TCS Basys Controls SZ1017N Product Manual

Manual is about: Modulating Thermostat with 7-day Time Clock

Summary of SZ1017N

  • Page 1

    Description the sz1017n is a thermostat with a 7-day time clock designed for applications with modulating heating or cooling. Features ! Stand-alone or network operation ! 7-day time clock ! Discharge air sensor input with high and low limits and reset ! Outdoor air sensor input with heating & cooli...

  • Page 2: Caution

    Wiring the sz1017n uses standard terminal designations for wiring. See diagram below. Remote sensor wiring use 18 awg shielded twisted-pair grounded at the sensor mounting location. Sensor wiring runs of up to 250 feet are attainable if properly shielded wire is used and the installation environment...

  • Page 3

    Keypad access the dipswitches in the cover (shown above connected with ribbon cable) must be set in order to lock the user out of programming and/or to set the clock and schedule. Use the guide below to set these dipswitches for your application. Otherwise, user access may be limited with an access ...

  • Page 4

    Programming the sz1017n may be programmed through the display and keypad, or with a pc. If programming with a pc, the following must be set through the keypad prior to programming: ! Address (step #3) ! Temperature scale (step #4) for more information on programming through the pc, con- sult your so...

  • Page 5

    Program setup program setup program setup program setup program setup program setup program setup program setup 30. Discharge air low limit: 45f 29. 28. Enable discharge air sensor? Yes setpoint offset: 00f 27. Unoccupied action 25. Modulating modulating out range: 4-20 ma 24. Output action: . Direc...

  • Page 6

    Program setup program setup program setup program setup program setup program setup program setup program setup 39. Di2 used for: service 38. 37. Di1 used for fan proving heating lockout temp: 70f 36. Cooling lockout 35. Temp: 80f enable outdoor air sensor? Yes 34. Reset ratio 33. Factor: 2f 32. Dis...

  • Page 7

    Setting clock & schedule the sz1017n clock and schedule may be set through the keypad on the face, or with a pc. For more information on programming through the pc, consult your software manual. Setting clock & schedule through the keypad to access the clock and schedule screens, press the clock set...

  • Page 8

    Air temperature rises 2° above the lockout temperature. If the outdoor temperature rises above the heating lock- out temp, all heating stages will be locked out and will remain locked out until the outdoor air temperature falls 2° below the lockout temperature. The outdoor air span is -40 to 160 °f ...

  • Page 9

    Analog output parameters use programming steps #22 through #26 to program the operating parameters for the analog output. Select whether the analog output is set for heating, cooling or aquastat. Select direct or reverse action. Select whether you want the analog output to modulate from 4 to 20ma or...

  • Page 10

    3. Press the program setup button until you reach the screen # 14 which allows you to set the occupant set- point adjustment limits. Change this to +/-20 °f (11.1 °c). Press the program setup button once more to store the change. Then press the service status but- ton once to exit the programming. 4...

  • Page 11

    Analog output not working properly check wiring. A separate transformer should be used for the sz1017n and a separate transformer should be used for the damper motor(s). Check to make sure that the analog output is programmed correctly. Check the service menu. The mod out screen will tell you what t...

  • Page 12: 800-288-9383

    User’s guide inside the hinged door of the thermostat is the superstat tm user’s guide. This guide is designed to assist the installer in explaining to the end user how to operate their new thermostat, as well as serve as a handy future reference for the end user. We recommend that the installer fil...

  • Page 13

    Pointmap table for sz1017n npt npa units point description range/value additional notes adi 1 # di2 control mode 0=aquastat, see programming step #39. 1=monitor, 2=service adi 2 # unocc analog output action 0=0or4 ma, 1=20 ma see programming step #26. 2=modulating adi 3 # analog output mode 0=heat, ...

  • Page 14

    Pointmap table for sz1017n (continued) npt npa units point description range/value additional notes adi 39 minutes monday occupied start time 0-1439 for schedule b adi 40 minutes monday occupied end time 0-1439 for schedule b adi 41 tuesday 0-1439 adi 42 tuesday 0-1439 adi 43 tuesday 0-1439 adi 44 t...

  • Page 15

    Pointmap table for sz1017n (continued) npt npa units point description range/value additional notes bd 17 di1 source 0=local contact "local" means read by or controlled by thermostat. 1=remote request "remote" means the state of the input or output is controlled only by computer. Bd 18 di2 source 0=...

  • Page 16

    Rev: 1000 r 2800 laura lane i middleton, wi 53562 i (800) 288-9383 i fax (608) 836-9044 i www.Tcs-basys.Com 16.