Vanguard V5 Operator's Manual

Manual is about: Fire Alarm Panel AVF & LCD -

Summary of V5

  • Page 1

    V 5 operator’s manual fire alarm panel (avf&lcd).

  • Page 2

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 1 of 21 contents 1. General 1.1 introduction 2 1.2 system description 2 1.2.1 zone detection module 3 1.2.2 system control module 3 1.2.3 lcd event logging module 5 2. Operating instructions 2.1. Normal operating conditions ...

  • Page 3

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 2 of 21 1. General 1.1 introduction this manual provided only the basis operator’s information on the control and operation of the fire alarm system. To ensure continuous reliability of the system, the owner or owner’s repre...

  • Page 4

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 3 of 21 1.2.1 zone detection module indicators and control a) fire (red) : zone in fire condition b) fault (amber) : zone detection circuit open/short fault condition c) disable (amber) : zone in disabled condition d) disabl...

  • Page 5

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 4 of 21 d) disabled (amber) : general disabled indicator, system in disabled condition e) system fault (amber) : indicate programmable micro controller failure f) fire sent (red) : fire signal to alarm remote monitoring stat...

  • Page 6

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 5 of 21 1.2.3 lcd event logging module indicators a) power on (green) : system energised by mains and/or standby battery b) processor fault (amber): indicates that micro processor unit failure in processing c) lcd display : ...

  • Page 7

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 6 of 21 2.2 fire alarm condition the panel / system shall enter into an alarm condition when an input device (such as smoke/heat detector, call point; or pressure/flow switch) is activated. Under fire alarm conditions: a) tw...

  • Page 8

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 7 of 21 2.2.2 resetting the system before the system is reset, the cause of the alarm must be investigated and duly rectified. In the case of a false alarm, make sure that there is no incident of fire before resetting the sy...

  • Page 9

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 8 of 21 2.4 initiating evacuate alarm the system is provided with a “sound alarm” switch in the event of emergency. To sound alarms for emergency evacuate: a) press “sound alarm” switch (red) (6) b) sound alarm amber led lig...

  • Page 10

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 9 of 21 d) no outputs are activated (fire output, external alarm bells/ aux output) e) when retard state (20 sec) lapses, retard state led go off f) “confirmation state” led (amber) lighted (120sec) during confirmation state...

  • Page 11

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 10 of 21 2.8.1.A view fire archive to view the recorded alarm zone event; a) press “menu” b) select “view fire archive” by “up” / “down” key and press “enter” (017tc: total event counter “017”, fire) (017: 17 th event of 017...

  • Page 12

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 11 of 21 (1) pnl adr: to set the panel address, select by “up” / “down” key and press “enter” to save (e.G. M000: main panel address 000, s001: sub panel address 001) (2) time: to set the time, select the time by “up” / “dow...

  • Page 13

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 12 of 21 3. Routine maintenance 3.1 introduction to ensure continuous reliability of the fire alarm system, regular testing and servicing shall be carried out. Only trained and competent personal are allowed to performance t...

  • Page 14

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 13 of 21 d) if possible, determine the cause of the fault or note the activities immediately prior to the area affected. E) silence the fault buzzer. F) inform the maintenance contractor responsible for servicing and arrange...

  • Page 15

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 14 of 21 d) check charger voltage and battery terminals condition. Ensure that no faults signal are indicated on the panel. E) disconnect the battery supply. The “power on” and “battery fault” indicators should be lighted an...

  • Page 16

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 15 of 21 c) where the heat-sensitive element of thermal detectors or the enclosure of other detectors are found to be coated with paint or any material likely to affect the operation of the detectors, such material should be...

  • Page 17

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 16 of 21 4. Fault finding tips check list fault specific indication possible causes action should be taken - manual call-point - vandalise - glass broken - heat / smoke detector - environment - faulty - flow switch - leakage...

  • Page 18

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 17 of 21 check list fault specific indication possible causes action should be taken earth “+ve” (red) (@ fbm) - one or more field “+ve” line and/or - alarm “–ve” line (in normal condition) earth fault earth “-ve” (amber) (@...

  • Page 19

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 18 of 21 check list fault specific indication possible causes action should be taken - fire signal line - disconnected “1” (amber) - open (@ dim) - termination - loose - fire signal line - shorted fire line trouble (alarm mo...

  • Page 20

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 19 of 21 v 5 technical specification and installation diagram.

  • Page 21

    O&m-v5-fap-avf-lcd r0 operator’s manual (fire alarm panel c/w avf & lcd) pg 20 of 21 technical specification fire alarm panel s/n i/p – o/p description capacity / rating end of line resistor (eolr) feature 1 zone - min 4 zones (multiple of 4 zones) - max 136 zones - 40 heat or 20 smoke detectors per...

  • Page 22

    O & m -v 5 -f a p -a v f -l c d r 0 o p e ra to r’s m a n u a l ( f ire a la rm p a n e l c /w a v f & l c d ) p g 2 1 o f 2 1 1 z1 + - 2 - + z2 3 4 - + z3 5 6 - + z4 7 8 - + z5 9 10 - + z6 11 12 - + z7 13 14 - + z8 15 16 - + alm-1 17 18 - + alm-2 19 20 c+ nc- aux-1 21 22 23 no- c+ aux-1 24 no- nc- ...