Vaisala DSC111 Installation Manual - page 6
1" CONDUIT & FITTINGS
SUPPLIED BY CONTRACTOR
20"X16"10" ALUMINUM
ENCLOSURE FOR SERIAL
DEVICE SPLICE PANEL
CABLE TIE
(SPACED APPROX. 2' APART)
ENCLOSURE MOUNTED
TO POLE WITH STAINLESS
STEEL STRAPS
RPU MOUNTED TO TOWER
TYPE V CABLE RUNS
THRU CONDUIT FROM
RPU TO SERIAL DEVICE
SPLICE PANEL ENCLOSURE
WSP150
WSP150 SURGE PROTECTOR
MOUNTED TO POLE WITH
STAINLESS STEEL STRAPS
DST111
DSC111
GROUND WIRE TO
CABINET PANEL
SUPPLIED BY CONTACTOR
GROUND ROD SUPPLIED BY CONTRACTOR
GRADE
STRANDED 10 AWG
GROUND WIRE TO WSP150 SURGE
PROTECTOR.
NOTE: KEEP WIRE STRAIGHT AND SHORT.
See Note 3: 0.6 Meter Cable, 216548
Connects Power and RS485
Between DSC111 and DST111
DS111_pg4.dwg
REV
REVISIONS
PART / ITEM
SCALE:
6/15/10
NOTICE:
FILE NAME:
0
Initial Release
TS
CHANGE
DRAWN BY
SHEET
DWG. NO.
None
OF
4
7
DATE
ISSUE DATE
6/15/10
PI214719
DSC111/DST111 POLE
EQUIPMENT OUTLINE
INSTALLATION
10 Meter Power/RS485 Cable, 216546
Note 1: Plugs into the connector labeled "Power In/RS485"
on the bottom of the DSC111.
Note 2: Plugs into the back of the DST111 when a DSC111 is
not present.
Note 3. When both sensors are present, connect the 0.6
meter cable, 216548, between the connector labeled "Power
Out/RS485" on the bottom of the DSC111 and the connector
on the back of the DST111.
THIS DRAWING AND THE INFORMATION IT
DISCLOSES IS THE EXCLUSIVE PROPERTY OF
VAISALA. ANY REPRODUCTION OR USE OF THIS
DRAWING IN WHOLE OR IN PART, WITHOUT THE
EXPRESS CONSENT OF VAISALA IS PROHIBITED.
IMPORTANT: MAX LENGTH OF TYPE V EXTENSION CABLE IS 1000 Feet.