Vaillant ecoLEVEL Installation And Maintenance Instructions Manual

Other manuals for ecoLEVEL: Operating Manual
Manual is about: Condensed water pump

Summary of ecoLEVEL

  • Page 1

    Installation and maintenance instructions for the competent person gb, ie installation and maintenance instructions ecolevel condensed water pump.

  • Page 2

    Table of contents 2 ecolevel installation and maintenance instructions 0020029316_01 table of contents 1 notes on the documentation ..................................... 3 1.1 attaching and storing documents ............................... 3 1.2 applicability of the instructions .......................

  • Page 3

    Notes on the documentation ecolevel installation and maintenance instructions 0020029316_01 3 11 1 notes on the documentation the following information is intended to help you through- out the entire documentation. Further documents apply in combination with these operat- ing, installation and maint...

  • Page 4

    Safety information and regulations 4 ecolevel installation and maintenance instructions 0020029316_01 2 the condensed water pump is not suitable for the pumping of other fluids or solid media. In particular, waste water of all types, chemicals and emulsions that contain oil must not be fed into the ...

  • Page 5

    Safety information and regulations ecolevel installation and maintenance instructions 0020029316_01 5 2 material damage caused by unsuitable discharge pipes if you use discharge pipes that are not acid-resistant, this can lead to leaks and damage caused by leaking condensed water. > if you need to e...

  • Page 6

    Installation 6 ecolevel installation and maintenance instructions 0020029316_01 3 3 installation 3.1 scope of delivery betriebs anleitung für den betreiber de, at, bede, chde betriebs anleitung ecolevel kondenswasserpumpe 1 2 3 4 5 6 8 7 9 10 3.1 scope of delivery item component dimensions number 1 ...

  • Page 7

    Installation ecolevel installation and maintenance instructions 0020029316_01 7 3 3.4 dimensions and installation clearances 100 mm 90 mm 165 mm 115 mm 150 mm 175 mm min. 2 00 mm min. 5 mm min. 5 mm min. 2 00 mm min. 5 mm min. 5 mm 3.2 dimensions and installation clearances > during installation, ad...

  • Page 8

    Hydraulic connection 8 ecolevel installation and maintenance instructions 0020029316_01 4 > push the condensed water pump from above onto the guide surfaces of the wall bracket. A small hook retains the pump on the bracket in the low- est position. I the condensed water pump can be secured in the br...

  • Page 9

    Hydraulic connection ecolevel installation and maintenance instructions 0020029316_01 9 4 4.2 install the inlet hose shortening and plugging in the inlet hose > determine the required length of the inlet hose. > shorten the hose so that it clicks a maximum of 3 notches into the cover. > ensure that ...

  • Page 10

    Hydraulic connection 10 ecolevel installation and maintenance instructions 0020029316_01 4 a caution: material damage caused by unsuitable discharge pipes if you use discharge pipes that are not acid- resistant, this can lead to leaks and damage caused by leaking condensed water. > if you need to ex...

  • Page 11

    Hydraulic connection ecolevel installation and maintenance instructions 0020029316_01 11 4 1 2 3 4 4.6 complete installation at the discharge pipe > push the end of the white 3/4" coupling piece (3) tightly onto the discharge pipe (4). > pull on the drain hose (1) to make sure that the snap-on conne...

  • Page 12

    Electrical connection 12 ecolevel installation and maintenance instructions 0020029316_01 5 5 electrical connection before you begin the electrical connection of the unit, the installation (¬ section 3) and the hydraulic connection (¬ section 4) for the ecolevel condensed water pump must be complete...

  • Page 13

    Electrical connection ecolevel installation and maintenance instructions 0020029316_01 13 5 5.4 connecting the condensed water pump to the safety cut-out switch the type of connection on the printed circuit board (pcb) depends upon the individual boiler. The table (¬ tab. 5.1) shows which boiler mus...

  • Page 14

    Electrical connection 14 ecolevel installation and maintenance instructions 0020029316_01 5 connection type b for connection type b, you can connect the safety cut-out switch to the extra-low voltage circuit of the boiler using variants i., or ii. 1 1 x35 x90 display x21 5.4 connecting the safety cu...

  • Page 15

    Operation and troubleshooting ecolevel installation and maintenance instructions 0020029316_01 15 6 6 operation and troubleshooting once the installation and the hydraulic and electrical con- nections are completed, the ecolevel condensed water pump is ready for operation. The green led lights up. T...

  • Page 16

    Handing over to the operator 16 ecolevel installation and maintenance instructions 0020029316_01 7 cause troubleshooting pump not pumping: kink in the drain hose remove kink motor blocked visual inspection of the motor inlet: check for foreign bodies and remove if necessary motor defective replace c...

  • Page 17

    Maintenance ecolevel installation and maintenance instructions 0020029316_01 17 8 8 maintenance a danger! Risk of death from electric shock! There is a risk of electrical shock from live con- nections. > always switch off the power supply to the pump and to the boiler before performing maintenance w...

  • Page 18

    Spare parts 18 ecolevel installation and maintenance instructions 0020029316_01 9 8.2 cleaning the pump 2 1 8.3 cleaning the pump removing the internal component > remove the cover of the pump. > press the clip on the internal component (1) inwards and hold. > remove the internal component (1) from ...

  • Page 19

    Guarantee and customer service ecolevel installation and maintenance instructions 0020029316_01 19 10 10 guarantee and customer service 10.1 vaillant guarantee vaillant provides a full parts and labour guarantee for this appliance for the duration as shown on the enclosed regis- tration card which m...

  • Page 20

    Technical data 20 ecolevel installation and maintenance instructions 0020029316_01 12 12 technical data technical data units ecolevel design appliance for wall-mounted installation nominal capacity l 0.5 supply voltage v 230 max. Current consumption a 1 frequency hz 50 max. Nominal output w 25 max. ...

  • Page 24

    00 2 0 0 2 9 3 16_01 gbie 10 2 012 – s ubject t o change manufacturer supplier.