TANDBERG MSERIES Installation Manual - page 42
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
42
Connecting the Library to AC Power
3-4
Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
Connect all libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
5-10
Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
Select one of the following options:
• Connect no more than 4 libraries to each
AC distribution unit rated 15A or 20A, with
a minimum 14AWG three wire cord, and a
15A or 20A plug. Must be three wire
grounding plug and wall outlet.
• Connect all libraries to one AC distribution
unit rated 20A, with a minimum 14AWG
three wire cord, with a 20A plug. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 20A, with a minimum
14AWG three wire cord, permanently
wired to the electrical supply and have a
ground warning label.
# of
Library
Modules
Distribution Unit Requirements
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)