Tanda TX7120 Installation And Operation Manual - page 7
TX7120 Intelligent Smoke & Heat Detector
Installation & Operation Manual
4050100264-Rev1.1-0815
TANDA UK
Specifications are subject to change without prior notice
7
3.3 Set: LED On/Off
1.
The LED can be turn-off if desire, the sensing ability of the detector will not disrupt even the
LED is off.
2.
Attach the programming cable to 1 and 6 Terminals of detector. Press
“Power”
to switch-on
the unit.
3.
Switch-on the programmer, then press button
“4”
to enter to Setting
mode (Figure 7). The
programmer will display the actual configuration after few seconds.
4.
Input the
“1”
then press
“Write”
to change the setting (Figure 8) and LED will turn-off. To
resume the default setting, press
“Clear”
and then press
“Write”
.
5.
Press
“Exit”
key to go back Main Menu. Press
“Power”
to switch off the programmer.
3.4 Read Configuration
1.
Attach the programming cable to 1 and 6 terminals of detector. Press
“Power”
to switch on
the unit.
2.
Switch-on the programmer, then press button
“Read”
or
“1”
to enter to Read
mode (Figure 9).
The programmer will display the configuration after few seconds. (Figure 10).
3.
Press “
Exit”
key to go back Main Menu. Press “
Power”
key to switch off the programmer.
1. Read
2. Write T
3. R/W Config
7
4. Set
Parameter: 1
Success
1. Read
2. Write T
3. R/W Config
7
4. Set
Address: 123
Base Value: 007
ID: 123456789012
Parameter Description
0-
LED On (Default)
1-
LED Off
Read Description
Address
: Unique number
assigned
Base: Value
: Detector status
value
ID
: Detector serial number
Figure 7
Figure 8
Figure 9
Figure 10