5. Door Lock Connections
1. Internal Power Supply Mode
Usethepowerofthesystemtosupplyfortheelectroniclock,sothatthelockcanbe
connectedtothedoorstationdirectly,withoutanadditionalpowersupplyfortheelectroniclock.
Notethatthedoorstationcanonlyoutput12Vdcpower,thereforethekindoflockislimited.
• Theratedpowerofthelockmustbelessthan12Vdc300mAwhenusinginternalpower
supplymode
• TheGNDmustconnecttothenegativeofthelock,andtheCOMconnecttothepositive.
• Jumpersetto1-2positionforPower-off-to-Unlocksafetytype(
Normally closed mode
);
setto2-3positionforPower-on-to-Unlocktype(
Normally open mode
).
• Ifdifferentunlockingtimeisneededtobeconfigured,changethe
Unlock Timing
on
doorstation.(Indebugstate,press[1#]-->[1]InstallerSetup-->[2]UnlockTiming)
JP_LK
12V 300mA
Jumper set to 2-3 position
+
-
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
1
2
3
set to Normally open on the
Unlock Relay mode
A. Connection for Power-on-to-Unlock type:
12V 300mA
Jumper set to 1-2 position
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
+
-
set to Normally Closed on the
Unlock Relay mode
JP_LK
1
2
3
B. Connection for Power--off-to-Unlock type: