Varec Data Entry Terminal 8620 Installation and opertions Installation Manual

Summary of Data Entry Terminal 8620 Installation and opertions

  • Page 1

    Iom097gvae4012 automation solutions for oil & gas, defense and aviation applications installa tion and oper ations manual dispa tc h a nd fue ls accounting 8620 data entry terminal field interface used for data entry and process management at facility control points.

  • Page 3: Copyright

    Varec, inc. Iii copyright all rights reserved. Printed in the united states of america. Except as permitted under the united states copyright act of 1976, no part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means - electronic, mechanical, ...

  • Page 4: Disclaimer of Warranties

    Disclaimer of warranties the contract between the seller and the buyer states the entire obligation of the seller. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment, or relationship between the seller and buyer. There are no expres...

  • Page 5: Safety Precautions

    Safety precaution definitions caution! Damage to equipment may result if this precaution is disregarded. Warning! Direct injury to personnel or damage to equipment which can cause injury to personnel may result if this precaution is not followed. Safety precautions read this manual carefully and mak...

  • Page 6

    Vi installation and operations manual.

  • Page 7

    Varec, inc. Vii contents 1 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 functionality and syste...

  • Page 8

    Contents viii installation and operations manual.

  • Page 9

    8620 driver entry terminal varec, inc. 1 1 introduction this manual provides the information needed to install, maintain, and troubleshoot the varec 8620 driver entry terminal (det). 1.1 overview the 8620 det is a field interface device designed for data entry and process management at facility cont...

  • Page 10

    Introduction 2 installation and operations manual the 8620 det is constructed with the following assemblies as shown in figure 1-1: figure 1-1: 8620 det system components item qty description 1 1 17.50" x 14.92" enclosure with window kit 2 1 8.4" lcd 3 1 fingerprint scanner 4 2 4-key keypad 5 1 smar...

  • Page 11

    8620 driver entry terminal varec, inc. 3 1.2 functionality and system design figure 1-2: 8620 det system diagram load rack • preset blending control • preset additive injection control entry gate • access control • truck identity • truck status weigh scale • select order to load • configure compartm...

  • Page 12

    Introduction 4 installation and operations manual.

  • Page 13

    8620 driver entry terminal varec, inc. 5 2 preparing for installation this chapter provides a site preparation checklist, safety information, unpacking instructions, and installation instructions. 2.1 site preparation checklist before installing the 8620 det, ensure the following items: • the use of...

  • Page 14

    Preparing for installation 6 installation and operations manual before installing/repairing any wiring to the 8620 det, make sure that the power is turned off at the main circuit breaker or switch. The power switch should be locked in the off position and labeled to prevent other personnel from turn...

  • Page 15

    8620 driver entry terminal varec, inc. 7 figure 2-1 shows the dimensions of the 8620 det. Figure 2-1: 8620 det dimensions 12.00 14.28 16.75 17.50 13.00 16.28 6.44 5.70

  • Page 16

    Preparing for installation 8 installation and operations manual.

  • Page 17

    8620 driver entry terminal varec, inc. 9 3 wiring this chapter describes wiring requirements for the 8620 det. Wiring should be performed after the unit is installed. 3.1 overview field wiring of the 8620 det consists of the following: • power (ac/dc) • communications (rs-232, rs-485/422, or etherne...

  • Page 18

    Wiring 10 installation and operations manual figure 3-1: 8620 det ac wiring diagram note: din rail wiring: ac: p108-14-001: 14 awg, 300 v min., 105 °c, ul/csa-black p108-14-001: 14 awg, 300 v min., 105 °c, ul/csa-white dc: p108-50-001: 18 awg, 300 v min., 105 °c, ul/csa-black p108-50-003: 18 awg, 30...

  • Page 19

    8620 driver entry terminal varec, inc. 11 figure 3-2: 8620 det dc wiring diagram blk red fuse spar e fuse cpu boar d batt er y fuse holder blk red note: din rail wiring: dc: p108-50-001: 18 awg, 300 v min., 105 °c, ul/csa-black p108-50-003: 18 awg, 300 v min., 105 °c, ul/csa-red.

  • Page 20

    Wiring 12 installation and operations manual 3.1.1 power to connect dc or ac power to the 8620, connect the power wires to the appropriate terminals supplied with the 8620 det. Note before connecting power wires to the 8620 det, ensure that the power is switched off and that the 8620 det is correctl...

  • Page 21

    8620 driver entry terminal varec, inc. 13 digital i/o wiring four digital i/o modules can be installed in the 8620 det. Field wiring should be installed directly onto the digital i/o rack as shown in table 3-2 and table 3-3. Ethernet wiring the 8620 det has two 100-base-t ethernet jacks. One is loca...

  • Page 22

    Wiring 14 installation and operations manual.

  • Page 23

    8620 driver entry terminal varec, inc. 15 4 configuration figure 4-1: j3 on the single board computer configuring the 8620 det consists of the following: • configuring the rs-232 com port (com 1, 2, 3, and 4) • configuring the rs-485/422 or rs-232 com port (com 2) • configuring the det.Config file n...

  • Page 24

    Configuration 16 installation and operations manual 4.1 configuring the det.Config file the det.Config file is found on the “local drive” directory in the single board computer. The values are edited to configure the det. Note be aware that making direct edits to the det.Config file can result in im...

  • Page 25

    8620 driver entry terminal varec, inc. 17 variables description values value notes hostinterfacetype sets the host interface to either serial or network network serial default touchscreen configures det software for touchscreen interface (currently touchscreen not supported) true false default watch...

  • Page 26

    Configuration 18 installation and operations manual.

  • Page 27

    8620 driver entry terminal varec, inc. 19 5 maintenance and troubleshooting 5.1 maintenance maintenance should be performed only by authorized personnel. Figure 5-1: 8620 det assembly diagram 1 18 2 3 6 5 7 11 17 16 13 19 12 14 8 9 20 15 4 10 4.

  • Page 28

    Maintenance and troubleshooting 20 installation and operations manual item part no. Quantity description 1 8620scr 1 smart carder reader 2 p14-08620 1 card reader gasket 3 8620fpr 1 biometric fingerprint scanner w/gasket 4 14001586 1 det enclosure including window kit 5 200008624 2 4-key keypads w/g...

  • Page 29

    8620 driver entry terminal varec, inc. 21 5.2 troubleshooting figure 5-2: leds and switch 7 on the varec interface board 5.2.1 using local diagnostics (led indicators) refer to figures 5-2 to locate the 8620 det switch 7 (sw7) and led indicators. 1. If sw7 is up, port 4 is available as a usb port. 2...

  • Page 30

    Maintenance and troubleshooting 22 installation and operations manual 5.2.2 replacing the main circuit fuse ! Warning explosion hazard. To prevent an electrical shock or ignition of a flammable atmosphere, do not remove or replace the main circuit board fuse while the circuit is live. 1. Turn off th...

  • Page 31

    8620 driver entry terminal varec, inc. 23 5.2.4 replacing the battery ! Warning there is a danger of a new battery exploding if it is incorrectly installed. Do not attempt to recharge, force open, or heat the battery. Replace the battery only with the same or equivalent type recommended by the manuf...

  • Page 32

    Maintenance and troubleshooting 24 installation and operations manual 5.2.5 8620 det voltage monitor the voltage monitor monitors the input voltage and detects whether the voltage is low or below an acceptable level (for dc units only). The voltage monitor led indicates the different states of the i...

  • Page 33

    8620 driver entry terminal varec, inc. 25 6 specifications 6.1 general 6.2 system components manufacturer varec, inc. Atlanta, ga usa designation 8620 driver entry terminal (det) function field interface device used to control access to different control points single board computer • expansion inte...

  • Page 34

    Specifications 26 installation and operations manual 6.3 host communication 6.4 environmental smart card reader • dual reader technology: •iclass •proximity • 64-bit authentication keys • programmable led/beeper operation • read range is dependant upon which card is used: •min. 1.0" (2.5 cm) to max....

  • Page 35

    8620 driver entry terminal varec, inc. 27 6.5 electrical 6.6 mechanical construction 6.7 certifications and approvals operating voltage ac or dc • 24 – 48 vdc • 100 – 240 vac line to neutral 50/60 hz power consumption dc • 1a @ 24 vdc power consumption ac • 175ma @ 110 vac enclosure type rated nema ...

  • Page 36

    Specifications 28 installation and operations manual.

  • Page 37

    Data entry terminal varec, inc. 29 7 ordering information 7.1 order codes approvals fm factory mutual approvals (cfmus) class i, division 2, groups c and d, t4 class i, zone 2, t4 power supply - input 1 dc 2 ac enclosure heater a none digital i/o 0 none 1 single dry contact output 2 single dc output...

  • Page 38

    Ordering information 30 installation and operations manual.

  • Page 40

    Varec, inc. • 5834 peachtree corners east, norcross (atlanta), ga 30092 usa tel: +1 (770) 447-9202 • fax: +1 (770) 662-8939 www.Varec.Com © 2006 varec, inc. All rights reserved. This document is for information purposes only. Varec, inc. Makes no warranties, express or implied, in this summary. The ...