Valor 534AN Installation And Owner's Manual - page 9
9
4.6. Corner Location, Rear Vent
Connection, Horizontal Vent Run Only
See figure 8.
Can be used with either #551DVK standard vent kit or
#984 Dura-vent terminal cap and accessories. Adapter
#817VAK and 45º Dura-vent elbow # 945B will be
required. (See venting options section of this manual.)
4.7. Corner Location, Rear Vent
Connection, Vertical Rise, Horizontal
Termination
See figure 9.
Can be used with either #551DVK standard vent kit or
#984 Dura-vent terminal cap and accessories. Adapter
#817VAK, two 90º Dura-vent elbows #990B and Dura-
vent pipe lengths will be required. (See venting options
section of this manual).
All the vent pipe dimensional limits are as section 4.4.
4.8. Rear Vent Connection, Vertical Rise,
Through the Roof Termination
See figure 10.
Adapter #817VAK, one 90º vent elbow #990B, Dura-vent pipe lengths, a vertical vent terminal and roof flashing will be
required. Various other ceiling or roof items may be necessary depending on the particular installation (See venting options
section of this manual).
Note
1. The distance from the roof to the lowest terminal discharge opening depends on the roof pitch and must be in accordance
with the Dura-vent instructions supplied with the termination unit.
2. The venting system for these appliances is considered to be a Special Venting System. The rule in the Installation Code
CAN/CGA–B149 requiring a minimum vent height of 2ft above any portion of a building within 10ft does not,
therefore, apply.
Figure 10 Rear vent connection, through the roof
termination
Figure 9 Corner location, rear vent connection, vertical rise,
horizontal vent run
Figure 8 Corner location, rear vent connection, horizontal vent run