Vanner BRAVO 1050 Owner's Manual

Manual is about: Inverter/Battery Charger

Summary of BRAVO 1050

  • Page 1

    Bravo 1050 inverter/battery charger table of contents introduction ................................................... 2 general description ................................... 2 specifications ............................................ 3 installation: hardwire units .......................... 4 o...

  • Page 2

    Page 2 of 12 introduction thank you for purchasing a vanner bravo power inverter/battery charger. We are confident that you will be very pleased with its performance. Vanner inverter/battery chargers are designed and manufactured by skilled professionals using the highest standards in workmanship. W...

  • Page 3

    Page 3 of 12 specifications inverter model # qbc10-12 qbc10-24 output at 120 vac-continuous 1050 watts surge capacity at 120 vac (3 secs) 2100 watts input voltage, vdc (deep cycle battery recommended) 12 vdc, nominal, 10.5 vdc min.,16.0 vdc max. 24 vdc, nominal, 21.0 vdc min.,32.0 vdc max. Output vo...

  • Page 4

    Page 4 of 12 installation: hardwired units caution! Battery input cables must be connected to the battery with proper polarity as instructed or damage to the inverter may occur. 1. The unit should be off before installation begins. Make sure the on-off/reset inverter switch is in the off-reset posit...

  • Page 5

    Page 5 of 12 operation: hardwired units 1. With installation complete, apply ac input power to the unit. The charger will activate automatically, and either the charge or ready lamp will light depending on battery status. The unit is now charging the battery. 2. Apply an ac load with utility power p...

  • Page 6

    Page 6 of 12 back panel.

  • Page 7

    Page 7 of 12 installation: gfci receptacle units caution! Battery input cables must be connected to the battery with proper polarity as instructed or damage to the inverter may occur. 1. The unit should be off before installation begins. Make sure the on-off/reset inverter switch is in the off-reset...

  • Page 8

    Page 8 of 12 operation: gfci receptacle units 1. With installation complete, plug the ac input power cord into a utility power outlet. The charger will activate automatically, and either the charge or ready lamp will light depending on battery status. The unit is now charging the battery. 2. Apply a...

  • Page 9

    Page 9 of 12 front panel back panel.

  • Page 10

    Page 10 of 12 troubleshooting symptom solution on lamp does not light fully after pushing in the on- off reset inverter switch. • if utility power is present, lamp will only flash • if utility power off, check battery connections • if utility power off, check dc fuses on lamp lights fully but ac loa...

  • Page 11

    Page 11 of 12 options remote panel provides on/off control and status monitoring. Remote has 3 leds to indicate present status. The red led lights when a fault occurs, the yellow when charging is in progress, and the green when the inverter is on or in load demand. Gfci test record for maximum prote...

  • Page 12

    Page 12 of 12 limited warranty north american limited warranty vanner inc., referred to herein as vanner, warrants that this product is free from defects in materials and workman- ship for a period of two (2) years from date of installation or two and one half (2 1/2) years from date of manufacture,...