearest tac sales or service office: • data sheet tac 2000 (part number 0-003-1745).

  • Page 8

    1:4 (4), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook this handbook blank page..

  • Page 9: 2.1

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 2:1 (2) tac 2413 handbook the air handling controller tac 2413 2 the air handling controller tac 2413 tac 2413 is a digital controller which is able to control, monitor and supervise air handling units (ahu) in buildings. Tac 2413 controls the room temperature o...

  • Page 10

    2:2 (2), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook the air handling controller tac 2413 ff01 st21 st22 gt31 gt71 gp71 gt81 p01 sv21 lv01 lk01 p02 sv51 gp61 tf01 gt11 gt21 gt41 sn01 st41 gx41 gx21 you can choose if you want room or supply air control by using dip switch 1. During room co...

  • Page 11: Using The Operator’S Panel

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 3:1 (6) tac 2413 handbook using the operator’s panel 3 using the operator’s panel 3.1 introduction this chapter will show you how to use the buttons of the operator’s panel to read and set parameters, such as temperatures, for example. 3.2 what is shown in the d...

  • Page 12

    3:2 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook using the operator’s panel 3.2.1 parameter numbers and parameter values the controller has a list of 100 parameters ranging from 0 to 99. Some of these parameters may be set, such as the room tempera- ture setpoint; others, however, can...

  • Page 13

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 3:3 (6) tac 2413 handbook using the operator’s panel 3.2.2 operating modes the different operating modes of the controller are shown in the display window by means of the symbols below. The symbols of the operating modes of the controller the symbols are interpr...

  • Page 14

    3:4 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook using the operator’s panel 3.2.3 weekly program the weekly program is shown as a 24 hour time bar from 00:00 to 24:00 for each day of the week. The part of the bar that is filled shows when daytime operation applies. The symbols of the ...

  • Page 15

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 3:5 (6) tac 2413 handbook using the operator’s panel 3.2.4 outputs of the controller the controller has a number of outputs for control, such as for the heating coil, and for controlling external units, such as the heating coil pump. When an output is active, it...

  • Page 16: 3.3

    3:6 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook using the operator’s panel 3.3 how are the buttons used? The controller has five buttons located below the display window. The buttons on the operator’s panel the and buttons are used to choose a parameter. The and buttons are used to c...

  • Page 17: Day-to-Day Usage

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 4:1 (6) tac 2413 handbook day-to-day usage 4 day-to-day usage 4.1 introduction this chapter provides enough information for you to be able to read and set temperatures and other parameters during normal operation. All parameters and functions are explained in de...

  • Page 18: 4.3

    4:2 (6), 0-004-7614-0 (se) tac ab, 1998-10-23 tac 2413 handbook day-to-day usage 4.3 setting temperatures procedure for setting a temperature: 1 choose the parameter number (p no.) by using or . You can increase the number by pressing and decrease it by pressing . 2 change the temperature by using o...

  • Page 19

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 4:3 (6) tac 2413 handbook day-to-day usage parameter p no. Weekly program 1/2 speed p 12 4.4.2 weekly program 1/1 speed for 1/1 speed to take effect, the weekly programs for both 1/2 speed and 1/1 speed operation have to be active. The 1/1 speed program is not s...

  • Page 20

    4:4 (6), 0-004-7614-0 (se) tac ab, 1998-10-23 tac 2413 handbook day-to-day usage procedure for setting a holiday period: 1 choose parameter number p 15 by using or . The parameter number is increased by using and decreased by using . 2 choose a holiday period (1–6) by using or . 3 confirm by using ....

  • Page 21: 4.5

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 4:5 (6) tac 2413 handbook day-to-day usage 4.5 reading and resetting alarms when an alarm is tripped, the symbol ! Will flash together with the symbol that the alarm is referring to. There are two types of alarms, a alarms and b alarms. Some alarms offer the opp...

  • Page 22: 4.7

    4:6 (6), 0-004-7614-0 (se) tac ab, 1998-10-23 tac 2413 handbook day-to-day usage chosen mode symbols in the display window timed operation , and depending on the time schedule, 1 1 or 1 2 . Manual control 1 2 (one speed operation) or 1 1 with . 4.7 setting the clock to show the current time, choose ...

  • Page 23: Installation

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 5:1 (8) tac 2413 handbook installation 5 installation 5.1 mounting controller position the controller so that it is easy to read and to set values and so that the cover can be opened. The permissible ambient temperature and humidity range must not be exceeded. T...

  • Page 24

    5:2 (8), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook installation the controller can be mounted in three different ways: • directly on a wall • on a norm rail en 500 22 (ts 35 mm) • in a panel, with or without a backplate procedure for mounting controller on a norm rail en 500 22: 1 place...

  • Page 25

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 5:3 (8) tac 2413 handbook installation fastening device procedure for mounting controller in a panel: 1 make an opening in the panel as shown in the adjacent scale drawing. The maximum panel thickness is 5 mm. 2. Remove the backplate from the electronic part (se...

  • Page 26: 5.2

    5:4 (8), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook installation 5.2 connection connect the cables to the controller as shown in the wiring diagram. Warning! All power cables should be installed by an authorised electrician. All equipment which is connected to the controller must comply ...

  • Page 27

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 5:5 (8) tac 2413 handbook installation wiring diagram with the valve actuators em5, em42 * does not need to be connected ** k1: contactor tf01 k2: contactor ff01 n.B.! These drawings only show the units that may be connected to tac 2413 using a heat exchanger as...

  • Page 28: 5.3

    5:6 (8), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook installation y1 15 y2 14 12 k6 11 k6 9 g 8 g0 7 6 kc1 5 k1 4 k2 3 k3 2 k4 1 k5 m m u1 u2 u3 m b1 m b2 b3 b4 x3 u4 x1 x2 m l r 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 10 16 13 10 y3 5.3 terminal blocks the location of the terminal blocks in ...

  • Page 29: 5.5

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 5:7 (8) tac 2413 handbook installation no off on 5.5 commissioning the following should be done before switching on the power: 1. Check that sensors and actuators are connected correctly. 2. Set the dip switch to configuration. Access to the dip switch can be ga...

  • Page 30

    5:8 (8), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook installation blank page..

  • Page 31: Troubleshooting

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 6:1 (2) tac 2413 handbook troubleshooting 6 troubleshooting tac 2413 is normally a very reliable controller. If there should be any problem in spite of this, you may use the following tips for troubleshooting. If you need further help, please contact your ne- ar...

  • Page 32

    6:2 (2), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook troubleshooting problem check that... The temperature in the • the ahu is in timed operation and ventilation system is too high no holiday program is active • an alarm has not stopped the ahu • high current protectors and power switches...

  • Page 33: Functional Description

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:1 (24) tac 2413 handbook functional description 7 functional description 7.1 introduction this chapter contains a description of all the functions of the controller. At the end of every section is a list of parameters. How parameters are read and set is descri...

  • Page 34

    7:2 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description when the controller is in the timed operating mode, and the holiday period starts, the clock symbol will be shown in the display window and the ahu stops. Air handling off when the controller is “off”, the symbol...

  • Page 35: 7.3

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:3 (24) tac 2413 handbook functional description 7.3 air handling 7.3.1 fan operation the fans are controlled by the built-in time program with separate ti- mes for half and full speed, respectively, or via manual control by using the buttons. Full speed is dis...

  • Page 36

    7:4 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description the heat recovery is controlled to 100 % when ff starts, and the posi- tion of the heating valve is determined by the outdoor temperature. It is completely closed at outdoor temperatures ≥ 10 °c, and opens on a l...

  • Page 37

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:5 (24) tac 2413 handbook functional description p no. Parameter min max factory set. Change comment p 18 output signal to hex (%) 0 100 p 19 output to heating valve (%) 0 100 p 20 output to cooling valve (%) 0 100 p 21 winter/summer period 0 1 (0/1) confirms t...

  • Page 38

    7:6 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description p no. Parameter min max factory set. Change comment p 02 supply air temp. Setpoint calculated p 04 room/exhaust air temp. Sp calculated p 10 heating setpoint 0 °c 50 °c 20 °c p 11 cooling setpoint 0 °c 50 °c 22 °...

  • Page 39

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:7 (24) tac 2413 handbook functional description the winter compensation starts when the outdoor temperature is be- low “start winter compensation”. The maximum compensation is achieved when the outdoor temperature is less than or equal to “stop winter compensa...

  • Page 40

    7:8 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description if the mixed air damper has been chosen, 100 % return air applies during night heating operation. If heat recovery is chosen, there is normal operation. In both cases, the normal setpoints apply. P no. Parameter ...

  • Page 41

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:9 (24) tac 2413 handbook functional description 7.3.6 co 2 / spc this function is chosen by using parameter p 55; 0 = no function, 1 = spc, and 2 = co 2 . By connecting an external 2–10 v dc control voltage to the spc in- put, the current setpoint can be shift...

  • Page 42

    7:10 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description p no. Parameter min. Max. Factory set. Change comment p 55 spc/co 2 0 0=no function, 1=spc, 2 = co 2 p 56 spc effect 0 °c 32 °c 0 °c at 2 and 10 v, respectively p 57 co 2 setpoint 0 v 10 v 4 v p 93 spc/co 2 inpu...

  • Page 43

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:11 (24) tac 2413 handbook functional description the exhaust air sensor is also used as a limitation sensor to pre- vent freezing of the hex. A separate controller monitors the tem- perature compared to the value of p 38 and will limit the output signal to the...

  • Page 44

    7:12 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description 7.3.9 heating coil when the heating demand cannot be met, in spite of the heat recovery ahu controller being set to maximum recovery, the control sequence will include the heating coil. The control signal of the...

  • Page 45

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:13 (24) tac 2413 handbook functional description p no. Parameter min. Max. Factory set. Change comment p 06 return temp., heating coil measured value p 19 output signal, heating valve p 26 min. Supply air temp. 0 °c 50 °c 14 °c setpoint, heating control p 28 m...

  • Page 46

    7:14 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description pump exercise the pump is exercised once a day at 12:00 noon–12:01 in order to prevent seizures during the summer months, for example. P no. Parameter min. Max. Factory set. Change comment p 35 outdoor temp limi...

  • Page 47

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:15 (24) tac 2413 handbook functional description the controller will return to heating control only when the supply air or room temperature has dropped to the “heating setpoint”. The con- trol principle for both heating and cooling is to provide the highest po...

  • Page 48

    7:16 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description 7.3.12 cooling coil, dx cooling, d x dx cooling may be chosen by using dip switch 6, and the choice is only valid if room control applies. One step is controlled using k5, and if there are several steps, they ar...

  • Page 49

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:17 (24) tac 2413 handbook functional description the negative hysteresis may not be greater than the difference bet- ween the heating and cooling setpoints, however. In this way, one dx step may be controlled via k5, or several dx steps may be controlled by us...

  • Page 50: 7.4

    7:18 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description 7.4 clock the controller contains a calendar clock which switches to and from summer time automatically, as well as compensating for leap years. The clock must be set manually after a power failure which lasts f...

  • Page 51: 7.5

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:19 (24) tac 2413 handbook functional description 7.5 timer programs tac 2413 contains two weekly programs (1/1 and 1/2 speed) which control how the ahu starts and stops. Apart from the weekly pro- grams, there is a yearly program containing six holiday periods...

  • Page 52

    7:20 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description fan alarm during waterborne heating when there is a fan alarm, the ! Symbol flashes, and “tf” and “ff” are shown in the display window. The alarm is disabled during 60 seconds when tf is started. If it is trippe...

  • Page 53

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:21 (24) tac 2413 handbook functional description 7.6.3 frost protection alarm when the frost protection alarm is tripped, the symbols ! And + will flash in the display window. When there is a risk of the heating coil freezing, the frost protection sensor in th...

  • Page 54

    7:22 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description 7.6.5 freezing alarm the symbols ! And + will flash when the freezing alarm is tripped. It is tripped if the defrosting has been activated by way of a closing contact from the pressure sensor and not been stoppe...

  • Page 55: 7.7

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 7:23 (24) tac 2413 handbook functional description 7.6.7 deviation alarm the symbols ! And “°c” will flash in the display window when the deviation alarm is tripped. If the supply air temperature deviates from the setpoint by more than an adjustable limit, which...

  • Page 56

    7:24 (24), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook functional description blank page..

  • Page 57: Technical Data

    Tac ab, 1998-10-23 0-004-7614-0 (gb), 8:1 (2) tac 2413 handbook technical data 8 technical data thermistor inputs thermistor type ..................................................... 1800 Ω /25 °c measurement range: supply air temperature, b1 ........ 0 °c – +45 °c outdoor temperature, b2 ....... -...

  • Page 58

    8:2 (2), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook technical data clock accuracy ........................................ ±16 minutes/year at +25 °c memory backup ...................... 48 hours; no battery is required power supply operating voltage ............................. 24 v ac...

  • Page 59: List of Parameters

    Tac ab, 1998-10-23 0-004-7614-0 (gb), app:1 (6) tac 2413 handbook commissioning protocol/list of parameters appendix a: commissioning protocol/ list of parameters off on off on default change supply air control room/return air control off room control (if 1=on) return air control (if 1=on) off hex m...

  • Page 60

    Tac 2413 handbook commissioning protocol/list of parameters app:2 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 p no. Parameter min. Max. Step default change comment p 00 time. Indication and off, manual, timed operation choice of operating mode 1/2 and 1/1 speed p 01 supply air temperature 0,1 °c measu...

  • Page 61

    Tac ab, 1998-10-23 0-004-7614-0 (gb), app:3 (6) tac 2413 handbook commissioning protocol/list of parameters time delay (s) 150 100 50 5 outdoor temperature (°c) –30 –20 –10 0 10 20 30 p 33 p 34 heating valve starting pos’n 0 % 100 % 1 % 50% at – 10 ° c p 35 outdoor temp. Limit for pump 0 °c 50 °c 0,...

  • Page 62

    Tac 2413 handbook commissioning protocol/list of parameters app:4 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 p 59 i time supply air controller 1 min 20 min 1 min 4 min during hex control p 60 p band supply air controller 1 °c 100 °c 0,1 °c 25 °c (0,5x at 1/1 speed) during heating control p 61 i time,...

  • Page 63

    Tac ab, 1998-10-23 0-004-7614-0 (gb), app:5 (6) tac 2413 handbook commissioning protocol/list of parameters p no. Parameter min. Max. Step default change comment p 66 p band, holding controller 1 °c 400 °c 0,1 °c 200 °c p 67 i time, holding controller 1 min 20 min 1 min 4 min p 68 p band, supply air...

  • Page 64

    Tac 2413 handbook commissioning protocol/list of parameters app:6 (6), 0-004-7614-0 (gb) tac ab, 1998-10-23 blank page..

  • Page 65: Index

    Tac ab, 1998-10-23 0-004-7614-0 (gb), ind:1 (2) tac 2413 handbook index index o operating mode priority 7:2 p parameter numbers 3:2 parameter values 3:2 r reading and resetting alarms 4:5 reading temperatures 4:1 s setting a holiday period 4:4 setting temperatures 4:2 setting the clock 4:6 setting t...

  • Page 66

    Ind:2 (2), 0-004-7614-0 (gb) tac ab, 1998-10-23 tac 2413 handbook index blank page..

  • Page 67

    Tac ab, 1998-10-23 tac 2413 handbook reply form you can help us make this handbook even better! In order to be able to make user-friendly documents, we kindly ask for your help. We would like you to make notes of possible errors or suggestions for improving this handbook. Send this form to: alternat...

  • Page 68

    Tac ab, 1998-10-23 tac 2413 handbook reply form.

  • Page 69

    Tac ab, 1998-10-23 tac 2413 handbook reply form.

  • Page 70

    Tac ab, 1998-10-23 tac 2413 handbook reply form tac ab, jägershillgatan 18, se-213 75 malmÖ, sweden, +46 40 38 68 50 (switchboard).