TCS Basys Controls SZ1017a Product Manual - page 6
2800 LAURA LANE
❘
MIDDLETON, WI 53562
❘
(800) 288-9383
❘
FAX (608) 836-9044
❘
www.tcs-basys.com
6
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
HEAT STAGE 1
2F
20.
DIFF:
STAGE 2
1F
DIFF:
HEAT STAGE 1
19.
OFFSET:
0F
STAGE 2
OFFSET:
1F
ENABLE THIRD
COOL
STAGE AS:
18.
STAGE 1
1F
DIFF:
17.
STAGE 1
OFFSET:
STAGE OUTPUT 1&2
AS:
16.
HEAT
SET OVERRIDE
15.
TIME: 180 MINUTES
LIMIT SETPOINT
5F
ADJUST +/-:
14.
program
setup
21.
HEAT STAGE 2
OFFSET:
2F
SET CONTROL
MODE:
program
setup
22.
HEAT STAGE 2
2F
DIFF:
TIMECLOCK OUTPUT
SZ1017a
Go to #23d. p. 10
SZ1051
Go to #23a. p. 8
SZ1053
Go to #23c. p. 9
SZ1041
Go to #16b. p. 7
0F
P+I
OCCUPIED=CLOSED
User Setpoint Limit Screen. Enter the
number of degrees you want the user to
be allowed to change the preset occu-
pied setpoints up or down.
Override Time Screen. Enter the num-
ber of minutes (0 to 255) that the ther-
mostat will maintain occupied setpoints
when overridden.
Stage Mode Screen. Choose whether
stage 1 and 2 perform heating or cool-
ing functions, or whether both stages
are to be disabled.
Stage 1 Offset Screen. Enter an offset
value for stage 1. First stage is normally
0 offset. This screen is not displayed if
stage outputs 1 and 2 are disabled.
Stage 1 Differential Screen. Enter a
differential value for stage 1. This
screen is not displayed if stage outputs
1 and 2 are disabled.
Stage 2 Offset Screen. Enter an offset
value for stage 2. This screen is not dis-
played if stage outputs 1 and 2 are dis-
abled.
Stage 2 Differential Screen. Enter a
differential value for stage 2. This
screen is not displayed if stage outputs
1 and 2 are disabled.
Control Mode Screen. Enter whether
you want to control by temperature only
(P) or add a time factor (P+I). This is
applied to both stage outputs.
Time Clock Output Screen. Choose
whether the auxiliary output will be
OPEN during occupied periods (and
closed during unoccupied periods) or
CLOSED during occupied periods (and
open during unoccupied periods).
program
setup
program
setup
program
setup
program
setup
48.
DI3 USED FOR:
FILTER SERVICE
47.
ENABLE SMART
YES
RECOVERY?
SET DI2 SETPOINT
02F
SHIFT:
46.
DELAY ON POWERUP
60 SECONDS
DI2 USED FOR:
MONITOR
DI3 USED FOR:
FILTER SERVICE
45.
DI1 USED FOR
MONITOR
program
setup
program
setup
50.
RECOVERY?
ENABLE SMART
YES
49.
DELAY ON POWERUP
10 SECONDS
program
setup
program
setup
program
setup
MON
12:00AM
11-19-01
72F
SET ACCESS
53.
CODE:
52.
REQUIRE CODE FOR
CLOCK/SCHED?
51 .
REQUIRE CODE FOR
PROGRAMMING? YES
YES
000
DI1 Choice Screen. Choose DI1 as FAN
PROVING or a MONITOR point. Select
MONITOR if unused.
DI2 Choice Screen. Choose DI2 as SER-
VICE, AQUASTAT, or MONITOR. Select
MONITOR if unused.
DI2 Shift Screen. Enter the setpoint shift
value. This screen will only appear if DI2 is
set to MONITOR.
DI3 Choice Screen. Choose FILTER SER-
VICE, EXTernal OVERRIDE, or EXTernal
TIME CLOCK. Select EXTernal OVERRIDE if
unused.
Delay On Powerup Screen. Enter a value
in seconds, such that when the unit is pow-
ered up, control is delayed for this amount
of time.
Smart Recovery Screen. Choose whether
or not smart recovery will be used. Note:
Smart Recovery is not available when DI3
is used as EXTernal TIME CLOCK.
Programming Access Screen. Choose
whether or not a code will be required to
enter programming setup. A dipswitch option
to lock out access altogether is also available.
Clock and Schedule Access Screen.
Choose whether or not a code will be
required to enter clock and schedule setup.
A dipswitch option to lock out access alto-
gether is also available.
Access Code Screen. Enter an access (0 to
255) code that will be used to enter the pro-
gramming and/or clock and schedule setups if
access code has been required in the last two
steps. The default is 248.
Main Monitoring Screen. (Date not shown
on SZ1017a.)
(Instructions continued on page 11.)