Configuration Menu
Decription
HART Address
METT's short address on HART bus. Set to 5 to use with MFT.
Address 14 is reserved for Handheld Interface dumb terminal
mode. (0-13 and 15 are valid)
Serial Number
Used for long address in multi-drop HART. Usually set at the
factory. If problems communicating, try setting to same as HART
address above.
Temp Units
Temperature units used for display. Use F2/F3 keys select.
Level Units
Level units used for display. Use F2/F3 keys to select.
Damping Value
Amount of damping. (0-16 is valid. 0 is minimal damping, 16 is
maximum damping)
Noise Reject
Type of noise rejection. 50 Hz/60 Hz are valid. Use F2/F3 keys to
select.
Temp Type: API Avg
Bulb/Avg Bulb/Multi-
Spot
Type of temperature system connected. API Avg Bulb/Avg Bulb/
Multi-Spot are valid. Use F2/F3 keys to select.
Temp Element Type
Type of temperature element used. Can be copper or platinum.
Use F2/F3 keys to select.
Bottom Probe Type
None/Installed
Indicates if bottom probe is installed. Use F2/F3 keys to select.
Bottom Probe Height
Height of installed bottom probe.
Top Probe Type: None/
Installed
Indicates if top probe is installed. Use F2/F3 keys to select.
Top Probe Height
Height of top probe.
Temp Elements
Number of temperature elements attached. (1 - 10 is valid)
Element 1 Height
Height/Length of element. The heights are ignored and over-
written if API average bulb is configured.
Element 2 Height
.
Element 3 Height
.
Element 4 Height
.
Element 5 Height
.
Element 6 Height
.
Element 7 Height
.
Element 8 Height
.
Element 9 Height
.
Element 10 Height
.
HART Variable 1 Type
Parameter to be returned as the first HART PV. Use F2/F3 to
select. No configuration required if used with Varec's MFT.
HART Variable 2 Type
Same as above for the second HART PV.
HART Variable 3 Type
Same as above for the third HART PV.
HART Variable 4 Type
Same as above for the fourth HART PV.