    Vacon nx ac drives basic i/o boards expander i/o boards adapter i/o boards user manual ®.

  • Page 3

    Vacon • 1 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ t able of c ontents document: dpd00884b release date : 1/9/16 1. General information.........................................................................................2 1.1 board slots on the control board of va...

  • Page 4

    1 vacon • 2 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1. G eneral information vacon ® nx range embodies a wide selection of expander and adapter boards with which the available i/o of vacon ® nx ac drive can be increased and its versatility improved...

  • Page 5

    General information vacon • 3 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 1.2 board slots on the control board of vacon ® nxl figure 2. Board slots on control board of vacon ® nxl. The control board of nxl includes fixed standard i/o and one place for option boards (se...

  • Page 6

    1 vacon • 4 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1.3 option board types the vacon ® option boards are divided in four groups according to their characteristics: types a, b, c and d. Short descriptions of the types below: opta_ • basic boards us...

  • Page 7

    General information vacon • 5 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 1.4 technical data the data in the table below applies to the inputs and outputs on all basic and expander boards. Table 1. Technical data safety (all boards) comply with en50178, c-ul and en6020...

  • Page 8

    1 vacon • 6 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1.4.1 isolation the control connections are isolated from the mains potential and the i/o ground is connected directly to the frame of the ac drive. Digital inputs and relay outputs are isolated ...

  • Page 9

    General information vacon • 7 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 requirements for an external power back-up: - output voltage +24dc±10%, max. Ripple voltage 100mv rms - max. Current 1a - 1a external fuse (no internal short-circuit protection on the control boa...

  • Page 10

    1 vacon • 8 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ if you use an external +24v the following arrangements are possible: figure 5. Positive logic with external +24v when cma is isolated from gnd using onboard jumper. The input is active when the s...

  • Page 11

    General information vacon • 9 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 1.5 hardware protections 1.5.1 terminal block coding in order to avoid incorrect connections of terminal blocks to boards, some terminal blocks as well as related terminal connectors on the board...

  • Page 12

    1 vacon • 10 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1.6 type identification number note: this information is relevant only for special applications designers using the vacon ® nc1131-3 engineering tool. Each vacon ® optxx board has a unique type ...

  • Page 13

    General information vacon • 11 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1 once you have set the desired code, press the enter button once to confirm the change. 1.8 defining a terminal for a certain function with ncdrive programming tool if you use the ncdrive program...

  • Page 14

    1 vacon • 12 general information local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 1.9 option board related parameters some of the input and output functions of certain option boards are controlled with associated parameters. The parameters are used to set the signal ranges fo...

  • Page 15

    Installation of vacon® option boards vacon • 13 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 2 2. I nstallation of vacon ® o ption b oards do not add or replace option boards or fieldbus boards on an ac drive with the power switched on. This may damage the boards. A vacon...

  • Page 16

    2 vacon • 14 installation of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ d install the option board in a correct slot on the control board of the ac drive. On attaching (also removing) the board, hold it in horizontally straight position to avoid twi...

  • Page 17

    Installation of vacon® option boards vacon • 15 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 2 2.1 control cables the control cables used must be at least 0.5mm 2 screened multicore cables. The maximum terminal wire size is 2.5mm 2 for the relay terminals and 1.5 mm 2 for...

  • Page 18

    2 vacon • 16 installation of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 2.2 board information sticker each i/o option board package delivered by the factory includes a sticker (shown below) where possible modifications made in the ac drive are noted...

  • Page 19

    Descriptions of vacon® option boards vacon • 17 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3. D escriptions of vacon ® option boards 3.1 basic boards opta_ • basic boards used for basic i/o; normally pre-installed at the factory. • this board type uses slots a, b and ...

  • Page 20

    3 vacon • 18 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3.1.1 opta1 figure 11. Vacon ® opta1 option board description: standard i/o board with digital inputs/outputs and analogue inputs/outputs allowed slots: a type id: 16689 termina...

  • Page 21

    Descriptions of vacon® option boards vacon • 19 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 i/o terminals on opta1 (coded terminals painted black) table 5. Opta1 i/o terminals terminal parameter reference on keypad and ncdrive technical information 1 +10 vref reference...

  • Page 22

    3 vacon • 20 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ jumper selections there are four jumper blocks on the opta1 board. The factory defaults and other available jumper selections are presented below. Figure 12. Jumper block select...

  • Page 23

    Descriptions of vacon® option boards vacon • 21 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 opta1 parameters 3.1.2 opta2 table 6. Opta1 board-related parameters number parameter min max default note 1 ai1 mode 1 5 3 1 = 0...20ma 2 = 4...20ma 3 = 0...10v 4 = 2...10v 5 =...

  • Page 24

    3 vacon • 22 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on opta2 3.1.3 opta3 table 7. Opta2 i/o terminals terminal parameter reference on keypad and ncdrive technical information 21 22 23 ro1/normal closed ro1/common ro...

  • Page 25

    Descriptions of vacon® option boards vacon • 23 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 i/o terminals on opta3 3.1.4 opta4 table 8. Opta3 i/o terminals terminal parameter reference on keypad and ncdrive technical information 21 22 23 ro1/normal closed ro1/common ro...

  • Page 26

    3 vacon • 24 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on opta4 (coded terminal painted black) description: encoder board for vacon ® nxp. Encoder input board with programmable control voltage for an encoder. The encod...

  • Page 27

    Descriptions of vacon® option boards vacon • 25 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 technical data: jumper selections on the opta4 board, there are two jumper blocks. The jumper x2 is used to define the status of the termination resistor (r=135Ω). The jumper x4...

  • Page 28

    3 vacon • 26 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ encoder connection – differential figure 13. Rs-422 type encoder connection using differential inputs note: the encoder pulses are handled by vacon ® software as presented below...

  • Page 29

    Descriptions of vacon® option boards vacon • 27 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 opta4 parameters par 7.3.1.4 encoder type (can be selected with boards a4, a5 and a7 (encoder 2 mode)) table 10. Opta4 board-related parameters number parameter min max default ...

  • Page 30

    3 vacon • 28 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 = a = forw, b = rev this type cannot be used for closed loop control! In this mode both channels are receiving signal but not at the same time. Pulses on channel a means posit...

  • Page 31

    Descriptions of vacon® option boards vacon • 29 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.1.5 opta5 description: encoder board for vacon ® nxp. Encoder input board with programmable control voltage for an encoder. The opta5 board is designed for htl (high voltage t...

  • Page 32

    3 vacon • 30 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on opta5 (coded terminal painted black) note: encoder inputs are wide range inputs that can be used with encoders using +15v or +24v. Technical data: note: a high ...

  • Page 33

    Descriptions of vacon® option boards vacon • 31 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 jumper selections on the opta5 board, there are four jumper blocks; x4 is used to program the control voltage (auxiliary voltage), x2, x5 and x6 are set according the voltage of...

  • Page 34

    3 vacon • 32 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ encoder connection – single-ended figure 15. Htl type encoder connection (open source) using single-ended inputs note! Grounding is to be connected only at the ac drive to avoid...

  • Page 35

    Descriptions of vacon® option boards vacon • 33 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.1.6 opta7 description: duplicate encoder board for vacon ® nxp. Encoder input board with programmable control voltage for the encoder. The opta7 board is designed for htl (hig...

  • Page 36

    3 vacon • 34 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on opta7 note: encoder inputs are wide range inputs that can be used with encoders using +15v or +24v. Table 12. Opta7 i/o terminals terminal parameter reference k...

  • Page 37

    Descriptions of vacon® option boards vacon • 35 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 technical data: note: a high pulse frequency combined with a great cable capacitance places a considerable load on the encoder. Apply therefore as low a voltage as possible for ...

  • Page 38

    3 vacon • 36 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ usage: closed loop vector control, positioning applications. The opta7 encoder board is mainly used in demanding system applications, e.G. When measuring the motor speed with tw...

  • Page 39

    Descriptions of vacon® option boards vacon • 37 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 encoder connection the figures below present examples of a chain connection of several opta7 boards (figure 17) and a connection of two encoders to the opta7 option board (figur...

  • Page 40

    3 vacon • 38 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ figure 18. Connection of two encoders to opta7 board opta7 parameters table 13. Opta7 parameters number parameter min max default note 7.3.1.1 encoder 1 pulse/revolution 0 65535...

  • Page 41

    Descriptions of vacon® option boards vacon • 39 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 opta7 monitoring values 3.1.7 opta8 table 14. Opta7 monitoring values number monitored value unit description mon 7.3.2.1 encoder 1 frequency hz motor speed in hz calculated fro...

  • Page 42

    3 vacon • 40 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on opta8 (coded terminals painted black) table 15. Opta8 i/o terminals terminal parameter reference keypad/ncdrive technical information 1 +10 vref refer.Output +1...

  • Page 43

    Descriptions of vacon® option boards vacon • 41 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 jumper selections there are four jumper blocks on the opta8 board. The factory defaults and other available jumper selections are presented below. Figure 19. Jumper positions fo...

  • Page 44

    3 vacon • 42 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ opta8 parameters 3.1.8 opta9 table 16. Opta8 board-related parameters number parameter min max default note 1 ai1 mode 1 5 3 1 = 0...20ma 2 = 4...20ma 3 = 0...10v 4 = 2...10v 5 ...

  • Page 45

    Descriptions of vacon® option boards vacon • 43 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 i/o terminals on opta9 see page 19. Jumper selections see page 20. Opta9 parameters see page 21. 3.1.9 optal description: dual i/o expander board with six 42…240 vac digital inp...

  • Page 46

    3 vacon • 44 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optal table 17. Optal i/o terminals terminal parameter reference keypad/ncdrive technical information 1 +15 v 15 v out – together with terminal 2 max 200 ma 2 +...

  • Page 47

    Descriptions of vacon® option boards vacon • 45 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.1.10 optae description: encoder board for vacon ® nxp. Encoder input board with programmable control voltage for an encoder. The optae board is designed for htl (high voltage ...

  • Page 48

    3 vacon • 46 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optae (coded terminal painted black) note: encoder inputs are wide range inputs that can be used with encoders using +15v or +24v. Technical data: jumper select...

  • Page 49

    Descriptions of vacon® option boards vacon • 47 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 usage: closed loop vector control. The optae board is mainly used in conventional industrial applications where encoder cable lengths are relatively long. Encoder connection - s...

  • Page 50

    3 vacon • 48 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ encoder connection – differential figure 22. Htl type encoder connection using differential inputs optae parameters table 19. Optae board-related parameters number parameter min...

  • Page 51

    Descriptions of vacon® option boards vacon • 49 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.1.11 optan description: standard i/o board for vacon ® nxp with 6 galvanically isolated digital inputs and two analogue inputs/outputs. The analogue channels are programma- bl...

  • Page 52

    3 vacon • 50 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optan table 20. Optan i/o terminals terminal technical information 1 ai1- selection v or ma with jumper block j1 default: 0– +10v (ri = 200 k Ω) (-10v..+10v joy...

  • Page 53

    Descriptions of vacon® option boards vacon • 51 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 jumper selections optan board parameters j1 (ai1), j2 (ai2) analog input mode 0 ... 10 d (default) j1 (ai1), j2 (ai2) analog input mode –10 ... +10v cd j1 (ai1), j2 (ai2) analog...

  • Page 54

    3 vacon • 52 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ optan board i/o monitor values 7.1.1.4 ao2 mode 1 5 3 1 = 0...20ma 2 = 4...20ma 3 = 0...10v 4 = 2...10v 5 = -10...+10v table 22. Optan board monitor values number parameter desc...

  • Page 55

    Descriptions of vacon® option boards vacon • 53 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.2 i/o expander boards optb_ • option boards used for i/o expansion • this board type can normally be plugged into slots b, c, d or e. The number of control inputs and outputs ...

  • Page 56

    3 vacon • 54 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3.2.1 optb1 i/o terminals on optb1 description: vacon ® nx i/o expander board with six bidirectional terminals. Allowed slots: b, c, d, e type id: 16945 terminals: one terminal ...

  • Page 57

    Descriptions of vacon® option boards vacon • 55 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 jumper selections on the optb1 board, there are two jumper blocks. The jumper block x2 is used to define the bidirectional terminal as either input or output. The other jumper b...

  • Page 58

    3 vacon • 56 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3.2.2 optb2 i/o terminals on optb2 note: this expander board can be placed into four different slots on the control board. Therefore, the 'x' given in the parameter reference mu...

  • Page 59

    Descriptions of vacon® option boards vacon • 57 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.2.3 optb4 description: vacon ® nx i/o expander board with one galvanically isolated analogue input and two galvanically isolated analogue outputs (standard signals 0(4)…20ma)....

  • Page 60

    3 vacon • 58 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optb4 note: this expander board can be placed into four different slots on the control board. Therefore, the 'x' given in the parameter reference must be replac...

  • Page 61

    Descriptions of vacon® option boards vacon • 59 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 i/o terminals on optb5 note: this expander board can be placed into four different slots on the control board. Therefore, the 'x' given in the parameter reference shall be repla...

  • Page 62

    3 vacon • 60 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3.2.5 optb8 i/o terminals on optb8 description: temperature measuring board with three pt-100 sensor (3-wire) inputs. The measurable temperature range is –30...200 cº on pt-100 ...

  • Page 63

    Descriptions of vacon® option boards vacon • 61 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 optb8 accuracy the following table represents the results of accuracy measurements in laboratory environment. In the tests we used draga jamak cable. The testing covered differe...

  • Page 64

    3 vacon • 62 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ jumper selections up to three pt100 sensors can be connected to the third pt100 input. You can select the number of sensors in use with jumper block x2: 1 2 3 1 2 3 1 2 3 1 sens...

  • Page 65

    Descriptions of vacon® option boards vacon • 63 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.2.6 optb9 i/o terminals on optb9 note: this expander board can be placed into four different slots on the control board. Therefore, the 'x' given in the parameter reference mu...

  • Page 66

    3 vacon • 64 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ depending on the slot which the expander board is plugged into. See chapter 1.7. 3.2.7 optbb an absolute encoder is a type of encoder capable of specifying its absolute position...

  • Page 67

    Descriptions of vacon® option boards vacon • 65 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 sinus signals require some precautions for noise immunity that may be a little more demanding than conventional square wave encoders. Use of twisted pairs (possibly with individ...

  • Page 68

    3 vacon • 66 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ jumper selections on the optbb board, there is one jumper block used to program the control voltage (auxiliary voltage). The factory default and other available jumper selection...

  • Page 69

    Descriptions of vacon® option boards vacon • 67 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 optbb board parameters optbb board monitoring values optbb board information pages table 33. Optbb board parameters code parameter min max default selections description 7.3.1.1...

  • Page 70

    3 vacon • 68 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ optbb option board status leds yellow led green led led meaning off option board not activated on option board in initialisation state waiting for activation command from the ac...

  • Page 71

    Descriptions of vacon® option boards vacon • 69 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.2.8 optbh i/o terminals on optbh optbh accuracy the following tables represent the results of accuracy measurements in laboratory environment. In the tests we used draga jamak...

  • Page 72

    3 vacon • 70 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ connecting temperature sensors to optbh option board: use shielded cables and connect the cable shield to grounding clamp in the drive. Allowed sensor configurations are shown o...

  • Page 73

    Descriptions of vacon® option boards vacon • 71 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.3 adapter boards optd_ the adapter boards do not provide any additional i/o but are used to connect the ac drive to a vacon ® communication bus (system bus, spi, can). Note th...

  • Page 74

    3 vacon • 72 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optd1 note: the terminals of the board are protected with a rubber pin. Be sure to leave the pin in the unused terminals in order to avoid disturbances. Connect...

  • Page 75

    Descriptions of vacon® option boards vacon • 73 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 figure 24. Basic connection of ac drives with optd1 3.3.2 optd2 note! This figure presents the layout of d2 board version h or later. See chapter jumper selections below. Descri...

  • Page 76

    3 vacon • 74 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optd2 jumper selections there are four jumper blocks on the optd2 board. The factory defaults and other available jumper selections are presented below. Figure ...

  • Page 77

    Descriptions of vacon® option boards vacon • 75 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 figure 26. X3 jumper selections for optd2, version h and later note! Position c can be used with 3- or 4-wire can cable to interconnect isolated can ground levels in the network...

  • Page 78

    3 vacon • 76 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ alternative connection of “can gnd” signal: connect ‘can gnd’ together between all nodes. Use the signal wire inside the shield for this purpose, see figure below: figure 28. Al...

  • Page 79

    Descriptions of vacon® option boards vacon • 77 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 figure 29. Connection example of ac drives with optd2 3.3.3 optd3 description: rs-232 adapter board. Galvanically decoupled. Used mainly for application engineering to connect a...

  • Page 80

    3 vacon • 78 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ i/o terminals on optd3 note: if optci ethernet option board is used for nc tools connection, like ncload, the optd3 board cannot be used. Jumper selections there is one jumper b...

  • Page 81

    Descriptions of vacon® option boards vacon • 79 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 3 3.3.4 optd6 i/o terminals on optd6 jumper selections there are two jumper blocks on the optd6 board. The factory defaults and other available jumper selections are presented bel...

  • Page 82

    3 vacon • 80 descriptions of vacon® option boards local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ figure 30. Jumper selections for optd6, up to version e. Figure 31. X3 jumper selections for optd6, version f and later. Note! Position c can be used with 3- or 4-wire can cable...

  • Page 83

    Vacon® o p tion boards – operational details v acon • 81 lo cal co ntacts: http://drive s. Danfo ss.Com/danfoss-d rive s/local- contacts/ 4 4. Vacon ® option boards – operational details table 46. Vacon ® option boards, types a and b board type slots allowed 6) id di do ai (ma/v) ai (ma), isol. Ao (...

  • Page 84

    4 vacon • 8 2 vaco n® op tion board s – op erational details local contacts: http ://driv e s.D a nfo ss. Com/danfos s -drive s/lo cal-con tacts/ table 47. Vacon ® option boards, type d adapter boards nxoptd_ optd1 de 17457 system bus adapter board: 2 x fiber optic pairs optd2 7) (b)de 17458 system ...

  • Page 85

    Vacon® option boards – operational details vacon • 83 local contacts: http://drives.Danfoss.Com/danfoss-drives/local-contacts/ 4 table 48. All in one applications and supported vacon ® nx option boards nxs, nxp nxl board type basic boards opta_ basic nxfiff01 standard nxfiff02 local- remote nxfiff03...