    Tcy-ft-u temperature pid controller doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 1 subject to alteration tcy-ft-u series intelligent temperature controller features • temperature pid control for hvac systems. • up to two 3-point outputs for 24vac actuators. • 1 internal ...

  • Page 2

    Tcy-ft-u technical specifications doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 2 subject to alteration technical specifications power supply operating voltage 24 v ac ± 10 %, 50…60 hz, class 2, 48va max power consumption max. 1.5 va electrical connection terminal connect...

  • Page 3

    Tcy-ft-u technical specifications doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 3 subject to alteration connection diagram description: g0 0v power supply: 0vac, internally connected to signal common g 24v power supply: 24vac m 0v signal common: common 0 potential for ana...

  • Page 4

    Tcy-ft-u operation instructions doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 4 subject to alteration display and operation operation mode comfort (occupied) all control functions operating per set points. Economy (unoccupied): set points shifted according to parameters c...

  • Page 5

    Tcy-ft-u configuration doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 5 subject to alteration configuration parameters for firmware version 1.2 the tcy-ft-u is preset to work for most applications. For special requirements it can be fine tuned to work ideally with a simple...

  • Page 6

    Tcy-ft-u configuration doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 6 subject to alteration control functions (password 241) warning! Only experts should change these settings! See user parameters for login procedure. Control configuration parameter description range def...

  • Page 7

    Tcy-ft-u configuration doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 7 subject to alteration output configuration parameter description range default cp 12 manual override mode: allows manual control of the floating outputs for using the controller as positioner or during...

  • Page 8

    Tcy-ft-u configuration doc: 70-00-0128b, v1.2, 20110621 © vector controls gmbh, switzerland page 8 subject to alteration input configuration parameter description range default cp 18 configuration of remote input (x1) 0 = control input 1 = comfort/economy mode switch 2 = comfort/off mode switch 3 = ...