4.4.2 Positioner without function
Connect 4 ... 20 mA.
Is the display active?
No
Exchange the + and - connection wires. Now is the display
active?
Yes
Good job! The work
activities are completed.
No
Yes
Check the power source or retu rn defective positioners for
repair.
Connect compressed air. Now is it
working?
s
e
Y
Good job! The work
activities are completed.
No
Switch the positioner to operating
mode 1.2 (manual). Press the
arrow button briefly. Press the
second arrow. Now is it working?
Yes
Start Autoadjust. Save parameters and switch the positioner
to operating mode 1.1 . In case of error messages, check
the mechanical configuration.
Now is it working?
No
Good job! The work
activities are completed.
No
No
No
Check the safe position for the
pneumatic output module (label on
the plastic cap) and compare with
parameter IP-Typ . The safe
position must be activated
(FAIL_POS ) before the parameter
can be changed. Save parameters.
Now is it working?
Yes
Press the arrow button
to read the current value. Is the
current value correct?
Check power source or
PLS.
Good job! Work
activities are over
after starting
Autoadjust!
Yes
No
Return the defective positioner for
repair.
Switch the function for the digital input ( FUNCTION ) to
none .