Trion HE Plus 1400 Installation & Operation Manual

Manual is about: Duct Mount Electronic Air Cleaner

Summary of HE Plus 1400

  • Page 1

    Electronic air cleaner limited three-year warranty this limited warranty covers trion residential type electronic air cleaners, excluding ductwork, wiring and installation. Trion warrants that all new trion electronic residential air cleaners are free from defects in material and workmanship under n...

  • Page 2

    Power tray assembly 120/50-60/1 power tray assembly 240/50-60/1 high frequency power supply* electronic air flow sensor* on/off switch* interlock switch* cabinet assembly pre-filter (2 req.) cell, ionizing-collecting (2 req.) ionizing wire assembly front panel assembly contact board assembly (2 req....

  • Page 3

    10. If no voltage is present, remove the second cell. Install cell number one and measure voltage as described in step #7. If voltage is present, the second cell, which is now out of the cabinet, is shorted. Refer to common troubleshooting techniques (pg. 9). 11. If no voltage is present, remove bot...

  • Page 4

    Secondary circuit power supply if the red cell energized light remains out with the ionizing-collecting cells removed from the cabinet, the power supply is defective. Specific problems in the power tray assembly can be isolated by using a multimeter and high voltage probe to check the output voltage...

  • Page 5

    Secondary circuit ionizing-collecting cell the cells are electrically energized through a contact terminal located at the top center of each cell. The ionizing wires and alternating collector plates are electrically charged while the interleaving plates are grounded. If the space between the charged...

  • Page 6

    Primary circuit with hvac system blower operating • if there is no supply line voltage at the transformer input connections, correct the fault at the dedicated power source or hvac system power source. • if there is supply line voltage at the transformer input connections and no output voltage (24 v...

  • Page 7

    Troubleshooting warning: • these procedures must be performed by a qualified hvac technician or electrician. • risk of personal injury or death could occur by attempting to troubleshoot or repair this unit by untrained persons. • exercise the usual precautions when working with high voltage. • when ...

  • Page 8

    System checkout warning: the following procedures must be conducted by a qualified hvac contractor or repair person only. These procedures will expose hazardous electrically energized charged components. Disconnect power between checks and proceed carefully. 1. The hvac system blower should be turne...

  • Page 9

    Electrical installation caution : if the electronic air cleaner is wired directly to the integrated accessory control on the furnace, it is imperative that the ampere rating of the control be sufficient to handle the current required by the air cleaner. All wiring shall be performed in accordance wi...

  • Page 10

    Note: the following is a typical installation of the air cleaner on a highboy furnace. You may have to alter the installation to fit your particular application. 1. Locate the cabinet in the cold air return duct such that all of the return air flows through the unit. If the furnace and air cleaner o...

  • Page 11

    Installation caution: only a trained, experienced servicer should install this electronic air cleaner. The front panel assembly, power tray assembly, ionizing-collecting cells and pre-filters should be removed before installation. To remove the power tray assembly, remove the two (2) screws from ins...

  • Page 12

    Installation 15 eac20002025 eac14001625 eac14002020 unit dimensions 10 for qualified hvac installer only typical mounting positions (air cleaner shown shaded in illustrations) horizontal furnace – mounted vertically in return duct as close to the furnace as possible. Offset installation – if there i...

  • Page 13

    Location selection remember to select a location that is readily accessible for periodic inspection and cleaning of the the pre- filters and ionizing-collecting cells. Allow a minimum of 24” clearance in front and 12” clearance above the air cleaner for component removal and service space. Direction...

  • Page 14

    Atomizing humidifiers if an atomizing humidifier is mounted upstream of the air cleaner: 1. Mount the humidifier as far upstream in the ductwork as possible. A distance of at least 10 feet is recommended to reduce the possibility of excessive arcing as water droplets pass through the electronic air ...