Flue installation instructions ecoTEC 834449_13
4
h
Note
Two types of flue gas installation are available
for ecoTEC boilers:
- standard concentric flue gas installations
(outer diameter 100 mm)
- a concentric system with a larger diameter
(outer diameter 125mm) which can be used to
achieve longer air/flue gas pipes.
Note
The air/flue duct operates at very low tempera-
tures therefore no clearance is necessary be-
tween the air duct and adjacent services.
Note
Ensure while installation work is being carried
out that no debris such as swarf, filings or frag-
ments of mortar are allowed to remain in the
air/flue duct.
2.1.1
Intended
use
Valliant flue pipes for ecoTEC are state-of-the-art
appliances which are designed in accordance with
approved safety regulations. Nevertheless, there is still
a risk of death or serious injury to the user or others or
of damage to the device and other property in the event
of improper use or use for which it is not intended.
The Vaillant flue pipes for ecoTEC may only be used
with the unit types named in this installation manual.
Any other use or extended use is considered to be im-
proper. The manufacturer or supplier is not liable for
any resulting damage. The user alone bears the risk. In-
tended use includes the observance of the relevant
manual.
2.1.2
Preliminary remarks for room sealed appli-
ances
This appliance should only be installed in conjunction
with either a Vaillant flue system or an alternative ap-
proved system (details of flue approval categories can
be found in the technical section of the installation man-
ual).
Install the flue system as detailed in the separate flue
installation instructions supplied with this boiler.
2.1.3 Related
documents
The installation of the boiler must be in accordance with
the relevant requirements of Gas Safety (Installation
and Use) Regulations 1998, Health and Safety Document
No. 635 (The Electricity at Work Regulations 1989),
BS7671 (IEE Wiring Regulations) and the Water Supply
(Water Fitting) Regulations 1999, or The Water Bylaws
2000 (Scotland). It should also be in accordance with
the relevant requirements of the Local Authority, Build-
ing Regulations, The Building Regulations (Scotland), he
Building Regulations (Northern Ireland) and the relevant
recommendations of the following British Standards:
BS 6700: Services supplying water for domestic use
within buildings and their curtilages.
BS 6798: Specification for installation of gas fired boil-
ers not exceeding 60 kW input.
BS 6891: Specification for installation of low pressure
gas pipework up to 28 mm (R1) in domestic
premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water
central heating systems.
Institute of Gas Engineers Publication IGE/UP/7/1998:
”Guide for gas installations in timber framed housing”
BS. 5482 Pt. 1 Domestic butane and propane gas burn-
ing installations.
IGE/UP1 Soundness testing and purging of industrial
and commercial gas installation.
IGE/UP2 Gas installation pipework, boosters and com-
pressors on industrial and commercial
premises.
IGE/UP10 Installation of gas appliances in industrial and
commercial premises.
BS. 6644 Installation of gas fired hot water boilers of
rated inputs between 60 kW and 2 MW (2nd
and 3rd family gases).
BS. 5449 Forced circulation hot water central heating
systems for domestic premises. Note: only up
to 45 kW.
BS. 6880 Low temperature hot water heating systems
of output greater than 45 kW.
Part 1 Fundamental and design consid-
erations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and
maintenance.
BS. 4814 Specification for: Expansion vessels using an
internal diaphragm, for sealed hot water heat-
ing systems.
BS. 5440 Installation and maintenance of flues and
ventilation for gas appliances of rated input
not exceeding 70 kW net (1st, 2nd and 3rd
familygases).
Part 1 Specification for installation of
flues.
Part 2 Specification for installation and
maintenance of ventilation for gas ap-
pliances.
2 Standard Concentric Systems Ø 60/100