Vector TCY3-T0121R Manual

Manual is about: TCY3-T0121R Series Intelligent Compact Controller

Summary of TCY3-T0121R

  • Page 1

    Tcy3-t0121r tcy3-t0121r series intelligent compact controller features • temperature control for 2-pipe, 4-pipe hvac systems. • -h version: humidity control with integrated humidity sensor • universal pid and binary control for any analog input/output signal and range • 4 independent pid sequences, ...

  • Page 2

    Tcy3-t0121r technical data name c y t t 0 1 2 1 h (- ) u (- ) d (- ) - 3 r deluxe version 2” x 4” housing integrated humidity sensor relays for binary outputs number of analog outputs (ao) = 1 number of binary output (do) = 2 number of analog inputs (ai) = 1 number of binary inputs (di) = 0 with ext...

  • Page 3

    Tcy3-t0121r technical data technical specifications doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 3 subject to alteration power supply operating voltage 24 v ac/dc ± 10 %, 50…60 hz power consumption max. 3 va electrical connection terminal connectors, wire 0.34…2.5 mm 2 (awg...

  • Page 4

    Tcy3-t0121r technical data doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 4 subject to alteration selection of actuators and sensors temperature sensors: use only our approved ntc sensors to achieve maximum accuracy. Recommended is sdb-tn10-20 as duct sensor, sra- tn10 as roo...

  • Page 5

    Tcy3-t0121r installation doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 5 connection terminals and jumpers terminal-description: 1. Connection for power-supply (24 v ac/dc, ±10%). In case of dc, connect the negative power- terminal. Common connection for analog in- and output...

  • Page 6

    Tcy3-t0121r operation display and operation the operation terminal uses an lcd display and four operation buttons. 2 legend: 1. 4-digit display of current value, time, control parameter or set point 2. Unit of displayed value, °c, °f, % or none 3. Graphical display of output or input value with a re...

  • Page 7

    Tcy3-t0121r operation operation of the terminal unit switching on the unit is switched on by pressing the power button. It will start up in comfort mode. Changing between comfort and standby pressing the power button for less than 2 seconds toggles between standby and comfort modes. Standby mode may...

  • Page 8

    Tcy3-t0121r operation accessing advanced settings pressing the option button for more than three seconds will start the advanced setup menu. The large lcd digits display sel. The advanced setup menu clock setup, time schedules, heat / cool change for 2 pipe systems. The menu may be left by pressing ...

  • Page 9

    Tcy3-t0121r operation operation with opr-1 the deluxe version may also be operated through an infrared remote controller. 1. Mode indication, auto, dry, cool, fan, heat 2. 2-digit display of setpoint 3. Fan indication 4. 4-digit display of current time or delayed switching time 5. Standby button: to...

  • Page 10

    Tcy3-t0121r operation doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 10 subject to alteration setting of parameters the tcy3 is an intelligent controller and can be adapted to fit perfectly into your application. The control operation is defined by parameters. The parameters ...

  • Page 11

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 11 subject to alteration control functions lp1: temperature control loop: signal input: either internal or external passive temperature probe lp2: universal control loop: signal input: analog input ...

  • Page 12

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 12 subject to alteration pid-control each loop has one reverse (heating) and one direct (cooling) acting pid sequence. Legend: t, u input signal x ph p-band heating, direct x pc p-band cooling, reve...

  • Page 13

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 13 subject to alteration binary control each loop has three reverse- (heating) and three direct- (cooling) acting binary sequences. The offset to the setpoint is adjustable for each sequence. The sw...

  • Page 14

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 14 subject to alteration temperature input accuracy in kelvin, temperature inp 0.2 ut 0 50 100 t °c the tcy3 includes an ntc-based passive temperature sensor. A sensor of the same type can be connec...

  • Page 15

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 15 subject to alteration output configuration general an output must be assigned to a function or a control loop using the op parameter set. Assigning an output to a control function will automatica...

  • Page 16

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 16 subject to alteration binary outputs if op11 is in the off position, do1 and do2 may be used as binary outputs. They may be used for binary sequences or other special functions: additional functi...

  • Page 17

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 17 subject to alteration configuration of controller proceed in the following steps in order to adapt the controller to its application: 1. Set jumpers for inputs and outputs 2. Connect power supply...

  • Page 18

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 18 subject to alteration control parameters temperature input (loop 1) parameter description range default 1l 00 standby set point shift 0…100° 5.0°c (10°f) 1l 01 minimum set point limit for heating...

  • Page 19

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 19 subject to alteration control parameters analog input parameter description range default 2l 00 standby set point shift acc input 0% 2l 01 minimum set point limit for reverse acc input 0% 2l 02 m...

  • Page 20

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 20 subject to alteration temperature input configuration parameter description range default ip 00 ti1: control input of loop 1: off = internal sensor on = external sensor on, off off ip 01 ti1: sam...

  • Page 21

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 21 subject to alteration humidity sensor configuration (-h version) parameter description range default ip 30 humidity sensor is control input of loop 2 on, off off ip 31 humidity sensor calibration...

  • Page 22

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 22 subject to alteration floating output parameter description range default op 11 fo1: enable floating output (do1, do2 floating) off = do1, do2 are two binary outputs on = do1, do2 are one floatin...

  • Page 23

    Tcy3-t0121r engineering manual doc: 70-000002 v1.0, 20101115 © vector controls gmbh, switzerland page 23 subject to alteration digital output 1 parameter description range default op 18 do1: configuration digital output (only if floating disabled) 0 = off 1 = loop 1 2 = loop 2 3 = dehumidifying, max...