Vaillant Flue pipe VKK SERIES Installation Manual

Manual is about: for ecoCRAFT

Summary of Flue pipe VKK SERIES

  • Page 1

    For the heating engineer installation manual flue pipe for ecocraft vkk 806/3-e vkk 1206/3-e vkk 1606/3-e vkk 2006/3-e vkk 2406/3-e vkk 2806/3-e gb modular gas condensing boiler.

  • Page 2

    Installation manual flue pipe for ecocraft 0020058722_02 2 contents contents 1 notes on the documentation .............................. 3 1.1 lodging and storage of the documents ..................3 1.2 symbols used .................................................................3 1.3 applicabilit...

  • Page 3

    3 installation manual flue pipe for ecocraft 0020058722_02 1 notes on the documentation the following information is intended to help you throughout the entire documentation. Further docu- ments apply in combination with this installation manu- al. We accept no liability for any damage caused by fai...

  • Page 4

    Installation manual flue pipe for ecocraft 0020058722_02 4 a caution! Risk of corrosion in the flue gas installation! The combustion air fed to the unit must be free of chemicals which contain, e.G. Fluorine, chlo- rine or sulphur. Sprays, release or cleaning agents, paints and adhesives can contain...

  • Page 5

    5 installation manual flue pipe for ecocraft 0020058722_02 4 tested and approved air/flue pipes - room-sealed this chapter describes the peripheral conditions under which the ecocraft condensing gas boilers can be fit- ted to flue pipes supplied by the manufacturers shown in table 4.1. 4.1 descripti...

  • Page 6

    Installation manual flue pipe for ecocraft 0020058722_02 6 the following describes the four possibilities for flue pipes: - flue pipes for room sealed operation, combustion air from the duct - flue pipes for room sealed operation, combustion air through the external wall - flue pipes for room sealed...

  • Page 7

    7 installation manual flue pipe for ecocraft 0020058722_02 appliance type minimum shaft cross-section maximum total pipe length (l 1 + l 2 + l 3 ) dn 130 dn 140 dn 150 dn 200 ecocraft vkk 806/3-e round: dn+60 mm square dn+40 mm 27.2 34.7 43.6 - round: dn+80 mm square: dn+60 mm 30.0 30.0 50.0 - ecocr...

  • Page 8

    Installation manual flue pipe for ecocraft 0020058722_02 8 4.4 air/flue pipe – room sealed, combustion air through the external wall l 1 l 2 l 4 l 3 min . 1 m fig. 4.2 air / flue pipe – room sealed, combustion air through the external wall appliance type minimum shaft cross-section maximum total pip...

  • Page 9

    9 installation manual flue pipe for ecocraft 0020058722_02 4.5 air/flue pipe – room sealed, combustion air and flue gas evacuation via the roof l 1 l 4 l 2 l 5 l 3 min . 1m fig. 6.3 air / flue pipe – room sealed, combustion air and flue gas evacuation via the roof appliance type maximum total pipe l...

  • Page 10

    Installation manual flue pipe for ecocraft 0020058722_02 10 4.6 air/flue pipe – room sealed, combustion air through the external wall, flue pipe on the facade l 1 l 4 l 2 l 3 min . 1 m fig. 6.47 air/flue pipe – room sealed, combustion air through the external wall, flue pipe on the facade appliance ...

  • Page 11

    11 installation manual flue pipe for ecocraft 0020058722_02 5 guarantee vaillant warranty vaillant provide a full parts and labour warranty for this appliance. The appliance must be installed by a suitably competent person in accordance with the gas safety (installation and use) regulations 1998, an...

  • Page 12