    V 12-025 w v 12-035 w v 12-050 w v 12-060 w v 12-060 m2w training manual air-conditioner - climavair split type en.

  • Page 2

    2 contents installations-und wartungsanleitung split-gerät, wandhängend contents 1 dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.1 indoor unit dimensions . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 outdoor unit dimensions . . . . . . . . . . . . . . . . . . . . . 4 ...

  • Page 3

    Split type installation manual 3 en 1 dimensions 1.1 indoor unit dimensions the indoor unit provides acclimatised air inside the room to be acclimatised. The dimensions and weights of the indoor unit are shown on figure 1.1 and table 1.1, depending on the model (please consult the model nameplate). ...

  • Page 4

    Split type installation manual 4 1 dimensions 1.2 outdoor unit dimensions the outdoor unit ensures that the absorbed air is released to the outside from the room during operation in cooling mode and that the heat introduced into the room during operation in heat pump mode is taken from the outside. ...

  • Page 5

    Split type installation manual 5 en 1.3 general installation diagram fig. 1.3 general sketch of the installation and the minimum mounting distances. Legend 1 indoor unit 2 outdoor unit 3 outdoor unit condensed water drainage pipe a front separation (minimum 10 cm) b top separation from the ceiling (...

  • Page 6

    Split type installation manual 6 3 connecting diagram fig. 3.1 connection. 3.1 electric characteristics v 12-025 w v 12-035 w v 12-050 w v 12-060 w power supply (v/ph/hz) 230/1/50 230/1/50 230/1/50 230/1/50 s upply recommended minimum supply section up to 25 meters (mm 2 ) 1,5 1,5 2,5 2,5 indoor / o...

  • Page 7

    Split type installation manual 7 en 4 technical specifications v 12-025 w v 12-035 w v 12-050 w v 12-060 w indoor unit v 12-025 hwi v 12-035 hwi v 12-050 hwi v 12-060 hwi outdoor unit v 12-025 hwo v 12-035 hwo v 12-050 hwo v 12-060 hwo power supply v/ph/hz 230/1/50 cooling capacity kw 2,86 3,40 5,40...

  • Page 8

    Split type installation manual 8 v12-060 m2w indoor unit 1 v 12-025 mhwi indoor unit 2 v 12-035 mhwi outdoor unit v 12-060 m2hwo power supply v/ph/hz 230/1/50 cooling capacity kw 6,55 btu 22.354 fg/h 5.633 capacity by indoor kw 2,92 kw 3,63 power input by indoor kw 0,97 kw 1,21 power input kw 2,18 n...

  • Page 9

    Split type installation manual 9 en outdoor unit air flow volume m3/h 3.050 sound power level db(a) 65 sound pressure level db(a) 52 number of fans 1 refrigerant r410a refrigerant charge heat pump gr 1000g & 1200g number of compressors 2 compressor type rotary compressor model pa108x1c-4fzde / pa140...

  • Page 10

    Split type installation manual 10 5 temperature by capacities cooling outdoor temperature dry indoor conditions 21ºc 25ºc 30ºc 35ºc 40ºc 45ºc 50ºc 21ºc d 15ºc w total capacity- kw 2,57 2,56 2,55 2,45 2,33 2,05 1,77 sensitive capacity- kw 1,96 1,95 1,94 1,87 1,78 1,57 1,35 input- kw 0,58 0,63 0,69 0,...

  • Page 11

    Split type installation manual 11 en temperature by capacities 5 cooling outdoor temperature dry indoor conditions 21ºc 25ºc 30ºc 35ºc 40ºc 45ºc 50ºc 21ºc d 15ºc w total capacity- kw 3,15 3,14 3,12 3,01 2,87 2,54 2,21 sensitive capacity- kw 2,37 2,36 2,35 2,27 2,16 1,91 1,66 input- kw 0,69 0,75 0,82...

  • Page 12

    Split type installation manual 12 5 temperature by capacities cooling outdoor temperature dry indoor conditions 21ºc 25ºc 30ºc 35ºc 40ºc 45ºc 50ºc 21ºc d 15ºc w total capacity- kw 4,95 4,93 4,91 4,72 4,49 3,94 3,38 sensitive capacity- kw 3,77 3,75 3,74 3,60 3,42 3,01 2,59 input- kw 1,08 1,18 1,28 1,...

  • Page 13

    Split type installation manual 13 en temperature by capacities 5 cooling outdoor temperature dry indoor conditions 21ºc 25ºc 30ºc 35ºc 40ºc 45ºc 50ºc 21ºc d 15ºc w total capacity- kw 6,25 6,23 6,21 6,02 5,79 5,24 4,68 sensitive capacity- kw 4,97 4,95 4,94 4,80 4,62 4,21 3,79 input- kw 1,49 1,59 1,69...

  • Page 14

    Split type installation manual 14 5 temperature by capacities cooling outdoor temperature dry indoor conditions 21ºc 25ºc 30ºc 35ºc 40ºc 45ºc 50ºc 21ºc d 15ºc w total capacity- kw 6,16 6,13 6,11 5,94 5,71 5,19 4,66 sensitive capacity- kw 4,90 4,89 4,87 4,74 4,57 4,18 3,79 input- kw 1,57 1,67 1,77 1,...

  • Page 15

    Split type installation manual 15 en 6 wiring circuit diagram 6.1 mono wiring circuit diagram 6 fig. 6.1.1 wiring circuit diagram for models v 12-025 w and v 12-035 w..

  • Page 16

    Split type installation manual 16 fig. 6.1.2 wiring circuit diagram for models v 12-050 w. 6 wiring circuit diagram.

  • Page 17

    Split type installation manual 17 en wiring circuit diagram 6 fig. 6.1.3 wiring circuit diagram for models v 12-060 w..

  • Page 18

    Split type installation manual 18 6 wiring circuit diagram 6.2 multi fig. 6.2.1 wiring circuit diagram for multi indoor units.

  • Page 19

    Split type installation manual 19 en wiring circuit diagram 6 rd red gy grey bk black gn green bl blue wh white pr purple ye yellow or orange br brown comp compressor duct-t duct temperature sensing device yv four way valve comp- delay compressor delay tr transformer fm out-warm fan motor led indica...

  • Page 20

    Split type installation manual 20 check if the resistance value of sensor is abnormal. Replace the sensor check if the circuit of sensor is open or short; pins are not well connected; sealing off or rosin join on the pcb correct the error yes n o components on pcb are broken. Replace the pcb yes 7 s...

  • Page 21

    Split type installation manual 21 en check if the winding resistance and operating current of the compressor are normal replace the compressor check if the high and low pressure is normal when the unit is running check unit if it is leakage and fill the refrigerant again. No y e s check if the coil ...

  • Page 22

    Split type installation manual 22 check if the power supply of fan motor is well connected re-connect it, and make sure it’s well connected replace the fan motor no y e s check if the controlled silicon or any electric components are broken yes e5 pg fan motor failure(no feedback signal of indoor fa...

  • Page 23

    Split type installation manual 23 en check whether the winding resistance and operation current of the compressor are normal replace the compressor no y e s check whether the indoor and outdoor wiring is right connect them again check unit if it is leakage and fill the refrigerant again. No e7 outdo...

  • Page 24

    Split type installation manual 24 check if high/low pressure valve is open. Open the valve. Replace the sensor. No y e s check if the indoor coil temperature sensor is not fixed well. No e8 lack of refrigerant e5 error diagnosis and solution: n o 7 service diagnosis no re-fix it well. Check if the i...

  • Page 25

    Split type installation manual 25 en check if the resistance value of sensor is abnormal. Replace the sensor check if the circuit of sensor is open or short; pins are not well connected; sealing off or rosin join on the pcb correct the error yes n o components on pcb are broken. Replace the pcb yes ...

  • Page 26

    Split type installation manual 26 check if the power supply of fan motor is well connected re-connect it, and make sure it’s well connected replace the fan motor no y e s check if the controlled silicon or any electric components are broken yes e5 pg fan motor failure e3 error diagnosis and solution...

  • Page 27

    Split type installation manual 27 en check if high/low pressure valve is open. Open the valve replace the sensor no y e s no e7 lack of refrigerant e7 error diagnosis and solution check if the indoor coil temperature sensor runs normal check if the indoor coil temperature sensor is not fixed well y ...

  • Page 28

    Split type installation manual 28 8 photographs 8 photographs 8.1 compresor 025 w 8.2 compresor 025 w multi.

  • Page 29

    Split type installation manual 29 en photographs 8 8.3 compresor 035 w 8.4 compresor 035 w multi.

  • Page 30

    Split type installation manual 30 8 photographs 8.5 compresor 050 w 8.6 compresor 065 w.

  • Page 31

    Split type installation manual 31 en photographs 8 8.7 pcb-025-035-multi.

  • Page 32

    Split type installation manual 32 8 photographs 8.8 pcb-025-035w mono.

  • Page 33

    Split type installation manual 33 en photographs 8 8.9 pcb-050-065w-mono.

  • Page 34

    Split type installation manual 34 8 photographs 8.10 pcb-outdoor-multi.

  • Page 35

    Split type installation manual 35 en 9 pcb explanation 9.1 pcb mono 9.1.1 electronic function - electric control working environment • input voltage: 220~240v • input power frequency:50hz • ambient temperature: -7°c~+43°c • indoor fan normal working amp is less than 1a, • outdoor fan. Normal working...

  • Page 36

    Split type installation manual 36 • auto fan under cooling mode: condition t=indoor temp.- setting temp. Indoor fan speed temp. Up t low 3ºc med. T>5ºc high temp. Down t>3ºc high 1ºc med. T low • anti-freezing control to indoor evaporator under cooling mode condition compressor outdoor fan temp. Tim...

  • Page 37

    Split type installation manual 37 en pcb explanation 9 the operation will be restarted up six minutes later, if t is higher than te7 for the second time within 10 minutes after the start up, all of the output will be closed, and e8 will be displayed on the display panel. • the louver opens to standa...

  • Page 38

    Split type installation manual 38 9 pcb explanation 9.2.2 functions: automatic mode: 1. The range of setting temperature: 16ºc - 32ºc (as for the jingling common remote controller, the setting temperature is just 25ºc and not adjustable); 2. The air conditioner will enter automatic mode(the default ...

  • Page 39

    Split type installation manual 39 en • when the air conditioner is turned off, the air door turns to the full opening position firstly, and then turns back 92° and closed. • when the air conditioning is powered up, the air door turns to the full opening position firstly and then begins to operate. •...

  • Page 40

    Split type installation manual 40 9. The frosting protection of indoor evaporator: after the compressor runs for 3 minutes, the compressor, indoor fan and swaying wind stop running if the temperature of the indoor coil keeps no higher than -10 ºc within 3 minutes(the programming data is 1e#).The com...

  • Page 41

    Split type installation manual 41 en note! When tp is lower than 30ºc, the air door will turn on upward to the position of anti-cold wind at 60° b. During the process that the temperature of indoor coil increases from 25 ºc to 30 ºc, the slight breeze is blown from the indoor fan. A. During the proc...

  • Page 42

    Split type installation manual 42 two circles and then stops at the starting position to be idle for 30s for protection. 7. The assistant electric heating working condition: the assistant electric heating will be operated automatically when all of the following conditions are met. 1) the compressor ...

  • Page 43

    Split type installation manual 43 en immediately and show the time which is reduced by one per hour. When the time comes, the air conditioner is turned on. If you set the timing off, the air conditioner continues to run and show the time which will be reduced by one per hour. When the time comes, th...

  • Page 44

    Split type installation manual 44 the high speed. Every half second the following items will be output in turn: the compressor, the outdoor fan, the four-way valve and the electrical heater. 3. Input: if the room temperature sensor or the tube temperature sensor is in short circuit or breaks, the fa...

  • Page 45

    Split type installation manual 45 en 2) if the room temperature sensor goes wrong, the system still has the anti-frosting protection and anti- freezing protection function. 6. In heating mode, if the temperature sensor of the indoor coil goes wrong, after delaying for 3 minutes the fault code will b...

  • Page 46

    Split type installation manual 46.

  • Page 47

    Vaillant behoudt zich het recht voor om veranderingen aan te brengen zonder voorafgaande kennisgeving. Vaillant si riserva il diritto di apportare modifiche senza preavviso. Vaillant pridržava pravo na izmjene bez najave. Vaillant se reserva el derecho de introducir modificaciones sin previo aviso. ...

  • Page 48

    V12_w_m2w -tt 01/ 2 009 vaillant ltd vaillant house medway city estate trident close rochester kent me2 4ez telephone 0164 292300 fax 0164 290166 www.Vaillant.Co.Uk info@vaillant.Co.Uk vaillant bv paasheuelweg 42 1105 bj amsterdam telefoon (020) 565 92 00 telefax (020) 696 93 66 www.Vaillant.Nl vail...