Therma-Stor Santa Fe HC 4025081 Quick Manual - page 3
Santa Fe HC Owners Manual
3
4.1A in Humid Area, No Ducting (Fig. 4)
The simplest installation is to place the Santa Fe
HC in the humid area with no ducting. To ensure
optimal performance the air inlet and the outlet
of the unit must be at least 1' from walls and
other obstructions to air flow.
4.1B In The Humid Area, Duct Inlet
and/or Outlet (Fig. 5)
If the humid area is large or has high ceilings,
dehumidification can be improved by adding an
inlet and/or outlet duct to circulate and destratify
stagnant areas. For a large area, add inlet or
outlet ducting to create flow across the area's
greatest length.
For areas with ceilings higher than 12', use an inlet
duct to draw warm, moist air from near the ceiling.
See section 5 for attaching duct collars & ducting.
4.1C In A Remote Area, Duct
Inlet & Outlet (Fig. 6)
It is often desirable, especially in recreational rooms
and finished areas, to install the Santa Fe HC in an
adjacent equipment room or unfinished area. Air is
transferred between the humid room and the unit
via ducting. The factory mounted humidity control
on the Santa Fe HC cabinet may not sense the
humidity in the humid room accurately enough with
this installation method. If so, a remote humidity
control can be mounted in the humid room and
wired to the Santa Fe HC. Refer to the optional
equipment table in this document. Local electrical
codes must be followed when wiring the control.
Figure 4: Installation in humid area with no ducting.
Figure 5: Installation in humid area with inlet and outlet ducting.
Figure 6: Installation in a remote area with ducted inlet and outlet.
Inlet
Inlet
Inlet
Output
Output
Output