Vacon NXI User Manual

Manual is about: fi9-fi14

Summary of NXI

  • Page 1

    Vacon nxi inverters fi9-fi14 user manual ®.

  • Page 2

    At least the 10 following steps of the start-up quick guide must be performed during the installation and commissioning. If any problems occur, please contact your local distributor. Start-up quick guide 1. Check that the delivery corresponds to your order, see chapter 3. 2. Before taking any commis...

  • Page 3

    Contents vacon nxi user’s manual index 1 safety 2 eu directive 3 receipt of delivery 4 technical data 5 installation 6 cabling and connections 7 control keypad 8 commissioning 9 fault tracing.

  • Page 4

    4 • vacon safety puhelin: 0201-2121 • fax: 0201-212 205 1 about the vacon nxi user's manual and the ”all in one” application manual congratulations for choosing vacon nx inverters! The user's manual will provide you with the necessary information about the installation, commissioning and operation o...

  • Page 5

    Safety vacon • 5 päivystys: 040- 8371 150 • email: vacon@vacon.Com 1 vacon nxi user's manual index document code: dpd00909a date: 11/03/2014 1. Safety ............................................................................................................................. 7 1.1 warnings ...........

  • Page 6

    6 • vacon safety puhelin: 0201-2121 • fax: 0201-212 205 1 6.1.1.8 terminal sizes, nxi_xxxx 6 .................................................................................... 46 6.1.2 installation instructions ..........................................................................................

  • Page 7

    Safety vacon • 7 päivystys: 040- 8371 150 • email: vacon@vacon.Com 1 1. Safety 1.1 warnings 1 the components of the power unit of the inverter are live when the vacon nx is connected to dc supply. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The ...

  • Page 8

    8 • vacon safety puhelin: 0201-2121 • fax: 0201-212 205 1 1.3 earthing and earth fault protection the vacon nx inverter must always be earthed with an earthing conductor connected to the earthing terminal. The earth fault protection inside the inverter only protects the inverter against earth faults...

  • Page 9

    Receipt of delivery vacon • 9 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 3 2. Eu directive 2.1 ce marking the ce marking on the product guarantees the free movement of the product within the eea (european economic area). It also guarantees that the product complies with applicabl...

  • Page 10

    10 • vacon receipt of delivery tel: +358-201-2121 • fax: +358-201-212 205 3 eu declaration of conformity we manufacturer's name: vacon oyj manufacturer's address: p.O.Box 25 runsorintie 7 fin-65381 vaasa finland hereby declare that the product product name: vacon nx common dc bus products model desi...

  • Page 11

    Receipt of delivery vacon • 11 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 3 3. Receipt of delivery vacon nx inverters have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no s...

  • Page 12

    12 • vacon receipt of delivery tel: +358-201-2121 • fax: +358-201-212 205 3 3.1.2 the standard features of nxi inverters inverter sales code nxi_aaaa 5/6 standard features of fi9, fi10, fi12, fi13 and fi14 air cooling alphanumeric control panel with fiber connection emc class t (en 61800-3 for it ne...

  • Page 13

    Receipt of delivery vacon • 13 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 3 3.2 storage if the inverter is to be stored before use, make sure that the ambient conditions are acceptable: storage temperature –40…+70 ° c relative humidity when inverter units are stored without volta...

  • Page 14

    14 • vacon receipt of delivery tel: +358-201-2121 • fax: +358-201-212 205 3 table 5. Maintenance interval interval maintenance 12 months (if unit stored) capacitor reforming, see separate instructions 6 - 24 months (depending on environment) check the input and output terminals and control i/o- term...

  • Page 15

    Technical data vacon • 15 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 4 4. Technical data 4.1 introduction the figure below presents the block diagram of the vacon nx inverter. The inverter mechanically consists of two units, the power unit and the control unit. The power unit con...

  • Page 16

    16 • vacon technical data tel: +358-201-2121 • fax: +358-201-212 205 4 the control keypad constitutes a link between the user and the inverter. The control keypad is used for parameter setting, reading status data and giving control commands. It is detachable and can be operated externally and is co...

  • Page 17

    Technical data vacon • 17 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 4 4.2 power ratings 4.2.1 vacon nxi_xxxx 5 – supply voltage 465-800 vdc, motor voltage 380—500 vac high overload = max current i s ; 2 sec/20 sec, 150% overloadability; 1 min/10 min following continuous operatio...

  • Page 18

    18 • vacon technical data tel: +358-201-2121 • fax: +358-201-212 205 4 4.2.2 vacon nxi_xxxx 6 – supply voltage 640-1100 vdc, motor voltage 525—690 vac high overload = max current i s; 2 sec/20 sec, 150% overloadability; 1 min/10 min following continuous operation at rated output current, 150 % rated...

  • Page 19

    Technical data vacon • 19 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 4 4.3 technical information supply connection input voltage u in 465...800vdc ( 380-500 vac) 640...1100vdc ( 525-690 vac) the waviness of the inverter supply voltage, which is formed in rectification of the elec...

  • Page 20

    20 • vacon technical data tel: +358-201-2121 • fax: +358-201-212 205 4 vibration en50178/en60068-2-6 displacement amplitude 0.25 mm (peak) at 5…31 hz max acceleration 1 g at 31…150 hz shock en50178, en60068-2-27 ups drop test (for applicable ups weights) storage and shipping: max 15 g, 11 ms (in pac...

  • Page 21

    Technical data vacon • 21 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 4 structure i n (output) motor p.F. I dc (input) fi9 261 0,89 304 300 0,89 350 fi10 385 0,9 454 460 0,9 542 520 0,9 613 fi12 590 0,9 695 650 0,9 766 730 0,91 870 820 0,91 977 920 0,91 1096 1030 0,91 1227 fi13 11...

  • Page 22

    22 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 5 5. Installation 5.1 mounting the inverter can be mounted in a vertical position on the back plane of a cubicle. Enough space must be reserved around the inverter to ensure sufficient cooling, see figure 5-7. Follow the minimum dime...

  • Page 23

    Installation vacon • 23 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 5 figure 5-1. The dimensions of vacon nxi fi9.

  • Page 24

    24 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 5 figure 5-2. Vacon nxi dimensions, fi10

  • Page 25

    Installation vacon • 25 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 5 figure 5-3. Vacon nxi dimensions, fi12 back view..

  • Page 26

    26 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 5 figure 5-4. Vacon nxi dimensions, fi12 front view.

  • Page 27

    Installation vacon • 27 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 5 figure 5-5. Vacon nxi dimensions, fi13 back view. Note, fi14 is a douple fi13.

  • Page 28

    28 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 5 figure 5-6. Vacon nxi dimensions, fi13 front view. Note, fi14 is a douple fi13.

  • Page 29

    Installation vacon • 29 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 5 5.2 fan cooling 5.2.1 frames fi9 to fi14 enough free space must be left around the inverter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table bel...

  • Page 30

    30 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 5 type frame cooling air required (m 3 /h) minimum air holes on switchgear (mm 2 ) nxi_0168 – 0300 5 nxi_0125 – 0208 6 fi9 1.150 inlet: 55.000 outlet: 30.000 nxi_0385 – 0520 5 nxi_0261 – 0416 6 fi10 1.400 inlet: 65.000 outlet: 40.000...

  • Page 31

    Cabling and connections vacon • 31 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 figure 5-8. Cabinet openings for cooling. 1. Cooling air inlets 2. Hot air exhaust 1 1 1 2 2.

  • Page 32

    32 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 steering air flow cooling air must be taken in through the ventilation gaps on the door and blown out at the top of the enclosure. To steer the hot air from the power unit to the outlet at the top of the enclosure and pr...

  • Page 33

    Cabling and connections vacon • 33 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6. Cabling and connections 6.1 power unit the following wiring diagrams show the supply and motor connections. Figure 6-1. Fi9/10 basic wiring diagram without charging dc+ dc- 21 22 23 x15 charging re...

  • Page 34

    34 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 figure 6-2, fi9/10 basic wiring diagram with charging dc+ dc- c ool in g f an b+ b- u v w nxp control fi 9/10 m x9 x15 x10 h1...H7 pe external supply 21 22 23 x15 charging relay 25 26 x9 charging feedback 2 4 vd c o e va.

  • Page 35

    Cabling and connections vacon • 35 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 figure 6-3, fi12 basic wiring diagram without charging dc+ dc- nxp control c ool in g f an b+ b- u v w pe m dc+ dc- c ool in g f an b+ b- x 10 x9 x 15 h1 -7 h9 03 h9 00 note! Min cable length 40m fi10...

  • Page 36

    36 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 figure 6-4, fi12 basic wiring diagram with charging 21 22 23 x15 charging relay 25 26 x9 charging feedback 2 4 vd c o e va nxp control c ool in g f an b+ b- m c ool in g f an b+ b- x 10 x9 x 15 h1 -7 h9 03 h9 00 note! Mi...

  • Page 37

    Cabling and connections vacon • 37 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 figure 6-5, fi13 basic wiring diagram without charging dc+ dc- nxp control c ool in g f an b+ b- m dc+ dc- c ool in g f an b+ b- fi10 / module v fi10 / module w c ool in g f an b+ b- fi10 / module u w...

  • Page 38

    38 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 figure 6-6. Fi13 basic wiring diagram with charging dc+ dc- dc+ dc- dc+ dc- m nxp control c ool in g f an b+ b- c ool in g f an b+ b- fi10 / module v fi10 / module w c ool in g f an w u v x 10 h1 -7 b+ b- fi10 / module u...

  • Page 39

    Cabling and connections vacon • 39 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 figure 6-7. Fi14 basic wiring diagram without charging dc+ dc- dc+ dc- dc+ dc- dc+ dc- dc+ dc- dc+ dc- nxp control c ool in g f an b+ b- m c ool in g f an b+ b- fi10 / module v fi10 / module w c ool i...

  • Page 40

    40 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 figure 6-8. Fi14 basic wiring diagram with charging m note! Min cable length 40m 21 22 23 x15 charging relay 25 26 x9 charging feedback 2 4v d c oeva dc+ dc- dc+ dc- dc+ dc- nxp control c ool in g f an b+ b- c ool in g f...

  • Page 41

    Cabling and connections vacon • 41 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.1 power connections 6.1.1.1 dc supply and motor cables the power supply is connected to terminals b+ and b- and the motor cables to terminals u/t1, v/t2 and w/t3. A cable entry gland should be use...

  • Page 42

    42 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 nxi_1300 5 1300 170m8547 3sht 690 1250 6 nxi_1450 5 1450 170m8547 3sht 690 1250 6 nxi_1770 5 fi14 1770 170m8547 3sht 690 1250 2 × 6 nxi_2150 5 2150 170m8547 3sht 690 1250 2 × 6 nxi_2700 5 2700 170m8547 3sht 690 1250 2 × ...

  • Page 43

    Cabling and connections vacon • 43 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.1.5 inverter supply and motor cables , nxi_xxxx 5 frame type il [a] module supply (dc) (per terminal) cu [mm2] motor cable [mm2] nxi_0168 5 fi9 170 1 ) 2×(1×24) cu: 3×95+50 al: 3×120+70 nxi_0205 5...

  • Page 44

    44 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 6.1.1.6 terminal sizes, nxi_xxxx 5 frame type i l [a] dc supply terminal ] motor cable terminal nxi_0168 5 fi9 170 pe: m8 × 25 nxi_0205 5 205 nxi_0261 5 261 nxi_0300 5 300 nxi_0385 5 fi10 385 pe: m8 × 25 nxi_0460 5 460 n...

  • Page 45

    Cabling and connections vacon • 45 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.1.7 inverter supply and motor cables, nxi_xxxx 6 frame type il [a] module supply (dc) cu [mm2] motor cable [mm2] nxi_0125 6 fi9 125 1 ) 2×(1×24) cu: 3×95+50 al: 3×120+70 nxi_0144 6 144 1 ) 2×(1×24...

  • Page 46

    46 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 6.1.1.8 terminal sizes, nxi_xxxx 6 frame type il [a] dc supply terminal motor cable terminal nxi_0125 6 fi9 125 pe: m8×25 nxi_0144 6 144 nxi_0170 6 170 nxi_0208 6 208 nxi_0261 6 fi10 261 pe: m8×25 nxi_0325 6 325 nxi_0385...

  • Page 47

    Cabling and connections vacon • 47 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.2 installation instructions 1 before starting the installation, check that none of the components of the inverter are live. 2 in accordance with protection class ip00 requirements. There is no nee...

  • Page 48

    48 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 5 connect the cables: remove the screws of the cable protection plate. Do not open the cover of the power unit! Make holes into and pass the cables through the rubber grommets on the bottom of the power unit. The rubber ...

  • Page 49

    Cabling and connections vacon • 49 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.2.1 vacon nxi frames figure 6-9. Vacon nxi, fi9. Protection class ip00 figure 6-10. Vacon nxi, fi10. Protection class ip00

  • Page 50

    50 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 figure 6-11. Vacon nxi, f12. Protection class ip00 figure 6-12. Vacon nxi, fi13. Protection class ip00

  • Page 51

    Cabling and connections vacon • 51 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.1.3 cable installation and the ul standards to meet the ul ( underwriters laboratories ) regulations, a ul-approved copper cable with a minimum heat-resistance of +60/75 ° c must be used. The tighte...

  • Page 52

    52 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 6.2 control unit the control unit of the inverter consists of the control board and option boards (see figure 6-13 and figure 6-20) connected to the five slot connectors (a to e) on the control board. The control board i...

  • Page 53

    Cabling and connections vacon • 53 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 dotted line indicates the connection with inverted signal levels 24 v gnd 24 v gnd u i + 0(4)/20ma rl Ω basic i/o board nxopta1 +10vref aia1+ gnd aia2+ aia2- 24vout gnd dia1 dia2 dia3 cma 24vout gnd d...

  • Page 54

    54 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 6.2.1.1 control cables the control cables shall be at least 0.5 mm 2 screened multicore cables, see table 6 - 9. The maximum terminal wire size is 2.5 mm 2 for the relay terminals and 1.5 mm 2 for other terminals. You ca...

  • Page 55

    Cabling and connections vacon • 55 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.2.2 control terminal signals terminal signal technical information 1 +10 vref reference voltage maximum current 10 ma 2 ai1+ analogue input, voltage or current selection v or ma with jumper block x1...

  • Page 56

    56 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 opt-a2 21 ro1/1 relay output 1 switching capacity 24vdc/8a 250vac/8a 125vdc/0.4a min.Switching load 5v/10ma 22 ro1/2 23 ro1/3 24 ro2/1 relay output 2 switching capacity 24vdc/8a 250vac/8a 125vdc/0.4a min.Switching load 5...

  • Page 57

    Cabling and connections vacon • 57 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 6 6.2.2.2 jumper selections on the opt-a1 basic board the user can customise the functions of the inverter to better suit his needs by selecting certain positions for the jumpers on the opt-a1 board. Th...

  • Page 58

    58 • vacon cabling and connections tel: +358-201-2121 • fax: +358-201-212 205 6 ! Varoitus ! Huom! Figure 6-21. Jumper selection for opt-a1 ensure that the jumper positions are correct. Running the motor with signal settings that differ from the jumper positions will not harm the inverter but may ha...

  • Page 59

    Control keypad vacon • 59 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7. Control keypad the control keypad is the link between the vacon inverter and the user. The vacon nx control keypad features an alphanumeric display with seven indicators for the run status (run, , ready, st...

  • Page 60

    60 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 alarm = indicates that the drive is running outside a certain limit and a warning is given. Fault = indicates that unsafe operating conditions were encountered due to which the drive was stopped. 7.1.2 control place indications t...

  • Page 61

    Control keypad vacon • 61 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.1.4 text lines the three text lines ( • , •• , ••• ) provide the users with information on their present location in the keypad menu structure as well as with information related to the operation of the driv...

  • Page 62

    62 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.2 keypad push-buttons the vacon alphanumeric control keypad has 9 push-buttons that are used for controlling the inverter (and motor), setting parameters, and monitoring values. Figure 7-2 keypad push-buttons 7.2.1 button descr...

  • Page 63

    Control keypad vacon • 63 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 = menu button right move forward in menu. Move cursor right ( in parameter menu ). Enter edit mode. = start button pressing this button starts the motor if the keypad is the active control place. See chapter 7...

  • Page 64

    64 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 figure 7-3 keypad navigation chart f t1 t7 stop fault i/ote rm stop i/ote rm fault h1 h3 ready i/ote rm t1 t7 i/ote rm ready i/oterm ready s1 s9 stop r eady i/ote rm stop r eady i/ote rm enter g1 g5 ready i/oterm a:nxopta1 r eady...

  • Page 65

    Control keypad vacon • 65 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.3.1 monitoring menu (m1) you can enter the monitoring menu from the main menu by pressing menu button right when the location indication m1 is visible on the first line of the display. Figure 3-1 shows how t...

  • Page 66

    66 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.2 parameter menu (m2) parameters are the way of conveying the commands of the user to the inverter. Parameter values can be edited by entering the parameter menu from the main menu when the location indication m2 is visible o...

  • Page 67

    Control keypad vacon • 67 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 figure 7-1. Parameter value change procedure g1 g8 ready keypad p1 p18 ready keypad 13.95 hz ready keypad g1 g8 ke ypa d ready keypad 13.95 hz enter ready keypad 14.45 hz parameters basic parameters min freque...

  • Page 68

    68 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.3 keypad control menu (m3) in the keypad control menu , you can choose the control place, edit the frequency reference and change the direction of the motor. You can enter the submenu level by pressing menu button right . 7.3...

  • Page 69

    Control keypad vacon • 69 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 see also chapter 7.3.3. 7.3.3.4 stop button activated by default, pushing the stop button will always stop the motor regardless of the selected control place. You can disable this function by giving parameter ...

  • Page 70

    70 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.4 active faults menu (m4) you can enter the active faults menu from the main menu by pressing menu button right when the location indication m4 is visible on the first line of the keypad display. When a fault brings the inver...

  • Page 71

    Control keypad vacon • 71 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 fault type symbol meaning a (alarm) this type of fault is a sign of an unusual operating condition. It does not cause the drive to stop, nor does it require any special actions. The 'a fault' remains in the di...

  • Page 72

    72 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.4.2 fault codes the fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are a faults only. The items in white on black background are faults for which you can program differe...

  • Page 73

    Control keypad vacon • 73 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 fault code fault possible cause correcting measures 12 brake chopper supervision no brake resistor installed brake resistor is broken brake chopper failure check brake resistor. If the resistor is ok, the chop...

  • Page 74

    74 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 fault code fault possible cause correcting measures 37 device changed (same type) option board or control unit changed. Same type of board or same power rating of drive. Reset note: no fault time data record! 38 device added (sam...

  • Page 75

    Control keypad vacon • 75 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 fault code fault possible cause correcting measures 56 pt100 board temp. Fault temperature limit values set for the pt100 board parameters have been exceeded find the cause of temperature rise table 7 - 2. Fau...

  • Page 76

    76 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.4.3 fault time data record when a fault occurs, the information described in chapter 7.3.3.4 is displayed. By pressing menu button right , you will enter the fault time data record menu indicated by t.1 t.#. In this menu, som...

  • Page 77

    Control keypad vacon • 77 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.3.5 fault history menu (m5) vikahistoriavalikkoon pääsee päävalikosta painamalla oikeanpuoleista valikkonäppäintä kun you can enter the fault history menu from the main menu by pressing menu button right whe...

  • Page 78

    78 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.3.6 system menu (m6) you can enter the system menu from the main menu by pressing menu button right when the location indication m6 is visible on the first line of the keypad display . The controls associated with the general u...

  • Page 79

    Control keypad vacon • 79 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 system menu functions code function min max unit default cust selections s6.1 selection of language english english deutsch suomi svenska italiano s6.2 application selection basic application basic application...

  • Page 80

    80 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 t6.8.2.3 operation day counter t6.8.2.4 operation hour counter t6.8.2.5 clear operation hour counter s6.8.3 software information s6.8.3.1 software package s6.8.3.2 system software version s6.8.3.3 firmware interface s6.8.3.4 syst...

  • Page 81

    Control keypad vacon • 81 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.3.6.1 selection of language the vacon control keypad offers you the possibility to control the inverter through the keypad in the language of your choice. Locate the language selection page under the system ...

  • Page 82

    82 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 figure 7-6. Change of application 7.3.6.3 copy parameters the parameter copy function is used when the operator wants to copy one or all parameter groups from one drive to another. All the parameter groups are first uploaded to t...

  • Page 83

    Control keypad vacon • 83 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 figure 7-7. Storing and loading of parameter sets upload parameters to keypad (to keypad, s6.3.2) this function uploads all existing parameter groups to the keypad provided that the drive is stopped. Enter the...

  • Page 84

    84 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 automatic parameter backup (p6.3.4) on this page you can activate or inactivate the parameter backup function. Enter the edit mode by pressing menu button right . Select yes or no with the browser buttons . When the parameter bac...

  • Page 85

    Control keypad vacon • 85 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 figure 7-9. Parameter comparison 7.3.6.5 safety note: the security submenu is protected with a password. Store the password in a safe place! Password (s6.5.1) the application selection can be protected against...

  • Page 86

    86 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 this function allows the user to prohibit changes to the parameters. If the parameter lock is activated, the text *locked* will appear on the display if you try to edit a parameter value. Note: this function does not prevent unau...

  • Page 87

    Control keypad vacon • 87 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 multimonitoring items (p6.5.4) vacon alphanumeric keypad features a display where you can monitor up to three actual values at the same time (see chapter 7.3.1 and chapter monitoring values in the manual of th...

  • Page 88

    88 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 default page in the operating menu (p6.6.2) here you can set the location (page) in the operating menu (in special applications only) to which the display automatically moves to when the set timeout time (see below) has expired o...

  • Page 89

    Control keypad vacon • 89 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.3.6.7 hardware settings note: the hardware settings submenu is protected with a password. Store the password in a safe place! In the hardware settings submenu (s6.7) under the system menu, you can further co...

  • Page 90

    90 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 to change the value: enter the edit mode by pressing menu button right . The value starts blinking. Use the browser buttons to change the fan mode and confirm the change with the enter button. If you do not want to change the val...

  • Page 91

    Control keypad vacon • 91 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 figure 7 - 19. Hmi acknowledge timeout number of retries to receive hmi acknowledgement (p6.7.4) with this parameter you can set the number of times the drive will try to receive acknowledgement if it does not...

  • Page 92

    92 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 trip counters trip counters (menu s6.8.2) are counters the values of which can be reset i.E. Restored to zero. You can use the following resettable counters: note! The trip counters run only when the motor is running. Page counte...

  • Page 93

    Control keypad vacon • 93 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 in the applications information page, press menu button right to enter the application pages of which there are as many as there are applications loaded into the inverter. Locate the desired application with t...

  • Page 94

    94 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 figure 7-22. Expander board information menus e1 e5 ready i/o term a:nxopta1 i/o term ready b:nxopta2 i/oterm e1 e2 i/o term ready i/oterm e1 e2 10001.0 expander boards software version state run.

  • Page 95

    Control keypad vacon • 95 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 7 7.3.7 expander board menu (m7) in the expander board menu the user can 1) see the expander boards connected to the control board and 2) see and edit the parameters associated with the expander boards. Go to th...

  • Page 96

    96 • vacon control keypad tel: +358-201-2121 • fax: +358-201-212 205 7 7.4 further keypad functions the vacon nx control keypad contains additional application-related functions. See vacon nx application package for more information..

  • Page 97

    Commissioning vacon • 97 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 8 8. Commissioning 8.1 safety before commissioning, note the following directions and warnings: 1 internal components and circuit boards of the inverter (except for the galvanically isolated i/o terminals) are li...

  • Page 98

    98 • vacon commissioning tel: +358-201-2121 • fax: +358-201-212 205 8 7 set the parameters of group 1 according to the requirements of your application (see vacon all in one application manual). At least the following parameters should be set: motor nominal voltage motor nominal frequency motor nomi...

  • Page 99

    Commissioning vacon • 99 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 8 9 run the start-up tests without the motor being connected to the process. If this is not possible, make sure that running each test is safe prior to running it. Inform your co- workers of the tests. A) switch ...

  • Page 100

    100 • vacon fault tracing tel: +358-201-2121 • fax: +358-201-212 205 9 9. Fault tracing when a fault is detected by the inverter control electronics, the drive is stopped and the symbol f together with the ordinal number of the fault, the fault code and a short fault description appear on the displa...

  • Page 101

    Fault tracing vacon • 101 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 9 fault code fault possible cause correcting measures 10 input line supervision input line phase is missing. Check supply voltage and cable. 11 output phase supervision current measurement has detected that ther...

  • Page 102

    102 • vacon fault tracing tel: +358-201-2121 • fax: +358-201-212 205 9 fault code fault possible cause correcting measures 34 can bus communicatio n sent message not acknowledged. Ensure that there is another device on the bus with the same configuration. 36 control unit nxs control unit can not con...

  • Page 103

    Fault tracing vacon • 103 24-hour support: +358-(0)40- 8371 150 • email: vacon@vacon.Com 9 fault code fault possible cause correcting measures 54 slot fault defective option board or slot check board and slot. Contact the nearest vacon distributor. 56 pt100 board temp. Fault temperature limit values...

  • Page 105

    Document id: rev. A manual authoring: documentation@vacon.Com vacon plc. Runsorintie 7 65380 vaasa finland subject to change without prior notice © 2013 vacon plc. Find your nearest vacon office on the internet at: www.Vacon.Com.