Therma-Stor HI-E DRY 100 Installation, Operation & Service Instructions

Manual is about: High Efficiency Dehumidifier

Summary of HI-E DRY 100

  • Page 1

    Read the installation, operation and maintenance instructions carefully before installing and using this unit. Proper adherence to these instructions is essential to obtain maximum benefit from your hi-e dry dehumidifier. 1 specifications model: hi-e dry 100 dehumidifier electrical: 110-120 vac, 6.6...

  • Page 2

    2.1b in humid area, duct inlet and/or outlet if the humid area is very large or has high ceilings, dehumidification can be improved by adding an inlet and/ or outlet duct to circulate and destratify stagnant areas. For a large area, add inlet or outlet ducting to create flow across the area’s greate...

  • Page 3: 3 Operation

    3 operation 3.1 humidity control adjustment the dehumidifier will run continuously until the relative humidity (rh) is reduced to the humidity control dial setting. Setting the humidity control to lower rh levels will not increase the unit’s dehumidification rate, it will simply run longer to reduce...

  • Page 4: 4 Maintenance

    4 maintenance 4.1 air filter the hi-e dry 100 is equipped with two 2” thick, merv-11 pleated fabric air filters that must be checked regularly. Operating the unit with dirty filters will reduce the dehumidifier’s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily ...

  • Page 5

    Blower does not run. Compressor runs briefly but cycles on & off. 1. Loose connection in blower circuit (fig. 4). 2. Obstruction prevents impeller rotation. 3. Defective blower (sec. 5.5). Unit removes some water but not as much as expected. 1. Air temperature and/or humidity have dropped. 2. Humidi...

  • Page 6

    8. Compressor terminal c and compressor case: continuity indicates a grounded motor; the compressor must be replaced. 9. Disconnect the wires from the capacitor. Set the ohmmeter to the rx1 scale; the capacitor is shorted and must be replaced if continuity exists across its terminals. If there is no...

  • Page 7: 4023609

    5.9 defrost thermostat & timer the defrost thermostat is attached to the refrigerant suction tube between the accumulator and compressor. If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil, the thermostat opens. The compressor is then cycled off and...

  • Page 8

    6 service parts: hi-e dry 100 dehumidifier item part no. Qty. Description 1 4022254 1 accumulator 2 4021475 1 air filter, pleated, 2” x 16” x 20” 3 4021468 1 air filter, foam element 4 4026930 1 blower 5 4028233 3 capillary tubes 6 4029168 1 compressor 7 4029169 1 compressor overload 8 4029845 1 com...

  • Page 9

    7 filter installation instructions to prevent damaging the foam filter, place it “grid side up” on top of the pleated filter and slide them both into the filter slot. 9 www.Thermastor.Com • sales@thermastor.Com toll-free 1-800-533-7533 www.Sylvane.Com 1-800-934-9194.

  • Page 10

    10 www.Thermastor.Com • sales@thermastor.Com toll-free 1-800-533-7533 www.Sylvane.Com 1-800-934-9194.

  • Page 11

    Therma-stor hi-e dry dehumidifier limited warranty warrantor: therma-stor llc po box 8680 madison, wi 53708 telephone: 1-800-533-7533 who is covered: this warranty extends only to the original end-user of the hi-e dry dehumidifier, and may not be assigned or transferred. Year one: therma-stor warran...