Theben TR 635 top2 Installation And Operating Instructions Manual

Summary of TR 635 top2

  • Page 1

    309563 03 gb tr 635 top2 0 6 12 18 24 menu ok tr 635 top2 connection of different external wires is permitted installation and operating instructions digital time switch with weekly program tr tr 635 top2 6350100 tr 636 top2 6360100 d gb f i e nl.

  • Page 2: Contents

    2 contents basic advice 3 screen and keys 4 operating instructions 4 overview of menu selection 5 connection/installation 6 initial start-up 8 reset 8 menu item program set switching time 9 change/request switching time 11 delete switching time 11 pulse programming 12 cycle programming 13 menu item ...

  • Page 3: Basic Safety Instructions

    3 basic safety instructions • the device is intended for wall and front panel installation • corresponds to type 1 bstu in accordance with iec/en 60730-2-7 • power reserve (10 years) is reduced if memory card is inserted (in battery operation) designated use • the time switch can be used for lightin...

  • Page 4: Screen Display And Keys

    E s c ok c1 c2 c3 c4 4 screen display and keys operating instructions menu – activate screen – open menu – cancel menu – esc (leave menu) yes confirmation press ok no alter/ change press ok – store selection – confirm selection selection options are displayed date display date display channel status...

  • Page 5: 9:40

    Overview of menu selection 19 05 11 on 9:40 46 program new view change delete end menu time/date manual options end time date summer-- winter day of the week date format time format end permanent on permanent of manual on timer operating hours holiday random end lcd-illu- mination language pin facto...

  • Page 6: Connection

    6 connection warning, danger of death through electric shock! Must be installed by qualified electrician! Disconnect power source. Cover or shield any adjacent live components. Ensure device cannot be switched on! Check power supply is disconnected. Earth and bypass. Tr 635 top2 tr 636 top2 warning ...

  • Page 7: Installation

    Installation distributor installation (wall) – for installation on din top hat rails (in accordance with en 60715) with accessories (9070071) front panel installation – for installation in front frame and transparent cover (in accordance with din 43700) 7 907 0 071 gb.

  • Page 8: Initial Start-Up

    Initial start-up set date, time and summer/ winter time rule press required key and display follows on screen (see figure). Deutsch retain programs delete programs forme date su-wi gb/ irl/p su-wi fin/ gr/tr su-wi cdn su-wi usa su-wi iran su-wi free rule so-wi fix date no so-wi ok or 19 05 11 on 9:4...

  • Page 9: Program

    9 program program switching time example: switch on sports hall lighting from mon–fri, 7:30 to 12:00 hrs press menu . Program is displayed. Confirm by pressing ok . New is displayed. Confirm by pressing ok . Switching time is displayed. Confirm by pressing ok . Select on (for switch-on times). Confi...

  • Page 10

    Menu on 7.30 program new switch time on pulse tuesday wednesday cycle end hour minute monday copy add tuesday save save ... 84 memory locations are available. 10

  • Page 11

    11 request/change/delete switching time press menu . Program is displayed. Confirm by pressing ok . New is displayed. Use to select check. Confirm by pressing ok . Confirm switch time by pressing ok . The first of the entered switching times is displayed. Confirm by pressing ok . Next is displayed. ...

  • Page 12: Pulse Time Programming

    12 pulse time programming example: switch on pause signal on monday 8:05 hrs for 5 sec press menu . Program is displayed. Confirm by pressing ok . New is displayed. Confirm by pressing ok . Switch time is displayed. Select pulse by pressing . Confirm by pressing ok . On is displayed. Confirm by pres...

  • Page 13: Cycle Time Programming

    13 cycle time programming in addition to switch-on and switch-off times (switching time) and short time pulses (pulse) cycle times (cycle) can also be programmed. The pulse length (+ pulse pause) is limited to 17 hrs, 59 min, 59 sec • cycle times refers to cyclically repetitive time functions such a...

  • Page 14: Manual And Permanent

    14 options manual and permanent switching manual and permanent switching can be set using the menu in manual or (in the auto- matic screen) by key combination (see fig.). Activate manual switching briefly press both keys simultaneously. Activate permanent switching simultaneously press both keys for...

  • Page 15: Obelisk Top2 Memory Card

    15 obelisk top2 memory card use memory card insert memory card in the time switch. Read / read out saved switching times and device settings in the time switch or start obelisk program. Remove memory card obelisk top2 (no. 9070404) after copying. Avoid mechanical stress or dirtying with other storag...

  • Page 16: Technical Data

    16 technical data • operating voltage: 230 –240 v~, +10 %/-15 % • frequency: 50–60 hz • power consumption: 0,8 w (tr 635 top2), 0,9 w (tr 636 top2) • standby: 0,9 w (tr 635 top2), 1,1 w (tr 636 top2) • switch output: switching of choice of external wires is permitted • contact: two way switch • gap:...